   Display       Summary of function                        

H--L

High & low current output limits

Defines the lower ‘Lo’ and upper ‘Hi’
4/20mA Set Point Station output current
limits.
See section 5.6

P5Et

Pre-set outputs

The values of the five pre-set current out-
puts are defined by this function. The
pre-set output currents are identified

5Et1

to

5Et5

and are displayed in engin-

eering units.
This function only appears in the config-
uration menu when

P5Et

, which allows

pre-set values to be viewed and selected
in the operating mode, is selected in the

P

 

.

 

Fn

 function.

See section 5.7

rAtE

Maximum output rate of change

Enables the maximum rate of change of
the 4/20mA output current to be defined.
Adjustable between approximately 1 and
100 seconds for full scale output travel.
0 disables this rate of change limit.
See section 5.8

P

 

.

 

Fn

Function of

(

push button in operat-

ing mode.

The Set Point Station may be configured
to display the output current in milliamps,
the output current as a percentage or to
provide access to the five pre-set outputs
when the

(

push button is pressed in

the operating mode.
See section 5.9

   Display       Summary of function                        

EnC

Encoder

In addition to the Set Point Station
4/20mA output being adjusted by the
front panel push buttons, an external
quadrature encoder may be connected to
provide control via a rotary knob.

This

function allows the number of pulses per
revolution of the knob to be entered.
See section 5.10

Hnd

One or two handed operation

Allows the Set Point Station output cur-
rent to be adjusted by the front panel

&

 or 

*

push button and by the optional

external encoder with or without the

)

button be pressed at the same time.
See section 5.11

CodE

Security code

Defines a four digit numeric code that
must be entered to gain access to the
configuration menu.

Default code

0000

disables this security function and allows
unrestricted access to all conditioning
functions.
See section 5.12

r5Et

Reset

Returns the Set Point Station configura-
tion to the default condition. To prevent
accidental use, reset must be confirmed
by entering

5urE

before it will be ex-

ecuted.
See section 5.13

10

Summary of Contents for BA627E-SS

Page 1: ...Issue 2 5th May 2017 BA627E SS General purpose 2 wire 4 20mA rugged manual set point station Issue 2...

Page 2: ...imit 5 7 Pre set outputs 5 8 Maximum output rate of change 5 9 Function of push button in operating mode 5 10 Encoder 5 11 One or two handed operation 5 12 Security code 5 13 Reset to factory defaults...

Page 3: ...front panel and push buttons Initially the output current changes slowly but after the button has been pressed for five seconds the rate of change accelerates to allow large changes to be made quickl...

Page 4: ...or ten seconds during which time operat ing the button will update the Set Point Station output to the displayed pre set value If the button is not op erated during this period the Set Point Station o...

Page 5: ...If the button is not operated during this period the Set Point Station output will not be changed and the original engineering display will be shown Firmware number followed by version Access to conf...

Page 6: ...m operating voltage of the BA627E SS Fig 2 Typical application 4 INSTALLATION 4 1 Location The BA627E SS Set Point Station has a stainless steel case with a 10mm thick toughened glass win dow The case...

Page 7: ...ess steel wing nut e Evenly tighten the four clamps to secure the instrument The recommended minimum tightening torque for each wing nut is 22cNm 1 95 lbf in f Connect the panel enclosure wiring to th...

Page 8: ...c cessory from BEKA associates Custom printed scale cards can also be supplied To change a scale card unclip the protruding end of the flexible strip by gently pushing it upwards and pulling it out of...

Page 9: ...ault Configuration Resolution rE5n 10 Display at 4mA output 2ero 0 00 Display at 20mA output 5PAn 100 00 Output current limits H L 03 000 22 000 Maximum output rate of change 000 button in operating m...

Page 10: ...ent as a percentage or to provide access to the five pre set outputs when the push button is pressed in the operating mode See section 5 9 Display Summary of function EnC Encoder In addition to the Se...

Page 11: ...11...

Page 12: ...different values Zero and Span measured by a calibrated external current meter and the corresponding Set Point Station dis play to be entered The bargraph is not displayed while using the CAL functio...

Page 13: ...lect Lo to adjust the lower current output limit or Hi to adjust upper output current limit Pressing will display the selected output current limit in milliamps with one digit flashing The flashing di...

Page 14: ...s a panel mounting encoder that generates 12 contact pulses per revolution which complies with the requirements for simple apparatus and is intended for use with the BA627E SS Other encoders that prod...

Page 15: ...e BA627E SS Set Point Station to the factory default configurations shown in section 5 To reset the Set Point Station select r5Et from the configuration menu and press To prevent acci dental resetting...

Page 16: ...LP Lo Voltage between BA627E SS ter minal 1 3 is too low Increase 4 20mA loop supply voltage 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA627E SS Set P...

Page 17: ...ight that may be loop or separately powered When loop powered the backlight produces back ground illumination enabling the display to be read at night or in poor lighting conditions No additional powe...

Page 18: ...int Station s output when the button is operated see section 2 1 Alternatively with single handed operation it is not necessary to press the button see section 2 2 7 4 1 BEKA BA490 rotary encoder The...

Reviews: