8
In this configuration the AVR is powered directly from
the generator output (or from an auxiliary winding).
The AVR DC output is feeding the stator of the exciter.
In this configuration the AVR is powered from a PMG.
The AVR DC output is feeding the stator of the exciter.
This configuration shows a possible replacement of a
Direct Current excitation machine.
SM: Synchronous Machine E: Exciter PMG: Permanent-Magnet-Generator D:Direct Current machine
2.6 Basic Insertion Configurations
The following SLD show some basic insertion configurations of the S2014.
SM
E
AVR
S2014
Vsense
Ig
Power
SM
D
AVR
S2014
Vsense
Ig
Power
SM
PMG
E
AVR
S2014
Vsense
Ig
Power
BELTRAME
CENTRO SERVIZI ENERGIA
Summary of Contents for S2014
Page 1: ...Rev 4 0 BELTRAME CENTRO SERVIZI ENERGIA...
Page 2: ......
Page 40: ...39 BELTRAME CENTRO SERVIZI ENERGIA...