44
ATICS-2-ISO_D00046_04_M_XXEN / 03.2021
Mounting and connection
4.3.2 Manual mode
I
r
isk
of injury from rotating Allen key.
When the transparent cover is closed, the ATICS® is in automatic mode. The ATICS® detects this by the
button being pressed under the transparent cover. When the transparent cover is opened, the button
is no longer pressed and the ATICS® switches to manual mode. When the transparent cover is open,
make sure that this button is not pressed accidentally. Check and make sure that the message
"Manual mode" appears on the display. Only then can the Allen key be used to set the changeover
switch to manual mode.
Enabling manual mode
Variant A: Open the transparent cover. Set the digital input. "M/A" function must be set
(see chapter „Settings menu 6: Dig. input“ on p. 74).
Variant B: Place the handle on the Allen key, use the Allen key to switch over.
4.3.3 Lock transfer switching and monitoring device with a padlock
1. Pull out locking device.
2. Insert padlock and close it.
It is only possible to lock the switch in manual mode (transparent cover open). The locking device can
only be locked in switch position "0". Padlock shackle diameter: 4 mm…8 mm (3/16”…5/16”). The
switch position cannot be changed until the lock has been removed and the locking device has been
pushed in.
A
B
Summary of Contents for ATICS-2-63A-ISO
Page 10: ...10 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Intended use...
Page 12: ...12 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 System description...
Page 21: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 21 ATICS 2 63A ISO...
Page 41: ...ATICS 2 ISO_D00046_04_M_XXEN 03 2021 41 ATICS 2 63A ISO...
Page 82: ...82 ATICS 2 ISO_D00046_04_M_XXEN 03 2021 Troubleshooting...