12
0
6/16 - Subject to change. © Belimo Air
controls
(USA
), Inc
.
Installation
Avoid mounting in areas where acid fumes or other deteriorating vapors
can disintegrate the metal parts of the module’s circuit board, or in areas
where escaping gas or other explosive vapors are present.
You must mount the sensor in a position that will allow for proper clearance
for installation, servicing, wiring, and removal.
Using the dimensions as a reference, mount the Temperature and Humidity
Sensor on the outside of the dampers to measure outside temperature and
humidity, or inside the return air duct to measure the return temperature
and humidity. If mounted outside, the sensor must be placed within hood
behind the outdoor air fi lter. It needs to be protected from direct exposure
to water (snow/rain) and direct exposure to sunlight (UV radiation).
The orientation of the sensor is critical to ensure optimal performance.
(Please see fi gures on recommended orientation.)
Ensure installation matches an approved orientation before securing with
#8 self-tapping screws (included in kit).
The electrical connection needs to be wired using appropriate insulated
spade connectors, ¼”female, according to the wiring diagram.
Wiring
Input/Output Specifications
Technical Data
Type
Name
Description
Electrical Specifi cation ZIP Terminal
Input
24V
Supply Hot
24 VAC, ± 20%,
50/60Hz
Same Power
Supply R
Output T(+/-)
Temperature
Type: 10K NTC
(Type II thermistor)
OAT (+/-);
RAT (+/-)
Output RH(+/-) Relative Humidity 0-10 VDC
OAH (+/-);
RAH (+/-);
ECON-ZIP-TH
ZIP Economizer™ Temperature and Humidity Sensor
Technical Data
Power Supply
24 VAC ± 20%, 50/60Hz, Class 2 power source
Current Consumption
Max. 5mA
Rated Impulse Voltage
800V
Connectors
1/4" male spade connectors
Environmental
RoHS conformally coated
Software Class
A
Control Pollution Degree
3
Temperature Sensor Type
NTC 10kOhm
Humidity
0 to 100% RH
Humidity Sensor Type
0-10VDC (0 to 100% RH) max load 10kOhm,
Class 2 limited energy
Housing
NEMA 1
Ambient Temperature Range
-40°F to +140°F (-40°C to +60°C)
Storage Temperature Range
-40°F to +158°F (-40°C to +70°C)
Accuracy
± 3% 35-65% rH @ 75°F
± 5% 0-34%, 66-100% rH @ 75°F
Response Time
<45 seconds @ 40 FPM, 75°F
Hysterisis
<2.5% rH
Long Term Stability
<1% rH/year
Agency Listing
UL60730-1,-2-9,-2-13. UL2043 compliant, CE
2004/108/EC "Electromagnetic compatibility
(EMC)", EN60730-1,-2-9 and-2-13
Dimensions
(Inches [mm])