11
0
6/16 - Subject to change. © Belimo Air
controls
(USA
), Inc
.
Installation
Dimensions in Inches [mm]
Avoid mounting in areas where acid fumes or other deteriorating vapors
can attack the metal parts, or in areas where escaping gas or other
explosive vapors are present.
Mount the sensor in a position that will allow for proper clearance for
installation, servicing, wiring, and removal.
Using the dimensions as a reference, mount the 10K Sensor on the outside
of the dampers to measure outside temperature, or inside the return air
duct to measure the return temperature. If mounted outside, the sensor
must be placed within hood behind the outdoor air fi lter. It needs to be
protected from direct exposure to water (snow/rain) and direct exposure to
sunlight (UV radiation).
Secure the sensor with #8 self-tapping screws (included in kit) using a size
16 or 18 drill.
Wiring Diagram
ZIP Economizer Terminal inputs
SAT (+/-)
OAT (+/-)
RAT (+/-)
ECON-ZIP-10K
ECON-ZIP-10K
ZIP Economizer™ Temperature Sensor
Technical Data
Temperature output signal
NTC 10k Ohm, Type II
Connectors
1/4" female spade insulated connectors,
3 ft. cable
Accuracy
± 0.36°F,(± 0.2°C)
Stability drift
less than 0.036°F/yr [0.02°C/yr]
Material
etched Teflon, plenum-rated & FEP jacketed
cable; galvanized t-bracket
Ambient temperature range
-67°F to +176°F (-55°C to +80°C)