8.12.4 Indication of a Service Warning
A service warning is an exceptional event and requires the attention of the operator/service technician. The dryer will
not be stopped.
When a service warning is active, the
Led flashes.
When a service warning is no longer active but not reset yet (so it has been stored)
Led is continuously on.
In both cases the display shows the dew point temperature and the service warnings which are active or which are no
longer active but not yet reset.
Service warnings are NOT automatically reset.
To
RESET
the service warning,
the
Led must be continuously on (not flashing), keep pressed simultaneously
Set
+
buttons for three seconds. Only the stored service warning will be reset. Service warnings which
are still active continue to be indicated by the
Led flashing.
NOTE: the operator/service technician must check the dryer and eliminate the problem that caused the service
warning.
Service warning
Description
HdP – High dew point: dew point too high, higher than the adjusted HdS value
LdP – Low dew point: dew point too low
Setting T1< -1°C (30°F) delay five minutes / reset T1> -0.5°C (31°F)
SrV - Service: maintenance service time expired SrV
8.12.5 Indication of an Alarm
An alarm is an exceptional event which, to avert damage from to the machine and the operator, always leads to the
dryer stop.
When an alarm is active, the
LED flashes.
When an alarm is no longer active but not reset yet (so it has been stored)
Led is continuously on (in any case,
the dryer remains OFF).
In both cases the display shows
and the alarms which are active or which are no longer active but not yet reset.
Alarms are NOT automatically reset.
To
RESET
the alarm,
the
Led must be continuously on (not flashing), keep pressed simultaneously
Set
+
buttons for three seconds. Only the stored alarm will be reset. Alarms which are still active continue to be
indicated by the
Led flashing.
The dryer will start automatically subsequent to the reset of the alarms.
NOTE: the operator/service technician must check the dryer and eliminate the problem that caused the alarm.
Alarm Description
LP – Low pressure: the refrigerant low-pressure switch LPS has tripped.
Hdt – High outlet temperature: compressor outlet temperature outside the safety limit
Setting T2> 110°C (230°F) delay one minute / reset T2< 90°C (194°F)
ICE - ICE / Icing: Temperature in the exchanger (probe T1) is too low and leads to icing
of the condensate.
Setting T1< -2°C (28°F) delay one minute / reset T1> 0°C (32°F)
toC – Too many Cycles : compressor has been cycled On/OFF unusually too often
(stopped more than 5 times before reaching its minimum ON time)
PF1 – Probe 1 failure: failure probe T1
PF2 – Probe 2 failure: failure probe T2
Summary of Contents for DRYPOINT RA CT 100-NA-EB
Page 39: ...Maintenance troubleshooting spare parts and dismantling DRYPOINT RA CT 20 500 NA 39 ...
Page 40: ...Maintenance troubleshooting spare parts and dismantling 40 DRYPOINT RA CT 20 500 NA ...
Page 43: ...Appendices DRYPOINT RA CT 20 500 NA 43 13 1 2 Dryer dimensions DRYPOINT RA CT 75 NA ...
Page 44: ...Appendices 44 DRYPOINT RA CT 20 500 NA 13 1 3 Dryer dimensions DRYPOINT RA CT 100 150 NA ...
Page 45: ...Appendices DRYPOINT RA CT 20 500 NA 45 13 1 4 Dryer dimensions DRYPOINT RA CT 200 250 NA ...
Page 46: ...Appendices 46 DRYPOINT RA CT 20 500 NA 13 1 5 Dryer dimensions DRYPOINT RA CT 300 350 NA ...
Page 47: ...Appendices DRYPOINT RA CT 20 500 NA 47 13 1 6 Dryer dimensions DRYPOINT RA CT 400 500 NA ...
Page 52: ...Appendices 52 DRYPOINT RA CT 20 500 NA 13 2 2 Exploded diagram DRYPOINT RA CT 20 30 NA ...
Page 53: ...Appendices DRYPOINT RA CT 20 500 NA 53 13 2 3 Exploded diagram DRYPOINT RA CT 50 NA ...
Page 54: ...Appendices 54 DRYPOINT RA CT 20 500 NA 13 2 4 Exploded diagram DRYPOINT RA CT 75 NA ...
Page 55: ...Appendices DRYPOINT RA CT 20 500 NA 55 13 2 5 Exploded diagram DRYPOINT RA CT 100 NA ...
Page 56: ...Appendices 56 DRYPOINT RA CT 20 500 NA 13 2 6 Exploded diagram DRYPOINT RA CT 125 150 NA ...
Page 57: ...Appendices DRYPOINT RA CT 20 500 NA 57 13 2 7 Exploded diagram DRYPOINT RA CT 200 250 NA ...
Page 58: ...Appendices 58 DRYPOINT RA CT 20 500 NA 13 2 8 Exploded diagram DRYPOINT RA CT 300 350 NA ...
Page 59: ...Appendices DRYPOINT RA CT 20 500 NA 59 13 2 9 Exploded diagram DRYPOINT RA CT 400 500 NA ...
Page 72: ...Appendices 72 DRYPOINT RA CT 20 500 NA ...
Page 73: ...Appendices DRYPOINT RA CT 20 500 NA 73 ...