Torque min. 180 in-lb, for control of air dampers

Application

For On/Off, fail-safe control of dampers in HVAC systems. Actuator sizing should be
done in accordance with the damper manufacturer’s specifications. Control is On/Off 
from an auxiliary contact, or a manual switch.

The actuator is mounted directly to a damper shaft up to 1.05” in diameter by means
of its universal clamp. A crank arm and several mounting brackets are available for
applications where the actuator cannot be direct coupled to the damper shaft.

Operation

The AFB and AFX series actuators provide true spring return operation for reliable fail-
safe application and positive close off on air tight dampers. The spring return system 
provides constant torque to the damper with, and without, power applied to the
actuator.

The AFB and AFX series provides 95° of rotation and is provided with a graduated 
position indicator showing 0° to 95°.

The actuator may be stalled anywhere in its normal rotation without the need of 
mechanical end switches.

The AFB24-S and AFX24-S versions are provided with two built-in auxiliary switches.
These SPDT switches are provided for safety interfacing or signaling, for example, for
fan start-up. The switching function at the fail-safe position is fixed at +10°, the other
switch function is adjustable b10° to +90°. The AFB24, AFB24-S, AFX24 and 
AFX24-S actuator is shipped at +5° (5° from full fail-safe) to provide automatic
compression against damper gaskets for tight shut-off.

Dimensions

 (Inches [mm])

K7-2 

(supplied)

 1/2" 

Centered 

 

 (Default)

 

 3/4" 

Centered 

 (Field 

Selectable) 

1.05" Centered 
(Field Selectable)

W

AFBNFBDi

m

AFB24, AFB24-S, AFX24, AFX24-S

On/Off, Spring Return, 24 V

Technical Data

AFB24, AFB24-S, AFX24, AFX24-S

Power supply

24 VAC ± 20% 50/60 Hz
24 VDC +20% / -10%

Power consumption

running 5 W

holding 2.5 W

Transformer sizing

7.5 VA (class 2 power source)

Electrical connection

AFB24...

3 ft, 18 GA appliance cable, 1/2" conduit
connector

-S models:

 two 3 ft, 18 gauge appliance cables 

with 1/2” conduit connectors

AFX24...

3 ft [1m], 10 ft [3m] or 16 ft [5m] 18 GA 
appliance or plenum cables, with or without 1/2”
conduit connector

-S models:

 two 3 ft [1m], 10 ft [3m] or 

16 ft [5m] appliance cables, with or without 1/2" 
conduit connectors 

Overload protection

electronic throughout 0 to 95° rotation

Control

on/off

Torque

180 in-lb [20 Nm] minimum

Direction of rotation

spring reversible with CW/CCW mounting

Mechanical angle of rotation

95° (adjustable with mechanical end stop, 35° to
95°)

Running time

motor < 75 seconds

spring 20 seconds @ -4°F to 122°F [-20°C to 50°C];

< 60 seconds @ -22°F [-30°C]

Position indication

visual indicator, 0° to 95°
(0° is full spring return position)

Manual override

5 mm hex crank (

³⁄₁₆

" Allen), supplied

Humidity

max. 95% RH non-condensing

Ambient temperature

-22°F to 122°F [-30°C to 50°C]

Storage temperature

-40°F to 176°F [-40°C to 80°C]

Housing 

Nema 2, IP54, Enclosure Type2

Housing material

zinc coated metal and plastic casing

Agency listings

cULus acc. to UL60730-1A/-2-14,
CAN/CSA E60730-1:02, CE acc. to
2004/108/EC & 2006/95/EC

Noise level

<50dB(A) motor @ 75 seconds

62dB(A) spring return

Servicing

maintenance free

Quality standard

ISO 9001

Weight

4.6 lbs (2.1 kg); 4.9 lbs (2.25 kg) with switches

†  Rated Impulse Voltage 800V, Type of action 1.AA (1.AA.B for -S version), Control Pollution Degree 3.

AFB24-S, AFX24-S

Auxiliary switches

2 x SPDT 3A (0.5A) @ 250 VAC, UL approved
one set at +10°, one adjustable 10° to 90°

 N40103 - 09/11 - Subject to change.

 © Belimo 

Aircontrols (USA),

 Inc

.

Summary of Contents for AFB Series

Page 1: ... AFX24 MFT p 61 AFB24 MFT N4 H AFX24 MFT N4 p 63 AFB24 MFT S AFX24 MFT S p 61 AFB24 MFT S N4 H AFX24 MFT S N4 p 63 AFB24 MFT95 AFX24 MFT95 p 65 AFB24 MFT95 N4 H AFX24 MFT95 N4 p 67 Torque 180 in lb Power supply 24 VAC DC 120 VAC 230 VAC Control signal On Off 2 to 10 VDC Multi function 0 to 135 Ω Feedback signal VDC variable Running time motor 75 seconds 95 seconds Adj 70 to 220 seconds spring 20 s...

Page 2: ...ction Do it easily with a simple switch modulating actuators Microprocessor controlled brushless DC motor increases actuator life span and reliability provides constant running time modulating actuators Rugged metal on plastic housing withstands rough handling in the mechanical room Standard 3 ft appliance cable and conduit connector eases installation Double insulated no need for separate safety ...

Page 3: ...05 Centered Field Selectable WAFBNFBDim AFB24 AFB24 S AFX24 AFX24 S On Off Spring Return 24 V Technical Data AFB24 AFB24 S AFX24 AFX24 S Power supply 24 VAC 20 50 60 Hz 24 VDC 20 10 Power consumption running 5 W holding 2 5 W Transformer sizing 7 5 VA class 2 power source Electrical connection AFB24 3 ft 18 GA appliance cable 1 2 conduit connector S models two 3 ft 18 gauge appliance cables with 1...

Page 4: ...tors with auxiliary switches must be constructed to meet the requirements for Double Insulation so an electrical ground is not required to meet agency listings Actuators shall be cULus Approved and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and disconnec...

Page 5: ... 20 50 60 Hz 24 VDC 20 10 Power consumption running 5 W heater 25 W holding 2 5 W Transformer sizing 7 5 VA class 2 power source heater 25 VA Electrical connection AFB N4 3 ft 18 GA appliance cable 1 2 conduit connector S models Two 3 ft 18 gauge appliance cables with 1 2 conduit connectors heater N4H terminal block 26 16 GA AFX N4 3 ft 1m 10 ft 3m or 16 ft 5m 18 GA appliance cable with or without...

Page 6: ...electrical components Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed to live electrical compo nents could result in death or serious injury 1 Common 2 Hot 1 2 24 VAC Transformer AFB24 N4 H AFB24 S N4 H AFX24 N4 AFX24 S N4 Line Volts 3 ...

Page 7: ...ered Default 3 4 Centered Field Selectable 1 05 Centered Field Selectable WAFBNFBDim Technical Data AFBUP AFBUP S AFXUP AFXUP S Power supply 24 240 VAC 20 10 50 60 Hz 24 125 VDC 10 Power consumption running 7 W holding 3 5 W Transformer sizing 7 VA 24 VAC class 2 power source 8 5 VA 120 VAC 18 VA 240 VAC Electrical connection AFBUP 3 ft 18 GA appliance cable 1 2 conduit connector S models Two 3 ft...

Page 8: ...f one being adjustable Actuators with auxiliary switches must be constructed to meet the requirements for Double Insulation so an electrical ground is not required to meet agency listings Actuators shall be cULus approved and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overl...

Page 9: ...VDC 10 Power consumption running 7 W heater 25 W holding 3 5 W Transformer sizing 7 VA 24 VAC class 2 power source 8 5 VA 120 VAC heater 25 VA 120 VAC 18 VA 240 VAC Electrical connection AFBUP N4 3 ft 18 GA appliance cable 1 2 conduit connector S models Two 3 ft 18 gauge appliance cables with 1 2 conduit connectors heater N4H terminal block 18 16 GA AFXUP N4 3 ft 1m 10 ft 3m or 16 ft 5m 18 GA appl...

Page 10: ...ality Control Standards Actuators shall be as manufactured by Belimo AFBUP N4 H AFBUP S N4 H AFXUP N4 AFXUP S N4 NEMA 4 On Off Spring Return 24 to 240 VAC AFBUP N4 H AFBUP S N4 H AFXUP N4 AFXUP S N4 W066_AFBUP_N4 On Off Wiring Wht Blk AFBUP S N4 H AFXUP S N4 W067_AFBUP S_N4 Auxiliary Switches AF NF N4H 120V heater NEMA 4 Heater Wiring Diagrams 1 Provide overload protection and disconnect as requir...

Page 11: ...SR AFB24 SR S AFX24 SR and AFX24 SR S actuator is shipped at 5 5 from full fail safe to provide automatic compression against damper gaskets for tight shut off ATTENTION AFB24 SR S and AFX24 SR S cannot be tandem mounted on the same damper or valve shaft Only On Off and MFT AF models can be used for tandem mount applications Dimensions Inches mm K7 2 supplied 1 2 Centered Default 3 4 Centered Fiel...

Page 12: ... International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and disconnect as required 2 CAUTION Equipment Damage Actuators may be connected in parallel Power consumption and input impedance must be observed 2 Up to 4 actuators may be connected in parallel if not mechanically mounted to the same shaft With 4 actuators wired to...

Page 13: ...72 Clamp Configurations 1 2 Field Selectable 3 4 Centered 1 05 Centered Default Field Selectable 12 99 330 6 45 163 9 0 39 10 0 92 23 4 3 62 92 1 9 37 238 1 12 28 5 3 36 85 2 3 5 0 14 0 81 20 5 1 17 29 8 0 79 20 D312_Confi g Technical Data AFB24 SR N4 H AFB24 SR S N4 H AFX24 SR N4 AFX24 SR S N4 Power supply 24 VAC 20 50 60 Hz 24 VDC 20 10 Power consumption running 5 5 W heater 25 W holding 3 W Tra...

Page 14: ...AUTION Equipment Damage Actuators may be connected in parallel Power consumption and input impedance must be observed 2 Up to 4 actuators may be connected in parallel With 4 actuators wired to one 500 Ω resistor Power consumption must be observed 3 Actuator may also be powered by 24 VDC 4 For end position indication interlock control fan startup etc AFB24 SR S N4 H AFX24 SR S N4 incorporates two b...

Page 15: ...m specified torque to the application during a power interruption The AFB24 MFT AFX24 MFT actuator is shipped at 5 5 from full fail safe to provide automatic compression against damper gaskets for tight shut off NOTE Please see documentation on Multi Function Technology Dimensions Inches mm AFBNFBDim Technical Data AFB24 MFT AFB24 MFT S AFX24 MFT AFX24 MFT S Power supply 24 VAC 20 50 60 Hz 24 VDC ...

Page 16: ... either clockwise or counterclockwise fail safe operation Actuators shall use a brushless DC motor controlled by a microprocessor and be protected from overload at all angles of rotation Run time shall be constant and independent of torque A 2 to 10 VDC feedback signal shall be provided for position feedback Actuators shall be cULus Approved and have a 5 year warranty and be manufactured under ISO...

Page 17: ... 10 5 lbs 4 8 kg with heater Variable when configured with MFT options Rated Impulse Voltage 800V Type of action 1 AA 1 AA B for S version Control Pollution Degree 4 Programmed for 70 sec motor run time At 150 sec motor run time transformer sizing is 8 5 VA and power consumption is 6 W running 3 W holding i AFB24 MFT S N4 H AFX24 MFT S N4 Auxiliary switches 2 x SPDT 3A 0 5A 250 VAC UL approved one...

Page 18: ... shall be provided for position feedback Actuators shall be cULus Approved and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and disconnect as required 2 CAUTION Equipment Damage Actuators may be connected in parallel if not mechanically mounted to the same...

Page 19: ...eed of mechanical end switches The AFB24 MFT95 AFX24 MFT95 is mounted directly to control shafts up to 1 05 diameter by means of its universal clamp and anti rotation bracket A crank arm and several mounting brackets are available for damper applications where the actuator cannot be direct coupled to the damper shaft The spring return system provides minimum specified torque to the application dur...

Page 20: ...imum Position Potentiometer Shunting Resistor Used with the W973 and W7100 controllers Honeywell T675A Morning Warmup W973 W7100 T775 W W W R R R Y B B W R B 21 21 Line Volts Line Volts 24 VAC Transformer W W R R W R B B 5 23 25 23 25 24 Line Volts Line Volts 21 21 24 VAC Transformer MFT95 Blk 1 Common Red 2 Hot Pnk 4 W Wht 3 R Gry 5 B Org 6 U5 Output 2 to 10 VDC MFT95 Blk 1 Common Red 2 Hot Pnk 4...

Page 21: ...unting brackets are available for damper applications where the actuator cannot be direct coupled to the damper shaft The spring return system provides minimum specified torque to the application during a power interruption Dimensions inches mm 6 77 172 Clamp Configurations 1 2 Field Selectable 3 4 Centered 1 05 Centered Default Field Selectable 12 99 330 6 45 163 9 0 39 10 0 92 23 4 3 62 92 1 9 3...

Page 22: ...inimum Position Potentiometer Shunting Resistor Used with the W973 and W7100 controllers Honeywell T675A Morning Warmup W973 W7100 T775 W W W R R R Y B B W R B 21 21 Line Volts Line Volts 24 VAC Transformer W W R R W R B B 5 23 25 23 25 24 Line Volts Line Volts 21 21 24 VAC Transformer MFT95 N4 Blk 1 Common Red 2 Hot Pnk 4 W Wht 3 R Gry 5 B Org 6 U5 Output 2 to 10 VDC MFT95 N4 Blk 1 Common Red 2 H...

Page 23: ...e out 2 If the universal clamp is not on the correct side of the actuator mount it onto the correct side 3 Slide the actuator onto the shaft and tighten the nuts on the V bolt with a 10mm wrench to 6 8 ft lb of torque 4 Slide the anti rotation strap under the actuator so that it engages the slot at the base of the actuator Secure the strap to the duct work with 8 self tapping screws NOTE Read the ...

Page 24: ...800 543 9038 USA 866 805 7089 CANADA 203 791 8396 LATIN AMERICA CARIBBEAN 70 1 2 Installation Instructions K7 2 Universal Clamp N40103 09 11 Subject to change Belimo Aircontrols USA Inc ...

Page 25: ...he actuator The AFB S AFX S versions are provided with two built in auxiliary switches These SPDT switches are provided for safety interfacing or signaling for example for fan start up The switching function at the fail safe position is fixed at 10 the other switch function is adjustable between 10 to 90 Automatic Airtight Dampers Manual Override The AFB AFX series provides 95 of rotation and is p...

Page 26: ... on the clamp using a 10mm wrench or socket using 6 8 ft lb of torque 8 Slip the stud of the anti rotation strap into the slot at the base of the actuator The stud should be positioned approximately 1 16 of an inch from the closed end of the slot Bend the strap as needed to reach the duct Attach the strap to the duct with 8 self tapping screws 9 If damper position indication is required use the op...

Page 27: ...signed rotation less than 90 An example would be a 45 or 60 rotating damper The other application would be to set a minimum damper position which can be easily set or changed without having to remove the actuator from the damper Damper Rotation Limiting 1 Determine the amount of damper rotation required 2 Locate the Angle of Rotation Limiter on the actuator Figure B 3 Position the limiter to the d...

Page 28: ...power to the unit for than 3 sec Testing the installation Without Power The actuator damper installation may be tested without power at the actuator Refer to the manual positioning section of the instructions Move the damper to its full non fail safe position using the manual crank Disengage the manual position mechanism and have the damper go to full fail safe position Correct any mechanical prob...

Page 29: ...clip supplied with the clamp is not used to mount the KH t A AFB crank arm The KH AFB crank arm is used in non direct coupled mounting applications The KH A AFB may also be used to simultaneously direct couple to a damper shaft and provide an additional crank arm connection to a second damper KH AFB For round shafts up to 3 4 or square shafts up to 5 8 Dimensions Inches mm Vorlage_ Klappenhebel 3 ...

Page 30: ...d stops the pulses to the motor when it senses a stall condition The DC motor remains energized and produces full rated torque to the load This helps ensure that dampers are fully closed and that edge and blade seals are always properly compressed Motor Position Detection Belimo brushless DC motors eliminate the need for potentiometers for positioning in modulating type actuators Inside the motor ...

Page 31: ...following rules are followed 1 The transformers are properly sized 2 All No 1 wires from all actuators are tied together and tied to the negative leg of the control signal See wiring diagram Wire Length for AFB AFX Actuators Keep power wire runs below the lengths listed in the Figure H If more than one actuator is powered from the same wire run divide the allowable wire length by the number of act...

Page 32: ... Signal position Actuator operates properly Step 7 Step 5 5 Check input signal with a digital volt meter DVM Make sure the input is within the range of the actuator NOTE The input signal must be above the 2 VDC or 4 mA to have the actuator move Input voltage or current should be 1 of what controller s adjustment or programming indicates Controller output actuator input is correct Input Polarity Co...