Installation
DRYPOINT® RA CT 20-500 NA
23
9.3 Correction
factors
Correction factor for operating pressure modifications:
Inlet air pressure
psig
60
80
100
120
140
160
180
203
barg 4 5.5 7 8 10 11 12 14
Factor (F1)
0.79
0.91
1.00
1.07 1.13 1.18 1.23 1.27
Correction factor for ambient temperature modifications:
Ambient temperature
ºF
80 90 95 100 105 110 115 122
ºC
27
32 35 38 40 43 45 50
Factor (F2)
1.11
1.09
1.06
1.00 0.94 0.87 0.78 0.69
Correction factor for inlet air temperature modifications:
Air temperature
ºF
90 100 110 122 130 140 150 158
ºC
32
38 43 50 55 60 65 70
Factor (F3)
1.16
1.00
0.82
0.68 0.61 0.52 0.45 0.40
Correction factor for DewPoint modifications:
DewPoint
ºF
38
41
45
50
ºC
3
5
7
10
Factor
(F4)
1.00 1.08 1.20 1.36
Calculation of the actual air throughput:
Actual air throughput = air throughput acc. to planning x factor (F1) x factor (F2) x factor (F3) x factor (F4)
Example:
The
DRYPOINT RA CT 75 NA
has a planned nominal capacity of 75 scfm (127 m³/h). The highest
achievable air mass under the following operating conditions is:
Air inlet pressure = 120 psig (8 barg)
Ambient temperature = 115°F (45°C)
Air inlet temperature = 122°F (50°C)
Pressure dew point = 50°F (10°C)
Factor (F1) = 1.07
Factor (F2) = 0.78
Factor (F3) = 0.68
Factor (F4) = 1.36
Every function parameter corresponds to a numerical factor which, multiplied by the planned nominal capacity,
determines the following:
Actual air throughput = 75 x 1.07 x 0.78 x 0.68 x 1.36 = 58 scfm (99 m³/h)
58 scfm (99 m³/h)
is the maximum flow rate of the dryer under the aforementioned operating conditions.
Selection of the best suitable model in accordance with the operating conditions:
Air throughput acc. to planning =
Requ. air throughput
Factor (F1) x Factor (F2) x Factor (F3) x Factor (F4)
Example:
The following operating parameters are known:
Required air mass = 100 scfm (170 m
3
/h)
Air inlet pressure = 120 psig (8 barg)
Ambient temperature = 115°F (45°C)
Air inlet temperature = 122°F (50°C)
Pressure dew point = 50°F (10°C)
Factor (F1) = 1.07
Factor (F2) = 0.78
Factor (F3) = 0.68
Factor (F4) = 1.36
To find out the correct dryer version, the required air mass must be divided by the correction factors of the
parameters indicated above:
Air throughput acc. to planning =
100
= 130 scfm (221 m³/h)
1.07 x 0.78 x 0.68 x 1.36
The suitable model for these requirements is
DRYPOINT RA CT 150 NA
(with a spec. nominal capacity of
150 scfm [255 m³/h]
).
Summary of Contents for DRYPOINT RA CT 100-NA-EB
Page 39: ...Maintenance troubleshooting spare parts and dismantling DRYPOINT RA CT 20 500 NA 39 ...
Page 40: ...Maintenance troubleshooting spare parts and dismantling 40 DRYPOINT RA CT 20 500 NA ...
Page 43: ...Appendices DRYPOINT RA CT 20 500 NA 43 13 1 2 Dryer dimensions DRYPOINT RA CT 75 NA ...
Page 44: ...Appendices 44 DRYPOINT RA CT 20 500 NA 13 1 3 Dryer dimensions DRYPOINT RA CT 100 150 NA ...
Page 45: ...Appendices DRYPOINT RA CT 20 500 NA 45 13 1 4 Dryer dimensions DRYPOINT RA CT 200 250 NA ...
Page 46: ...Appendices 46 DRYPOINT RA CT 20 500 NA 13 1 5 Dryer dimensions DRYPOINT RA CT 300 350 NA ...
Page 47: ...Appendices DRYPOINT RA CT 20 500 NA 47 13 1 6 Dryer dimensions DRYPOINT RA CT 400 500 NA ...
Page 52: ...Appendices 52 DRYPOINT RA CT 20 500 NA 13 2 2 Exploded diagram DRYPOINT RA CT 20 30 NA ...
Page 53: ...Appendices DRYPOINT RA CT 20 500 NA 53 13 2 3 Exploded diagram DRYPOINT RA CT 50 NA ...
Page 54: ...Appendices 54 DRYPOINT RA CT 20 500 NA 13 2 4 Exploded diagram DRYPOINT RA CT 75 NA ...
Page 55: ...Appendices DRYPOINT RA CT 20 500 NA 55 13 2 5 Exploded diagram DRYPOINT RA CT 100 NA ...
Page 56: ...Appendices 56 DRYPOINT RA CT 20 500 NA 13 2 6 Exploded diagram DRYPOINT RA CT 125 150 NA ...
Page 57: ...Appendices DRYPOINT RA CT 20 500 NA 57 13 2 7 Exploded diagram DRYPOINT RA CT 200 250 NA ...
Page 58: ...Appendices 58 DRYPOINT RA CT 20 500 NA 13 2 8 Exploded diagram DRYPOINT RA CT 300 350 NA ...
Page 59: ...Appendices DRYPOINT RA CT 20 500 NA 59 13 2 9 Exploded diagram DRYPOINT RA CT 400 500 NA ...
Page 72: ...Appendices 72 DRYPOINT RA CT 20 500 NA ...
Page 73: ...Appendices DRYPOINT RA CT 20 500 NA 73 ...