background image

6.3.1  Access

Access  to  the  listener  configuration  menu  is
obtained  by  operating  the  

P

 and  

E

 buttons

simultaneously.    If  the  BA444DF-P  listener
configuration menu is not protected by an access
code the first parameter 'SCAn’ will be displayed.
If the BA444DF-P is protected by an access code,
‘CodE’ will be displayed first.  Pressing 

P

 will allow

the four digit security code to be entered digit by
digit using the 

 or 

 button to adjust the flashing

digit and 

P

 to move control to the next digit.  When

the correct code has been entered, pressing 

E

 will

cause the first parameter ‘SCAn’ to be displayed.
If  an  incorrect  code  is  entered,  or  no  button  is
pressed  for  ten  seconds,  the  indicator  will
automatically return to the display mode.  

Section  6.3.2  contains  a  summary  of  each
configuration function  including  a cross  reference
to a more detailed description.

6.3.2 Summary of listener configuration 
functions

   

Instrument          Summary

   

display               of function

‘SCAn’

Scan fieldbus segment 

Identifies

 

all  data  sources  on  the

fieldbus segment to which the listener is
connected and enables selected data to
be allocated to one of the eight listener
inputs in-1 to in-8.
See section 6.4.1

‘LiSt’

List configured input parameters

 

For  each  of  the  eight  BA444DF-P
listener inputs, in-1 to in-8 shows if the
input  is  enabled,  Source  Address,
Destination  Address  and  the  Index
which

 have

 been

 allocated.

Parameters  can  not  be  changed  from
within this function.
See section 6.4.2

‘Edit’

Enter addresses and display 
parameters

Sub-menu which allows known fieldbus
device addresses to be entered and all
display parameters adjusted for each of
the eight fieldbus listener inputs. 
See section 6.4.3

 

‘Enb’

Enable selected input

Enables  each  of  the  eight
listener   inputs   in-1   to   in-8   to
be  enabled  or  disabled
without

 affecting

 any

parameters.
See section 6.4.4

‘SrC’

Enter Source Address

Allows  hexadecimal  fieldbus
device  source  address  for
each  of  the  eight  listener
inputs  in-1  to  in-8  to  be
entered.
See section 6.4.5

‘dSt’

Enter Destination Address

Allows  hexadecimal  fieldbus
device destination address for
each listener input in-1 to in-8
to be entered.
See section 6.4.6

‘ind’

Enter Index

Allows  hexadecimal index for
specified  fieldbus  source
address  to  be  entered  for
each listener input   in-1 to in-
8.
See section 6.4.7

‘dP’

Decimal point position

Defines  position  of  displayed
decimal point for each listener
input in-1 to in-8.
See section 6.4.8

‘bAr’

Configuration of bargraph

Defines  the  bargraphs
justification  and  the  digital
display at which the bargraph
is zero and full scale for each
listener input in-1 to in-8.
See section 6.4.9

‘SCALE’

Scale numeric display

Applies zero offset and scale
factor  to  the  numeric  display
for each listener input in-1 to
in-8.
See section 6.4.10

‘CodE’

Access code for listener 
configuration menu

Enters  a  four  digit  security  access
code for configuration menu.  Default
code 0000 disables this function.
See section 6.4.11

tYPE’

Change from listener to node

Enables  the  instrument  to  be
conditioned as a fieldbus listener or a
fieldbus node.
See section 6.4.12

‘rESEt’

Reset to listener factory defaults

Returns  the  BA444DF-P  listener  to
factory defaults.
See section 6.4.13

10

Summary of Contents for PROFIBUS PA BA444DF-P

Page 1: ...Issue 5 16th December 2015 BA444DF P PROFIBUS PA Intrinsically safe Field mounting 8 variable Fieldbus Indicator Issue 5...

Page 2: ...ions 6 4 Description of listener menu functions 6 4 1 Scan fieldbus segment 6 4 2 List configured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source...

Page 3: ...There is an alternative version of the fieldbus display order code BA444DF P for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes ATEX system design and install...

Page 4: ...ure classification of T1 450oC T2 300oC T3 200oC T4 135oC At an ambient temperature between 40 and 70o C Note the guaranteed operating temperature range of the BA444DF P Fieldbus Indicator is 20 to 70...

Page 5: ...t should be equal to or less than Uo 22V dc Io 250mA dc Po 1 2W The segment can provide an additional 13mA to power the Fieldbus Indicator The equivalent capacitance Ci of the BA444DF P Fieldbus Indic...

Page 6: ...entries 5 2 Installation Procedure Fig 2 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a fl...

Page 7: ...Fig 3 Dimensions and terminal connections 7...

Page 8: ...ng the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button wil...

Page 9: ...ed by the BA444DF P listener are not known In the SCAn function pressing the P button causes the BA444DF P listener to search the fieldbus segment to which it is connected for all data sources The hex...

Page 10: ...rs Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected input En...

Page 11: ...rce address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a lis...

Page 12: ...ode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 6 4 9 Configuration of bargraph displ...

Page 13: ...sed access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 6 4 12 Change from fieldbus listener to fieldbus node t...

Page 14: ...nds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live ma...

Page 15: ...lf adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA444DF P can be supplied with a blank or custom laser marked stain...

Page 16: ...efer to over 5mm thick EN 60079 14 At an ambient temperature between 20 and 60o C The Indicator may be connected to any intrinsically safe segment providing The device powering the fieldbus segment is...

Page 17: ...name and location IECEx dust approval information is also shown non European certification information may also be included The label includes boxed areas which should be marked by the installer to s...

Page 18: ...mply with the Canadian Electrical Code C22 2 and with BEKA associates Control Drawing CI410 12 which is attached to this Appendix The FM and cFM entity parameters are identical to the ATEX parameters...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...25...

Page 26: ...allation requirements for both gas and dust approvals The ATEX installation requirements specified in the main section and in Appendix 1 of this manual may therefore be used for IECEx installations bu...

Reviews: