background image

APPENDIX 2   
FM Approval for use in the USA and
cFM Approval for use in Canada

A2.0  Factory Mutual Approval

For installations in the USA and Canada, a version
of the BA444DF-P is available with FM and cFM
intrinsic safety and nonincendive approval, project
identifications 3027031 and 3027031C.    Copies of
the Certificates  of Compliance are available from
BEKA associates sales office and www.beka.co.uk

The FM and cFM Approved version is identical to
the   ATEX   version   except   the   three   M20   x   1,5
tapped  cable  entries  are  replaced  by  three  plain
unthreaded 22.25mm diameter entries.  Approved
hubs and glands are listed in note 6 of Intrinsically
Safe  Control  Drawing  CI410-12  and  note  5  of
Nonincendive  Control  Drawing  CI410-13.    The
certification  label  on  the  FM  and  cFM  Approved
version includes ATEX gas certification information
so  that  the  BA444DF-P  PROFIBUS  PA indicator
may  be  used  in  systems  covered  by  either
authority.

A2.1  Intrinsic safety  approval

The  BA444DF-P  is  approved  to  FM  Class  3610
intrinsic  safety  standard  for  use  in  indoor  and
outdoor  hazardous  (classified)  locations.
Installations  must  comply  with  BEKA  associates
Control  Drawing  CI410-12,  which  is  attached  to
this Appendix, ANSI/ISA RP12.06.01 ‘Installation of
Intrinsically  Safe  Systems  for  Hazardous
(Classified)  Locations’  and  with  the  National
Electrical Code ANSI/NFPA70.

The  BA444DF-P  has  a  T4  rating  at  ambient
temperatures up to +70

o

C and may be used with

the following gases and dusts:

Intrinsic Safety

Division 1 or 2

Class I    Group A & B 
               Group C
               Group D

Class II   Group E, F & G

Class  III

Zone 0, 1 or 2

Class 1   Group IIC
               Group IIB
               Group IIA           

Canadian  installations  must  comply  with  the
Canadian  Electrical  Code  C22.2  and  with  BEKA
associates  Control  Drawing  CI410-12,  which  is
attached to this Appendix.

The FM and cFM entity parameters are identical to
the  ATEX  parameters  and,  like  the  ATEX
certification, confirm that the BA444DF-P complies
with  the  FISCO  Field  Device  requirements
specified  in  IEC60079-27.    The  intrinsically  safe
system  shown  in  Fig  1  of  this  manual  may
therefore be used for installations in the USA and
Canada,  providing  the  fieldbus  power  supply,
terminators,  Zener  barriers  and  galvanic  isolators
are FM Approved for US installations and cFM or
CSA  Approved  for  Canadian  installations.  All
installations  must  comply  with  BEKA  associates
Control Drawing CI410-12 .  

FM and cFM Approvals also allows the BA444DF-
P to  be  connected  to  non-FISCO  systems  using
the entity concept – see section 3.2 of this manual.

A2.2  Nonincendive approval

The  BA444DF-P is  FM  Class  3611  nonincendive
approved  allowing  it  to  be  installed  in  Division  2
indoor and outdoor hazardous (classified) locations
without  the  need  for  Zener  barriers  or  galvanic
isolators.   US installations must comply with the
BEKA associates Control Drawing CI410-13, which
is attached to this Appendix, and with the National
Electrical Code ANSI/NFPA70.

Canadian  nonincendive  installations  must  comply
with the Canadian Electrical Code C22.2 and with
BEKA associates Control Drawing CI410-13, which
is attached to this Appendix.

The  FM  and  cFM  Nonincendive  Approvals  also
allow the BA444DF-P PROFIBUS PA indicator to
be connected to any appropriately certified FNICO
compliant fieldbus segment.

The  BA444DF-P  has  a  T4  rating  at  ambient
temperatures up to +70ºC and may be used with
the following gases and dusts:

Nonincendive

Division 2

Class I    Group A & B 
               Group C
               Group D

Class II   Groups E, F & G 

Class III

Zone 2

Class I    Group IIC
               Group IIB
               Group IIA

18

Summary of Contents for PROFIBUS PA BA444DF-P

Page 1: ...Issue 5 16th December 2015 BA444DF P PROFIBUS PA Intrinsically safe Field mounting 8 variable Fieldbus Indicator Issue 5...

Page 2: ...ions 6 4 Description of listener menu functions 6 4 1 Scan fieldbus segment 6 4 2 List configured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source...

Page 3: ...There is an alternative version of the fieldbus display order code BA444DF P for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes ATEX system design and install...

Page 4: ...ure classification of T1 450oC T2 300oC T3 200oC T4 135oC At an ambient temperature between 40 and 70o C Note the guaranteed operating temperature range of the BA444DF P Fieldbus Indicator is 20 to 70...

Page 5: ...t should be equal to or less than Uo 22V dc Io 250mA dc Po 1 2W The segment can provide an additional 13mA to power the Fieldbus Indicator The equivalent capacitance Ci of the BA444DF P Fieldbus Indic...

Page 6: ...entries 5 2 Installation Procedure Fig 2 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a fl...

Page 7: ...Fig 3 Dimensions and terminal connections 7...

Page 8: ...ng the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button wil...

Page 9: ...ed by the BA444DF P listener are not known In the SCAn function pressing the P button causes the BA444DF P listener to search the fieldbus segment to which it is connected for all data sources The hex...

Page 10: ...rs Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected input En...

Page 11: ...rce address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a lis...

Page 12: ...ode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 6 4 9 Configuration of bargraph displ...

Page 13: ...sed access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 6 4 12 Change from fieldbus listener to fieldbus node t...

Page 14: ...nds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live ma...

Page 15: ...lf adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA444DF P can be supplied with a blank or custom laser marked stain...

Page 16: ...efer to over 5mm thick EN 60079 14 At an ambient temperature between 20 and 60o C The Indicator may be connected to any intrinsically safe segment providing The device powering the fieldbus segment is...

Page 17: ...name and location IECEx dust approval information is also shown non European certification information may also be included The label includes boxed areas which should be marked by the installer to s...

Page 18: ...mply with the Canadian Electrical Code C22 2 and with BEKA associates Control Drawing CI410 12 which is attached to this Appendix The FM and cFM entity parameters are identical to the ATEX parameters...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...25...

Page 26: ...allation requirements for both gas and dust approvals The ATEX installation requirements specified in the main section and in Appendix 1 of this manual may therefore be used for IECEx installations bu...

Reviews: