Starting operation
Technical manual LioN-P/ -R EtherNet/IP
Release 1.4 02/2016
5.4 Configuring the controlling
29
Using the rotary encoding switches, the following settings are possible for
LioN-P modules:
5.4
Configuring the controlling
5.4.1
Connections and assembly object
The modules support the
Exclusive Owner
,
Input Only
, and
Listen Only
connection types. The
Exclusive Owner
connection type is only available for
modules with an output function (variants 16DO and 8DI/8DO).
001 to 254
The last 3 digits of the saved or preset IP address are overwritten
by the setting of the rotary switch.
255 to 998
(exception: 888)
The network parameters are requested via DHCP and BOOTP but
are not saved.
888
The device performs a reset to the factory settings. The network
parameters are also reset to the default values. Communication is
not possible in this operation mode.
999
The factory setting of the IP address (192.168.001.001) is used.
Rotary switch setting
Function
000
(state on delivery)
In the state on delivery, the DHCP and BOOTP functions are
activated. The network parameters are initially requested via
DHCP requests. If this is not successful, BOOTP requests are
used. The network parameters are not saved, but the integrated
web server can be used to save them.
000
(network parameters
already saved)
The network parameters last saved are used (IP address, subnet
mask, gateway address, DHCP on/off, BOOTP on/off).
001 to 254
The last 3 digits of the saved or preset IP address are overwritten
by the setting of the rotary switch.
255 to 999
(exceptions: 299 and 979)
The network parameters are requested via DHCP and BOOTP but
are not saved.
299
The factory setting of the IP address (192.168.001.001) is used.
979
The device performs a reset to the factory settings. The network
parameters are also reset to the default values. Communication is
not possible in this operation mode.
Table 9:
Setting options of the rotary encoding switches for LioN-P modules
Rotary switch setting
Function
Table 8:
Setting options of the rotary encoding switches for LioN-R modules
Summary of Contents for 934 691-001
Page 2: ...2 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Page 6: ...Content 6 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Page 47: ...QuickConnect Technical manual LioN P R EtherNet IP Release 1 4 02 2016 7 2 Activation 47...
Page 48: ...QuickConnect 48 7 2 Activation Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Page 62: ...Technical data 62 10 7 LEDs Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Page 64: ...Declaration of conformity 64 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...
Page 68: ...Accessories 68 Technical manual LioN P R EtherNet IP Release 1 4 02 2016...