4. OPERATING MODES
S2014 allows bump less changeover between all operation modes:
Automatic voltage regulator (AVR)
It regulates the output voltage of the synchronous machine.
Note: Output Generator Current measurement is optional: it is
used only for droop compensation
Field Current Regulation (FCR)
It regulates the excitation (field) current of the synchronous
machine.
This operation mode is quite useful during commissioning and/or
troubleshooting.
PF or Var regulation (PF, Var)
Regulates the power factor or reactive power of the
synchronous machine.
Note: these functions are available only if the machine
is working in parallel (and with closed 52G signal)
SM
E
PID
PF
kVar
SM
E
PID
BELTRAME
CENTRO SERVIZI ENERGIA