800-543-9038
USA
866-805-7089
CANADA
203-791-8396
LATIN AMERICA / CARIBBEAN
77
WARNING
The wiring technician must be trained and experienced with electronic
circuits. Disconnect power supply before attempting any wiring connections or
changes. Make all connections in accordance with wiring diagrams and follow all
applicable local and national codes. Provide disconnect and overload protection as
required. Use copper, twisted pair, conductors only. If using electrical conduit, the
attachment to the actuator must be made with flexible conduit.
Always read the controller manufacturer's installation literature carefully
before making any connections.
Follow all instructions in this literature. If you
have any questions, contact the controller manufacturer and/or Belimo.
Transformers
The AFB24, AFX24…actuators require a 24 VAC class 2 transformer and draws a
maximum of 10 VA per actuator. The actuator enclosure cannot be opened in the
field, there are no parts or components to be replaced or repaired.
– EMC directive: 2004/108/EC
– Software class A: Mode of operation type 1
– Low voltage directive: 2006/95/EC
CAUTION:
It is good practice to power electronic or digital controllers from a
separate power transformer than that used for actuators or other end devices. The
power supply design in our actuators and other end devices use half wave
rectification. Some controllers use full wave rectification. When these two different
types of power supplies are connected to the same power transformer and the DC
commons are connected together, a short circuit is created across one of the diodes
in the full wave power supply, damaging the controller. Only use a single power
transformer to power the controller and actuator if you know the controller power
supply uses half wave rectification.
Multiple Actuators, One Transformer
Multiple actuators may be powered from one transformer provided the following rules
are followed:
1. The TOTAL current draw of the actuators (VA rating) is less than or equal to the
rating of the transformer.
2. Polarity on the secondary of the transformer is strictly followed.
This means that
all No. 1 wires from all actuators are connected to the common leg on the
transformer and all No. 2 wires from all actuators are connected to the hotleg.
Mixing wire No. 1 & 2 on one leg of the transformer will result in erratic operation
or failure of the actuator and/or controls.
Multiple Actuators, Multiple Transformers
Multiple actuators positioned by the same control signal may be powered from
multiple transformers provided the following rules are followed:
1. The transformers are properly sized.
2. All No. 1 wires from all actuators are tied together and tied to the negative leg of
the control signal. See wiring diagram.
Wire Length for AFB..., AFX... Actuators
Keep power wire runs below the lengths listed in the
Figure H
. If more than one
actuator is powered from the same wire run, divide the allowable wire length by the
number of actuators to determine the maximum run to any single actuator.
Example:
3 actuators, 16 Ga wire
350 Ft ÷ 3 Actuators = 117 Ft. Maximum wire run
MAXIMUM WIRE LENGTH FOR 10VA
Wire Size
Max. Feet.
Wire Size
Max. Feet
12 Ga
900 Ft.
18 Ga
220 Ft.
14 Ga
550 Ft.
20 Ga
120 Ft.
16 Ga
350 Ft.
22 Ga
60 Ft.
FIGURE H
Wire Type and Wire Installation Tips
For most installations, 18 or 16 Ga. cable works well with the AFB24, AFX24...
actuators. Use code-approved wire nuts, terminal strips or solderless connectors
where wires are joined. It is good practice to run control wires unspliced from the
actuator to the controller. If splices are unavoidable, make sure the splice can be
reached for possible maintenance. Tape and/or wire-tie the splice to reduce the
possibility of the splice being inadvertently pulled apart.
The AFB24, AFX24... proportional actuators have a digital circuit that is designed to
ignore most unwanted input signals (pickup). In some situations the pickup may be
severe enough to cause erratic running of the actuator. For example, a large
inductive load (high voltage AC wires, motors, etc.) running near the power or
control wiring may cause excessive pickup. To solve this problem, make one or
more of the following changes:
1. Run the wire in metallic conduit.
2. Re-route the wiring away from the source of pickup.
3. Use shielded wire (Belden 8760 or equal).
Ground the shield to an earth ground.
Do not
connect it to the actuator common.
Initialization of the -SR and -MFT
When power is initially applied, the actuator will first release its manual preload
position (This assumes a manual position has been set). The actuator will then rotate
to the full fail-safe position. At this point the microprocessor recognizes that the
actuator is at full fail-safe and uses this position as the base for all of its position
calculations. The microprocessor will retain the initialized zero during short power
failures of up to 20 seconds. The -SR and -MFT will also return to its position prior to
the 20-second-or-less power loss. For power failures greater than 20 seconds, the
actuator would naturally return to its full fail-safe position prior to the microprocessor
losing its memory. The actuator will also re-initialize if the manual position
mechanism is used.
Installation Instructions
General Wiring Instructions
N40103 - 09/11 - Subject to change.
© Belimo
Aircontrols (USA),
Inc
.