40
Installation BAT450-F
Release 12 07/2020
Figure 5: BAT450-F pole mounting set with tightening straps
2.2.3
Grounding the device
The device is grounded via the separate ground screw.
The device variants featuring supply voltage with characteristic value N
(110 V DC) have a connection for protective ground
.
The device variants featuring supply voltage with characteristic value W
(24 V DC) have a connection for functional ground
.
Terminate the ground conductor between the fastening plates.
Make sure the fastening plates cover the stripped part of the ground
conductor completely.
Tighten the grounding screw with a tightening torque of 26.55 lb-
in ± 4.43 lb-in (3 Nm ± 0.5 Nm).
WARNING
ELECTRIC SHOCK
Ground the device before connecting any other cables.
Failure to follow this instruction can result in death, serious injury, or
equipment damage.