BEKA BA627E-SS Manual Download Page 7

4.2

Installation Procedure

a.

Cut the aperture specified in Fig 3 in the panel
enclosure. Ensure that the edges of the aper-
ture are de-burred. 

b.

Inspect the instrument's captive gasket and en-
sure that it is not damaged before inserting the
Set Point Station into the panel enclosure aper-
ture.

c.

If the enclosure panel is less than 1.0mm thick,
or is non-metallic, an optional BEKA stainless
steel support plate should be slid over the rear
of the indicator before the panel clamps are fit-
ted to evenly distribute the clamping force and
prevent the enclosure panel being distorted or
creeping.

d.

Slide a panel clamp into the two grooves at
each corner of the indicator housing with the
M3 stud protruding through the hole at the rear

of the clamp.  Fit the stainless steel 

spring

washer over the stud and secure with  the

stain-

less steel wing nut.

e.

Evenly tighten the four clamps to secure the
instrument.

The

recommended

minimum

tightening torque for each wing nut is 22cNm
(1.95 lbf in).

f.

Connect the panel enclosure wiring to the rear
terminal blocks.

To simplify installation, the

terminals are removable so that wiring can be
completed before the instrument is installed.
Cables should be mechanically secured to en-
sure terminals are not damaged by vibration.

g.

Finally, fit a silicone rubber push-on cap to the
end of each M3 threaded rod.

Fig 4 Installation procedure

4.3

Instrument earthing

The BA627E-SS Set Point Station has an M4 earth
stud on the rear panel which should be electrically
connected to the panel enclosure in which the instru-
ment is mounted, or to the plant equipotential con-
ductor.

4.4

EMC

The BA627E-SS Set Point Station complies with the
requirements

of

the

European

EMC

Directive

2004/108/EC.

For specified immunity all wiring

should be in screened twisted pairs, with the screens
earthed at a common point.

Fig 5 Rear terminals

7

Summary of Contents for BA627E-SS

Page 1: ...Issue 2 5th May 2017 BA627E SS General purpose 2 wire 4 20mA rugged manual set point station Issue 2...

Page 2: ...imit 5 7 Pre set outputs 5 8 Maximum output rate of change 5 9 Function of push button in operating mode 5 10 Encoder 5 11 One or two handed operation 5 12 Security code 5 13 Reset to factory defaults...

Page 3: ...front panel and push buttons Initially the output current changes slowly but after the button has been pressed for five seconds the rate of change accelerates to allow large changes to be made quickl...

Page 4: ...or ten seconds during which time operat ing the button will update the Set Point Station output to the displayed pre set value If the button is not op erated during this period the Set Point Station o...

Page 5: ...If the button is not operated during this period the Set Point Station output will not be changed and the original engineering display will be shown Firmware number followed by version Access to conf...

Page 6: ...m operating voltage of the BA627E SS Fig 2 Typical application 4 INSTALLATION 4 1 Location The BA627E SS Set Point Station has a stainless steel case with a 10mm thick toughened glass win dow The case...

Page 7: ...ess steel wing nut e Evenly tighten the four clamps to secure the instrument The recommended minimum tightening torque for each wing nut is 22cNm 1 95 lbf in f Connect the panel enclosure wiring to th...

Page 8: ...c cessory from BEKA associates Custom printed scale cards can also be supplied To change a scale card unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it out of...

Page 9: ...ault Configuration Resolution rE5n 10 Display at 4mA output 2ero 0 00 Display at 20mA output 5PAn 100 00 Output current limits H L 03 000 22 000 Maximum output rate of change 000 button in operating m...

Page 10: ...ent as a percentage or to provide access to the five pre set outputs when the push button is pressed in the operating mode See section 5 9 Display Summary of function EnC Encoder In addition to the Se...

Page 11: ...11...

Page 12: ...different values Zero and Span measured by a calibrated external current meter and the corresponding Set Point Station dis play to be entered The bargraph is not displayed while using the CAL functio...

Page 13: ...lect Lo to adjust the lower current output limit or Hi to adjust upper output current limit Pressing will display the selected output current limit in milliamps with one digit flashing The flashing di...

Page 14: ...s a panel mounting encoder that generates 12 contact pulses per revolution which complies with the requirements for simple apparatus and is intended for use with the BA627E SS Other encoders that prod...

Page 15: ...e BA627E SS Set Point Station to the factory default configurations shown in section 5 To reset the Set Point Station select r5Et from the configuration menu and press To prevent acci dental resetting...

Page 16: ...LP Lo Voltage between BA627E SS ter minal 1 3 is too low Increase 4 20mA loop supply voltage 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA627E SS Set P...

Page 17: ...ight that may be loop or separately powered When loop powered the backlight produces back ground illumination enabling the display to be read at night or in poor lighting conditions No additional powe...

Page 18: ...int Station s output when the button is operated see section 2 1 Alternatively with single handed operation it is not necessary to press the button see section 2 2 7 4 1 BEKA BA490 rotary encoder The...

Reviews: