Installation
DRYPOINT® RA CT 20-500 NA
25
9.5 Electrical
connections
Danger
!
Supply voltage!
The connection to the electric mains should only be carried out by qualified skilled personnel and must
correspond to the legal provisions in force in your region.
Prior to connecting the device, please check the type plate to avoid exceeding the indicated values. The voltage
tolerance is +/- 10%.
DRYPOINT RA CT 20-500 NA dryers are supplied with a power cord and safety plug (two-pole and earth connection).
or with a junction box on the back plate.
Make sure that suitable fuses or circuit breakers in accordance with the indications on the type plate are available.
A residual-current device (RCD) with I
n =0.03A is suggested. The cross-section of the power supply cable must
correspond to the power consumption of the dryer. In this respect, the ambient temperature, the cable laying
conditions, the length of the cables and the requirements of the local electricity supplier need to be considered.
Danger!
Supply voltage and missing earth connection!
Important: ensure that the plant is connected to earth-ground.
Do not use plug adapters at the power plug.
Possible replacement of the power plug must only be carried out by a qualified electrician.
9.6 Condensate
drain
Danger
!
Compressed air and condensate under pressure!
The condensate is discharged at system pressure.
The drain pipe needs to be secured.
Never direct the condensate drain pipe at persons.
The dryer is delivered with an already integrated electronically level-controlled BEKOMAT condensate drain. Connect
the condensate drain with a collection system or container by properly screwing it on.
Do not connect the drain with pressurised plants.
Do not discharge the condensate into the environment.
The condensate accumulating in the dryer contains oil particles which were released into the air by the
compressor.
Dispose of the condensate in accordance with the local provisions.
It is advisable to install a water-oil separator, to which the total amount of condensate from the
compressors, dryers, tanks, filters etc. is supplied.
We recommend ÖWAMAT oil-water separators for dispersed compressor condensate and BEKOSPLIT
emulsion-splitting plants for emulsified condensate.
Summary of Contents for DRYPOINT RA CT 100-NA-EB
Page 39: ...Maintenance troubleshooting spare parts and dismantling DRYPOINT RA CT 20 500 NA 39 ...
Page 40: ...Maintenance troubleshooting spare parts and dismantling 40 DRYPOINT RA CT 20 500 NA ...
Page 43: ...Appendices DRYPOINT RA CT 20 500 NA 43 13 1 2 Dryer dimensions DRYPOINT RA CT 75 NA ...
Page 44: ...Appendices 44 DRYPOINT RA CT 20 500 NA 13 1 3 Dryer dimensions DRYPOINT RA CT 100 150 NA ...
Page 45: ...Appendices DRYPOINT RA CT 20 500 NA 45 13 1 4 Dryer dimensions DRYPOINT RA CT 200 250 NA ...
Page 46: ...Appendices 46 DRYPOINT RA CT 20 500 NA 13 1 5 Dryer dimensions DRYPOINT RA CT 300 350 NA ...
Page 47: ...Appendices DRYPOINT RA CT 20 500 NA 47 13 1 6 Dryer dimensions DRYPOINT RA CT 400 500 NA ...
Page 52: ...Appendices 52 DRYPOINT RA CT 20 500 NA 13 2 2 Exploded diagram DRYPOINT RA CT 20 30 NA ...
Page 53: ...Appendices DRYPOINT RA CT 20 500 NA 53 13 2 3 Exploded diagram DRYPOINT RA CT 50 NA ...
Page 54: ...Appendices 54 DRYPOINT RA CT 20 500 NA 13 2 4 Exploded diagram DRYPOINT RA CT 75 NA ...
Page 55: ...Appendices DRYPOINT RA CT 20 500 NA 55 13 2 5 Exploded diagram DRYPOINT RA CT 100 NA ...
Page 56: ...Appendices 56 DRYPOINT RA CT 20 500 NA 13 2 6 Exploded diagram DRYPOINT RA CT 125 150 NA ...
Page 57: ...Appendices DRYPOINT RA CT 20 500 NA 57 13 2 7 Exploded diagram DRYPOINT RA CT 200 250 NA ...
Page 58: ...Appendices 58 DRYPOINT RA CT 20 500 NA 13 2 8 Exploded diagram DRYPOINT RA CT 300 350 NA ...
Page 59: ...Appendices DRYPOINT RA CT 20 500 NA 59 13 2 9 Exploded diagram DRYPOINT RA CT 400 500 NA ...
Page 72: ...Appendices 72 DRYPOINT RA CT 20 500 NA ...
Page 73: ...Appendices DRYPOINT RA CT 20 500 NA 73 ...