6.2.4  Reset the instrument to node factory
          defaults           ‘rESEt’

The  BA444DF-P  may  be  reset  to  the  factory
defaults that are shown below:

Security Code

0000 (disabled)

Device address

126

For each of the eight inputs:

Decimal point

XXX.XX

Bar Type

Left

Bar lower limit

0.0

Bar Upper limit

100.0

Gain

1.0

Offset

0.0To reset the BA444DF-

P  select  ‘rESEt’  in  the  configuration  menu  by
operating  the  

 or  

 button.    To  enter  the

function press  

P

 which will reveal ‘0000’ with the

left hand digit flashing.  To prevent accidental use
of this function, ‘5urE’ must be entered to confirm
that the instrument is to be reset.

Using the 

 or 

 button set the flashing digit to ‘5’

and press the 

P

 button to move control to the next

digit  which  should  be  set  to  ‘u’.    When  the  four
letters of ‘5urE’ have been entered operating the 

E

button  will  reset  the  BA444DF-P  to  the  factory
defaults.      Any  existing  configuration  and
addresses will be lost when the instrument is reset.

FIG 4 Node configuration menu

6.3  Listener configuration menu

When used as a fieldbus listener the BA444DF-P
is not visible to the fieldbus host and can only be
configured  using  the  front  panel  push  buttons
shown in Fig 3.

The listener configuration menu is separated into
three sections, ‘SCAn’, ‘LISt’ and ‘Edit’, plus three
housekeeping functions ‘CodE’, ‘tYPE’ and ‘rESEt’
as shown in Fig 6.

‘SCAn’ is  the  simplest  method  of  configuration  if
the addresses of the data sources to be displayed
by the BA444DF-P listener are not known.  

In  the  ‘SCAn’  function  pressing  the  

P

 button

causes  the  BA444DF-P  listener  to  search  the
fieldbus  segment  to  which  it  is  connected  for  all
data  sources.     The  hexadecimal  device
addresses for each data source are displayed as
shown in Fig 5.    

The  

 and  

 push  buttons  scroll  the  display

through  all  the  data  sources  on  the  segment
showing  the  source  and  destination  address  for
each one.   To aid identification, operating the  

P

button  will  preview  the  value  of  the  data  at  the
selected addresses with a zero index i.e. the first
five bytes in the data string.   If the format of the
data is not DS-33 ( float) ‘no dAt’ will be
displayed.    The  selected  source  and  destination
addresses  may  be  allocated  to  one  of  the  eight
BA444DF-P listener inputs in-1, to in-8.  Operating
the  

P

  button  will  reveal  the  current  listener  input

which   may   be   changed   using   the  

 or  

 push

button, when set as required, operating the 

E

 push

button  will  enter  the  allocation.    If  the  process
variable to be displayed is located further along the
data stream i.e. has an index greater than 5, the
required index must be entered via the index ‘ind’
function in the edit sub-menu.  

A  worked  configuration  example  illustrating  this
procedure is contained in the Quick Set-up section
of the PROFIBUS PA Interface Guide.

Fig 5  Device Addresses

If the source and destination addresses and index
of  the  process  variable  to  be  displayed  by  the
BA444DF-P  listener  are  known,  they  may  be
directly entered via the edit sub-menu.  This sub-
menu also provides full control of both the numeric
and bargraph display parameters.

9

Summary of Contents for PROFIBUS PA BA444DF-P

Page 1: ...Issue 5 16th December 2015 BA444DF P PROFIBUS PA Intrinsically safe Field mounting 8 variable Fieldbus Indicator Issue 5...

Page 2: ...ions 6 4 Description of listener menu functions 6 4 1 Scan fieldbus segment 6 4 2 List configured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source...

Page 3: ...There is an alternative version of the fieldbus display order code BA444DF P for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes ATEX system design and install...

Page 4: ...ure classification of T1 450oC T2 300oC T3 200oC T4 135oC At an ambient temperature between 40 and 70o C Note the guaranteed operating temperature range of the BA444DF P Fieldbus Indicator is 20 to 70...

Page 5: ...t should be equal to or less than Uo 22V dc Io 250mA dc Po 1 2W The segment can provide an additional 13mA to power the Fieldbus Indicator The equivalent capacitance Ci of the BA444DF P Fieldbus Indic...

Page 6: ...entries 5 2 Installation Procedure Fig 2 illustrates the instrument installation procedure a Remove the instrument terminal cover by unscrewing the two captive A screws b Mount the instrument on a fl...

Page 7: ...Fig 3 Dimensions and terminal connections 7...

Page 8: ...ng the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button wil...

Page 9: ...ed by the BA444DF P listener are not known In the SCAn function pressing the P button causes the BA444DF P listener to search the fieldbus segment to which it is connected for all data sources The hex...

Page 10: ...rs Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected input En...

Page 11: ...rce address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a lis...

Page 12: ...ode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 6 4 9 Configuration of bargraph displ...

Page 13: ...sed access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 6 4 12 Change from fieldbus listener to fieldbus node t...

Page 14: ...nds the model number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live ma...

Page 15: ...lf adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA444DF P can be supplied with a blank or custom laser marked stain...

Page 16: ...efer to over 5mm thick EN 60079 14 At an ambient temperature between 20 and 60o C The Indicator may be connected to any intrinsically safe segment providing The device powering the fieldbus segment is...

Page 17: ...name and location IECEx dust approval information is also shown non European certification information may also be included The label includes boxed areas which should be marked by the installer to s...

Page 18: ...mply with the Canadian Electrical Code C22 2 and with BEKA associates Control Drawing CI410 12 which is attached to this Appendix The FM and cFM entity parameters are identical to the ATEX parameters...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...25...

Page 26: ...allation requirements for both gas and dust approvals The ATEX installation requirements specified in the main section and in Appendix 1 of this manual may therefore be used for IECEx installations bu...

Reviews: