Installation Instructions

The …-S model actuators are equipped with an adjustable
auxiliary switch used to indicate damper position or to inter-
face additional controls or equipment.  Switching positions can
be set over the full 0 to 95° rotation simply by setting a switch
on the actuator.

1. Set desired switch position. (Example 60%)
2. As the actuator rotates, the switch indicator moves from .6

(60%) toward 0 (0%).  When the indicator passes 0 the
switch contact between S1 and S2 is broken and the con-
tact between S1 and S3 is made.

Auxiliary Switches

.8

.6

.4

.2

0

1

S1

S2

S3

S1

S2

S3

Non-direct Mounting Methods

KH-LF crankarm including retaining ring.  

KH-LF
For shafts up to 1/2”

ZG-112

(pushrod not supplied with kit)

KG6 ball joint and

universal crankarm

(not included)

KG6 ball joint

(not included)

KH-LF
crankarm

KH-LF
crankarm

ZG-LF2 
Crankarm adaptor kit 

ZG-LF112 
Crankarm adaptor kit

Voltage

Resistive load

Inductive load

120 VAC

3 A

1.03 A

250 VAC

3 A

0.5 A

Switch Rating

Summary of Contents for LF120 US

Page 1: ...s adjustable between 0 and 95 Dimensions All numbers in brackets are in millimeters LF120 S US LF230 S US On off Spring Return Fail Safe 120 230 VAC Technical Data LF120 S US LF230 S US Power supply 120 VAC 10 230 VAC 10 50 60 Hz 50 60 Hz Power consumption running 5 5 W 5 W holding 3 5 W 3 W Transformer sizing 7 5 VA 7 VA Electrical connection 3 ft 18 GA appliance cable S models have 2 cables 1 2 ...

Page 2: ... tion Actuators shall be protected from overload at all angles of rotation If required 1 SPDT auxiliary switch shall be provid ed having the capability of being adjustable Actuators must be constructed to meet the requirements for Double Insulation so an electrical ground is not required to meet agency listings Actuators shall be UL listed and CSA certified have a 5 year warranty and be manufactur...

Page 3: ...6 1 is required Installation Instructions Quick Mount Visual Instructions min 3 1 2 90 min 3 1 2 90 min 3 4 20 IND LF Position Indicator optional min 3 4 20 IND LF Position Indicator optional 1 Rotate the damper to its failsafe position If the shaft rotates counterclockwise mount the CCW side of the actuator out If it rotates clockwise mount the actuator with the CW side out 2 If the universal cla...

Page 4: ...he universal clamp finger tight only 7 Mount the anti rotation strap at the base of the actuator Do not tighten the screws 8 Remove the screw from one end of the mounting bracket and pivot it away from the actuator 9 Loosen the universal clamp and making sure not to move the damper shaft rotate the actuator approximately 5 in the direction which would open the damper 10 Tighten the universal clamp...

Page 5: ... seconds During this time you will see no response at the actuator The microprocessor will retain the initialized zero during short power failures of up to 25 seconds When power is applied during this period the actuator will return to normal operation and proceed to the position corresponding to the input signal provided For power failures over 25 seconds the actuator will be at it fail safe posi...

Page 6: ...ows an increasing or decreasing control signal with a 80 mV resolution If the signal changes in the opposite direction the actuator will not respond until the control signal changes by 200 mV This allows these actuators to track even the slightest deviation very accurately yet allowing the actuator to wait for a much larger change in control signal due to control signal instability Control Accurac...

Page 7: ...es the switch indicator moves from 6 60 toward 0 0 When the indicator passes 0 the switch contact between S1 and S2 is broken and the con tact between S1 and S3 is made Auxiliary Switches 8 6 4 2 0 1 S1 S2 S3 S1 S2 S3 Non direct Mounting Methods KH LF crankarm including retaining ring KH LF For shafts up to 1 2 ZG 112 pushrod not supplied with kit KG6 ball joint and universal crankarm not included...

Page 8: ...ed by the same control signal may be powered from multiple transformers provided the following rules are followed 1 The transformers are properly sized 2 All No 1 wires from all actuators are tied together and tied to the negative leg of the control signal See wiring diagram Wire Length for LF Actuators Keep power wire runs below the lengths listed in the table in Fig A If more than one actuator i...

Page 9: ...ate Damper will go from fully closed to fully open Torque requirement is actua tor s minimum torque Gives Expected Response Go To Step Actuator operates properly Step 8 Power wiring correct ed actuator begins to drive Step 1 Actuator operates properly Step 8 Actuator operates properly Step 8 Controller output actuator input is correct Input Polarity Correct Step 6 Damper moves properly Step 7 Defe...

Reviews: