ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 73
ATICS-2-63A-ISO
Adjusting the settings:
Menu
Description
Exit
Exit settings menu "Relay"; go up one menu level
1. Function
ALARM Relay switches if at least one of the following menus 3…12 is
set to "on" and the corresponding alarm message appears.
Active
Relay switches if at least one of the following menus 3…10
is set to "on" and the corresponding alarm message does
not
appear (operating message). If several of these menus are set to
"on", none of them must have an alarm in order to be able to activate the
relay.
Application example
:
Function = "Active"
Line 1 = "on", all other menus (line 2, device error, etc.) are set to "off".
-> Relay is activated when line 1 is ready for operation.
GenSt
Relay is used as a generator start relay
2. Relay mode
N/O operation. Relay only switches in the event of an alarm.
N/C operation. Relay only switches in the event of an alarm.
N/O-T operation. Relay switches in the event of an alarm or a test.
N/C-T operation. Relay switches in the event of an alarm or a test.
3. Line 1
on
Line 1
off
4. Line 2
on
Line 2
off
5. Manual mode
on
Relay switches in manual mode (transparent cover open or digital input
"Manual mode" selected).
off
6. Device error
on
Internal device error 1.x, 3.x (except 3.50), 6.x, 7.x, 8.x, 9.x or BMS bus has
no master, short-circuit distribution board, failure distribution board.
off
7. Test interval
on
Relay switches when a test is due (interval elapsed).
off
8. Serviceinterv.
on
Relay switches when service is due (interval elapsed).
off
9. Dig. input
on
Alarm digital input. To ensure that the relay responds to the digital input,
the functions "ALARM" or "R-OPL" must be additionally set in the "Settings
-> Digital Input" menu.
off
10. Insulation
on
Relay switches in the event of an insulation fault
off
11. Load
on
Relay switches in the event of overload in the IT system
off
Summary of Contents for ATICS-2-63A-ISO
Page 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Page 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Page 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Page 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Page 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...