ZIP Economizer
Alarms
Alarm from Sequences - MMI Display
ID
Alarm Text
1
OAT Sensor out of range economizing is disabled
2
OAT Sensor not detected economizing is disabled
3
OAH Sensor out of range economizing is disabled
4
OAH Sensor not detected economizing is disabled
5
OAH Sensor out of range operation by diff temp
6
OAH Sensor not detected operation by diff temp
7
RAT Sensor out of range operation by OAT dry bulb
8
RAT Sensor not detected operation by OAT dry bulb
9
RAT Sensor out of range operation by OAH enthalpy
10
RAT Sensor not detected operation by OAH enthalpy
11
RAH Sensor out of range operation by OAH enthalpy
12
RAH Sensor not detected operation by OAH enthalpy
13
RAH Sensor detected but OAH Sensor not detected
14
RAH Sensor detected but RAT Sensor not detected
15
SAT Sensor out of range economizing is disabled
16
SAT Sensor not detected economizing is disabled
17
Y2 present without Y1 single stage
18
SAT drop for CC1 insuffi cent cooling system problem
19
SAT drop for CC2 insuffi cent cooling system problem
20
Damper Pos value missing
21
SAT should be lower
22
Damper is stuck
23
Energy Module is missing module functions disabled
24
Exhaust fan not detected
25
Compressor 1 not detected
26
Compressor 2 not detected
27
2 Speed fan not detected
28
CO2 Sensor not detected DCV functions disabled
29
CO2 Sensor out of range DCV functions disabled
30
Heat and Cool both present