4.  SYSTEM DESIGN FOR HAZARDOUS  
     AREAS

4.1  FISCO Systems

The  BA444DF-P  fieldbus  indicator  may  be
connected to any ATEX certified FISCO compliant
fieldbus  segment,  providing  the  segment  can
supply the additional 13mA required to operate the
instrument.

Fig 1 shows a typical fieldbus segment.  To comply
with  FISCO  requirements,  the  power  supply,
terminators,  field  devices  and  the  interconnecting
cables must conform with IEC60079-11.

Fig 1   FISCO fieldbus system

4.2

  

Ex ia entity systems

The  BA444DF-P  Fieldbus  Indicator  has  Ex  ia
certification with entity parameters for applications
in Zone 0, 1 and 2.

The  BA444DF-P  Fieldbus  Indicator  may  be
connected  to  any  intrinsically  safe  segment
providing:

The device powering the fieldbus segment is
ATEX   Ex   ia   certified   for   Zone   0,   1   or   2
applications, or Ex ib certified for application
in  Zone  1  or  2,  or  Ex  ic  certified  for
applications  in  Zone  2.    The  output
parameters of the segment should be equal
to or less than:

Uo

=

22V dc

Io

=

250mA dc

Po

=

1.2W

The segment can provide an additional 13mA
to power the Fieldbus Indicator.

The  equivalent  capacitance  Ci  of  the
BA444DF-P  Fieldbus  Indicator  is  zero  and
the  equivalent  inductance  is  insignificant.
Therefore  these  BA444DF-P parameters  do
not need to be considered.

4.3

  

Ex ic entity systems

The BA444DF-P Fieldbus Indicator also has Ex ic
certification with entity parameters for applications
in  Zone  2.      The  higher  Ui  voltage  allows  the
indicator  to  be  used  with  segment  couplers
powered by  Ex e or Power-i  fieldbus trunks.

When mounted in Zone 2 the BA444DF-P Fieldbus
Indicator may be connected to any intrinsically safe
segment providing:

The device powering the fieldbus segment is
ATEX Ex ia, ib or ic certified and has output
parameters equal to or less than:

Uo

=

32V dc

Io

=

125mA dc

Po

=

1W

The segment can provide an additional 13mA
to power the Fieldbus Indicator.

The  equivalent  capacitance  Ci  of  the
BA444DF-P  Fieldbus  Indicator  is  zero  and
the  equivalent  inductance  is  insignificant.
Therefore  these  BA444DF-P parameters  do
not need to be considered.

5

Summary of Contents for PROFIBUS PA BA444DF-P

Page 1: ...Issue 5 16th December 2015 BA444DF P PROFIBUS PA Intrinsically safe Field mounting 8 variable Fieldbus Indicator Issue 5...

Page 2: ...ions 6 4 Description of listener menu functions 6 4 1 Scan fieldbus segment 6 4 2 List configured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source...

Page 3: ...There is an alternative version of the fieldbus display order code BA444DF P for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes ATEX system design and install...

Page 4: ...ure classification of T1 450oC T2 300oC T3 200oC T4 135oC At an ambient temperature between 40 and 70o C Note the guaranteed operating temperature range of the BA444DF P Fieldbus Indicator is 20 to 70...

Page 5: ...t should be equal to or less than Uo 22V dc Io 250mA dc Po 1 2W The segment can provide an additional 13mA to power the Fieldbus Indicator The equivalent capacitance Ci of the BA444DF P Fieldbus Indic...

Page 6: ...entries 5 2 Installation Procedure Fig 2 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a fl...

Page 7: ...Fig 3 Dimensions and terminal connections 7...

Page 8: ...ng the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button wil...

Page 9: ...ed by the BA444DF P listener are not known In the SCAn function pressing the P button causes the BA444DF P listener to search the fieldbus segment to which it is connected for all data sources The hex...

Page 10: ...rs Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected input En...

Page 11: ...rce address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a lis...

Page 12: ...ode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 6 4 9 Configuration of bargraph displ...

Page 13: ...sed access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 6 4 12 Change from fieldbus listener to fieldbus node t...

Page 14: ...nds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live ma...

Page 15: ...lf adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA444DF P can be supplied with a blank or custom laser marked stain...

Page 16: ...efer to over 5mm thick EN 60079 14 At an ambient temperature between 20 and 60o C The Indicator may be connected to any intrinsically safe segment providing The device powering the fieldbus segment is...

Page 17: ...name and location IECEx dust approval information is also shown non European certification information may also be included The label includes boxed areas which should be marked by the installer to s...

Page 18: ...mply with the Canadian Electrical Code C22 2 and with BEKA associates Control Drawing CI410 12 which is attached to this Appendix The FM and cFM entity parameters are identical to the ATEX parameters...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...25...

Page 26: ...allation requirements for both gas and dust approvals The ATEX installation requirements specified in the main section and in Appendix 1 of this manual may therefore be used for IECEx installations bu...

Reviews: