Accessories
Tool-06
8mm and 10 mm wrench
43442-00001
Gland (needed for additional wires)
11097-00001
Gasket for Gland (needed for additional wires)
NOTE:
When using AFBUP N4(H), AFBUP-S N4(H), AFXUP N4, AFXUP-S N4 actuators, only use
accessories listed on this page.
For actuator wiring information and diagrams, refer to Belimo Wiring Guide.
Typical Specification
On/Off spring return damper actuators shall be direct coupled type which require
no crank arm and linkage and be capable of direct mounting to a jackshaft up to a
1.05” diameter. The actuators must be designed so that they may be used for either
clockwise or counterclockwise fail-safe operation. Actuators shall be protected
from overload at all angles of rotation. If required, two SPDT auxiliary switch shall
be provided having the capability of one being adjustable. Actuators with auxiliary
switches must be constructed to meet the requirements for Double Insulation so
an electrical ground is not required to meet agency listings. Actuators shall be
cULus Approved and have a 5 year warranty, and be manufactured under ISO 9001
International Quality Control Standards. Actuators shall be as manufactured by Belimo.
AFBUP N4(H), AFBUP-S N4(H), AFXUP N4, AFXUP-S N4
NEMA 4, On/Off, Spring Return, 24 to 240 VAC
AFBUP N4(H)
AFBUP-S N4(H)
AFXUP N4
AFXUP-S N4
W
066
_AFBUP_N
4
On/Off Wiring
Wht
Blk
AFBUP-S N4(H)
AFXUP-S N4
W067
_
AFBUP-
S_
N
4
Auxiliary Switches
A
F-NF N4H 12
0
V h
ea
ter
NEMA 4 Heater
Wiring Diagrams
1
Provide overload protection and disconnect as required.
2
CAUTION
Equipment Damage!
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
3
No ground connection is required.
4
For end position indication, interlock control, fan startup, etc.,
AFBUP-S N4(H), AFXUP-S N4 incorporates two built-in auxiliary switches:
2 x SPDT, 3A (0.5A) @250 VAC, UL Approved, one switch is fi xed at +10°,
one is adjustable 10° to 90°.
Meets cULus requirements without the need of an electrical ground con-
nection.
WARNING
Live Electrical Components!
G
During installation, testing, servicing and troubleshooting of this product, it may be
necessary to work with live electrical components. Have a qualifi ed licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo-
nents could result in death or serious injury.
N40103 - 09/11 - Subject to change.