background image

90

J20741 - Subject to change. © Belimo Aircontrols (USA), Inc.

®

If the shaft extends at least 3/4” from the duct, follow these
steps:

1. (See Fig. D) Move damper blades to the fail-safe position (a).
2. Determine the best orientation for the universal clamp on the

back of the actuator. The best location would be where you
have the easiest access to the V bolt nuts on the clamp.

3. Engage the clamp to the actuator as close as possible to

the determined location.

4. Lock the clamp to the actuator using the retainer clip.
5. Mount the spring return actuator to the shaft.  Tighten the

universal clamp, finger tight only.

6. Mount the anti-rotation strap at the base of the actuator.

Do not tighten the screws.

7. Remove the screw from one end of the mounting bracket

and pivot it away from the actuator.

8. Loosen the universal clamp and, making sure not to move

the damper shaft, rotate the actuator approximately 5° in
the direction which would open the damper.

9. Verify that the damper is still in its full fail-safe position.

10. Tighten the universal clamp to the shaft.
11. Rotate the actuator to apply pressure to the damper seals

(b) and re-engage the anti-rotation strap (c).

12. Tighten all fasteners.
13. Use IND-LF accessory if position indication is needed.

Installation Instructions

Short Shaft Mounting with IND-LF Position Indicator / Airtight Damper Procedure

Initialization of the LF24-SR US and LF24-MFT… US
When power is applied, the internal microprocessor recog-
nizes that the actuator is at its full fail-safe position and
uses this position as the base for all of its position calcula-
tions. This procedure takes approximately 15 seconds.
During this time you will see no response at the actuator.
The microprocessor will retain the initialized zero during
short power failures of up to 25 seconds. When power is
applied during this period, the actuator will return to normal
operation and proceed to the position corresponding to the
input signal provided.  For power failures over 25 seconds,
the actuator will be at it fail-safe position and will go through
the start up initialization again.

Motor position detection
Belimo brushless DC motors eliminate the need for poten-
tiometers for positioning.  Inside the motor are three “Hall
Effect” sensors.  These sensors detect the spinning rotor
and send pulses to the microprocessor which counts the

pulses and calculates the position to within 1/3 of a revolu-
tion of the motor.  

Overload protection
The LF, on-off actuators are electronically protected against
overload.  The LF, On-off actuators have an internal current
limiter  which maintains the current at a safe level which will
not damage the actuator while providing adequate holding
torque.

The LF24, modulating actuators (LF24-SR US, LF24-3 US,
LF24-MFT US) are protected against overload by digital tech-
nology located in the ASIC. The ASIC circuitry constantly mon-
itors the rotation of the brushless DC motor inside the actuator
and stops the pulsing to the motor when it senses a stall con-
dition.   The motor remains energized and produces full rated
torque during stall conditions.  The actuator will try to move in
the direction of the stall every 2 minutes, for a period of 32
minutes.  After this, the actuator will try again every 2 hours.

Operational Information for LF24-SR US and LF24-MFT… US Actuators

min 3/4”

[20]

IND-LF Position Indicator

(optional)

Fig. D

0

1

2

4

5

6

7

8

9

L

C

b

c

a

.2

.4

.6

.8

1

CW

0

®

Short Shaft
Mounting

Short Shaft
Mounting

Summary of Contents for LF120 US

Page 1: ...s adjustable between 0 and 95 Dimensions All numbers in brackets are in millimeters LF120 S US LF230 S US On off Spring Return Fail Safe 120 230 VAC Technical Data LF120 S US LF230 S US Power supply 120 VAC 10 230 VAC 10 50 60 Hz 50 60 Hz Power consumption running 5 5 W 5 W holding 3 5 W 3 W Transformer sizing 7 5 VA 7 VA Electrical connection 3 ft 18 GA appliance cable S models have 2 cables 1 2 ...

Page 2: ... tion Actuators shall be protected from overload at all angles of rotation If required 1 SPDT auxiliary switch shall be provid ed having the capability of being adjustable Actuators must be constructed to meet the requirements for Double Insulation so an electrical ground is not required to meet agency listings Actuators shall be UL listed and CSA certified have a 5 year warranty and be manufactur...

Page 3: ...6 1 is required Installation Instructions Quick Mount Visual Instructions min 3 1 2 90 min 3 1 2 90 min 3 4 20 IND LF Position Indicator optional min 3 4 20 IND LF Position Indicator optional 1 Rotate the damper to its failsafe position If the shaft rotates counterclockwise mount the CCW side of the actuator out If it rotates clockwise mount the actuator with the CW side out 2 If the universal cla...

Page 4: ...he universal clamp finger tight only 7 Mount the anti rotation strap at the base of the actuator Do not tighten the screws 8 Remove the screw from one end of the mounting bracket and pivot it away from the actuator 9 Loosen the universal clamp and making sure not to move the damper shaft rotate the actuator approximately 5 in the direction which would open the damper 10 Tighten the universal clamp...

Page 5: ... seconds During this time you will see no response at the actuator The microprocessor will retain the initialized zero during short power failures of up to 25 seconds When power is applied during this period the actuator will return to normal operation and proceed to the position corresponding to the input signal provided For power failures over 25 seconds the actuator will be at it fail safe posi...

Page 6: ...ows an increasing or decreasing control signal with a 80 mV resolution If the signal changes in the opposite direction the actuator will not respond until the control signal changes by 200 mV This allows these actuators to track even the slightest deviation very accurately yet allowing the actuator to wait for a much larger change in control signal due to control signal instability Control Accurac...

Page 7: ...es the switch indicator moves from 6 60 toward 0 0 When the indicator passes 0 the switch contact between S1 and S2 is broken and the con tact between S1 and S3 is made Auxiliary Switches 8 6 4 2 0 1 S1 S2 S3 S1 S2 S3 Non direct Mounting Methods KH LF crankarm including retaining ring KH LF For shafts up to 1 2 ZG 112 pushrod not supplied with kit KG6 ball joint and universal crankarm not included...

Page 8: ...ed by the same control signal may be powered from multiple transformers provided the following rules are followed 1 The transformers are properly sized 2 All No 1 wires from all actuators are tied together and tied to the negative leg of the control signal See wiring diagram Wire Length for LF Actuators Keep power wire runs below the lengths listed in the table in Fig A If more than one actuator i...

Page 9: ...ate Damper will go from fully closed to fully open Torque requirement is actua tor s minimum torque Gives Expected Response Go To Step Actuator operates properly Step 8 Power wiring correct ed actuator begins to drive Step 1 Actuator operates properly Step 8 Actuator operates properly Step 8 Controller output actuator input is correct Input Polarity Correct Step 6 Damper moves properly Step 7 Defe...

Reviews: