ATICS-2-ISO_D00046_04_M_XXEN / 03.2021 19
ATICS-2-63A-ISO
3.5.1.1 Time diagram: Changeover between preferred and redundant line
i
Time diagrams: Times are not shown to scale.
Example: Line 1 is set as preferred line.
Changeover to line 2
if line 1 has failed
Switching back to
line 1 (normal operation with delay on release)
Switching back to line 1
(if line 2 has failed)
Voltage line 1
Voltage line 2
Voltage output
ATICS®
Alarm failure line 1
Alarm failure line 2
Switch position
Time delay
t(pulse)
Pulse time: 15 … 30 ms
t(0)
Dead time
t(on)1
Response delay ALARM failure voltage line 1
Measuring time:
approx. 50 ms
t(off)1
Delay on release ALARM failure voltage line 1
Measuring time:
approx. 50 ms
t(on)2
Delay on release ALARM failure voltage line 2
Measuring time:
approx. 50 ms
t(2->1)
Return transfer delay time
*1
Changeover period t(1->2) indicated during a test
*2
The return transfer delay time may differ from the changeover period (t(1->2)
t(off)
1
0
2
t(on)
1
t(Imp)
t(0)
t(Imp)
1
t(Imp)
t(0)
t(Imp)
0
2
1
t(off)
1
t(Imp)
t(0)
t(Imp)
2
0
1
t(2->1)
t(2->1)
t(on)
2
*1
*2
Summary of Contents for ATICS-2-63A-ISO
Page 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Page 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Page 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Page 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Page 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...