ELECTRICAL SYSTEM DESIGN

3.1

4/20mA loop

The BA627E-SS requires an operating voltage
between 6.1 and 30V. Design of the loop is similar
to that for a 2-wire temperature or pressure transmit-
ter.

Fig 2 illustrates a typical application in which a
BA627E-SS is powered from a common supply.
When designing the loop it is only necessary to es-
tablish that the maximum voltage drop caused by the
Set Point Station, the load and cable resistance is al-
ways less than the minimum supply voltage.

For example:

Minimum operating voltage of BA627E-SS 6.1V

Maximum voltage drop caused by
speed controller  which is a 250ohm 

5.0V

load   (250ohms x 20mA)

Maximum voltage drop caused by cable 

0.2V

resistance   (10ohms x 20mA)

                                                                     ---------

Total maximum voltage drop

11.3V

The power supply voltage must therefore be greater
than 11.3V, but less than 30V which is the maximum
operating voltage of the BA627E-SS.

Fig 2  Typical application

4.

INSTALLATION

4.1

Location

The BA627E-SS Set Point Station has a stainless
steel case with a 10mm thick toughened glass win-
dow. The case provides 7J and the window 4J front
of panel impact protection. The captive silicone gas-
ket, which seals the joint between the instrument and
the panel enclosure, ensures IP66 front of panel in-
gress protection.

The rear of the instrument has

IP20 protection.

Although the front of the instrument has IP66 protec-
tion, it should be shielded from continuous direct
sunlight and severe weather conditions. 

The BA627E-SS Set Point Station may be installed
in any panel enclosure providing that the operating
temperature is between -40°C and +70°C.

Fig

3

shows

the

overall

dimensions

of

the

BA627E-SS together with the recommended panel
cut-out dimensions and terminal identifications. To
achieve an IP66 seal between the instrument enclos-
ure and the instrument panel an aperture with the re-
commended tolerance should be used.

Fig 3 Dimensions

6

Summary of Contents for BA627E-SS

Page 1: ...Issue 2 5th May 2017 BA627E SS General purpose 2 wire 4 20mA rugged manual set point station Issue 2...

Page 2: ...imit 5 7 Pre set outputs 5 8 Maximum output rate of change 5 9 Function of push button in operating mode 5 10 Encoder 5 11 One or two handed operation 5 12 Security code 5 13 Reset to factory defaults...

Page 3: ...front panel and push buttons Initially the output current changes slowly but after the button has been pressed for five seconds the rate of change accelerates to allow large changes to be made quickl...

Page 4: ...or ten seconds during which time operat ing the button will update the Set Point Station output to the displayed pre set value If the button is not op erated during this period the Set Point Station o...

Page 5: ...If the button is not operated during this period the Set Point Station output will not be changed and the original engineering display will be shown Firmware number followed by version Access to conf...

Page 6: ...m operating voltage of the BA627E SS Fig 2 Typical application 4 INSTALLATION 4 1 Location The BA627E SS Set Point Station has a stainless steel case with a 10mm thick toughened glass win dow The case...

Page 7: ...ess steel wing nut e Evenly tighten the four clamps to secure the instrument The recommended minimum tightening torque for each wing nut is 22cNm 1 95 lbf in f Connect the panel enclosure wiring to th...

Page 8: ...c cessory from BEKA associates Custom printed scale cards can also be supplied To change a scale card unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it out of...

Page 9: ...ault Configuration Resolution rE5n 10 Display at 4mA output 2ero 0 00 Display at 20mA output 5PAn 100 00 Output current limits H L 03 000 22 000 Maximum output rate of change 000 button in operating m...

Page 10: ...ent as a percentage or to provide access to the five pre set outputs when the push button is pressed in the operating mode See section 5 9 Display Summary of function EnC Encoder In addition to the Se...

Page 11: ...11...

Page 12: ...different values Zero and Span measured by a calibrated external current meter and the corresponding Set Point Station dis play to be entered The bargraph is not displayed while using the CAL functio...

Page 13: ...lect Lo to adjust the lower current output limit or Hi to adjust upper output current limit Pressing will display the selected output current limit in milliamps with one digit flashing The flashing di...

Page 14: ...s a panel mounting encoder that generates 12 contact pulses per revolution which complies with the requirements for simple apparatus and is intended for use with the BA627E SS Other encoders that prod...

Page 15: ...e BA627E SS Set Point Station to the factory default configurations shown in section 5 To reset the Set Point Station select r5Et from the configuration menu and press To prevent acci dental resetting...

Page 16: ...LP Lo Voltage between BA627E SS ter minal 1 3 is too low Increase 4 20mA loop supply voltage 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA627E SS Set P...

Page 17: ...ight that may be loop or separately powered When loop powered the backlight produces back ground illumination enabling the display to be read at night or in poor lighting conditions No additional powe...

Page 18: ...int Station s output when the button is operated see section 2 1 Alternatively with single handed operation it is not necessary to press the button see section 2 2 7 4 1 BEKA BA490 rotary encoder The...

Reviews: