MEDICS® includes::
AC and 3(N) AC changeover and monitoring modules. Examples of modules in the MEDICS®
system include UMC..., USC..., UFC... and EDS.... insulation fault location systems.
Display and operating units such as alarm indicator and operator panels or alarm indicator and test
combinations.
Communication between these components takes place via the BMS bus (two-wire connection).
The connection of third-party technical equipment by means of protocol converters (gateways), via
digital inputs and relay outputs.
The real strength of MEDICS® is to be found in communication between all involved components and the
resulting information provided to the user. Readiness for operation is monitored constantly; and operating
states, irregularities, faults and equipment failures are displayed. From the user's point of view, this means
high operational reliability.
3.2. Example applications
3.2.1. Example application operating theatre
UMA710 Module, Changeover between the preferred and redundant line while monitoring the
medical IT system with transformer load and temperature monitoring
IR426-D47: Monitoring the operating theatre light IT system (optional)
MK2430 / MK800 / TM800: Alarm for at least two points with independent power supplies for
functional safety