![Bender ATICS-2-63A-ISO Manual Download Page 84](http://html1.mh-extra.com/html/bender/atics-2-63a-iso/atics-2-63a-iso_manual_2731578084.webp)
84
ATICS-2-ISO_D00046_04_M_XXEN / 03.2021
Troubleshooting
Fault/message
Description
Action
Device error +
error code
For details about actions to be taken, refer to table section "Error code/service code“.
The message is on channel 6 of the BMS bus.
Short circuit distribu-
tion board
Short circuit detected
Eliminate short circuit
Failure distribution
board
No voltage on line 3, contact of the change-
over switch defective. The fault can also be
caused by an (impermissible) connection
between GND, k or l and PE.
• Replace ATICS®.
• Separate connection between GND,
k or l and PE.
Overcurrent I(3)
Overcurrent detected by measuring current
transformer STW3
• Eliminate cause of overcurrent.
• Eliminate any damage.
CT connection
Short circuit or interruption of connecting
wire has been detected. Measuring current
transformer STW3, channel 7
• Check connecting wire of measuring
current transformer.
No master
There is no device with master function or
back-up master (device with address "1")
available on the RS-485 interface
• Check BMS bus connection.
• Check whether the master has failed
or whether its address has changed.
If the device is operated without a
BMS bus, the "Failure monitoring"
(see chapter „Settings menu 9: Inter-
face“ on p. 77) must be disabled.
Service by __
(date)
Reminder for next service
• Schedule appointment with the
Bender service.
Functional test
by __ (date)
Reminder for next test
• Schedule appointment for next test.
• Perform test.
Manual mode
Message "Manual mode" although manual
mode has not been enabled
• Check the connections of the digital
input
Error during
changeover process
Occurs when the test set-ups do not supply
sufficient current for switching the coils of
the ATICS®.
• Only use test set-ups that provide
the necessary peak current of 17 A.
Summary of Contents for ATICS-2-63A-ISO
Page 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Page 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Page 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Page 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Page 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...