5.5.22 External reset
The Timer may be reset by connecting terminals
RS1 and RS2 together. This function defines how
long the connection must exist before resetting
occurs. When resetting is performed by a manually
operated external push button switch,
5td
should be
chosen. This requires the contact to be closed for
one second before resetting occurs which prevents
false resetting.
If the Timer is being reset by the a control output or
similar apparatus
Fa5t
should be selected.
Select Resetting time
5td
1s
fa5t
2ms
5.5.23 Status output:
5tat oP
The status output of the Timer is an opto isolated
open collector that can be used for transmitting the
status of the Timer to other instruments. It may also
be used for simple control applications.
When the
Status output is
on
the RTx annunciator on the
Timer display is activated.
The status output function contains four sub-
functions,
EnbL
,
5tat on
,
5tat
oFF
and
5tat.dELA
. To
gain access to the sub-menu select
5tat op
in the
configuration menu and press
(
which will show
the
EnbL
prompt from which the other sub-functions
can be accessed using the
&
or
*
button.
The status output may be configured to turn
on
when the Timer enters a selected Timer state and to
turn
off
when the Timer enters another specified
Timer state. e.g. if
run
is selected in the
5tat on
sub-function and
done
is selected the
5tat off
function. The status output will turn
on
when the
Timer enters the
run
state and will stay
on
until the
Timer enters the
done
state. Alternatively, the status
output phase may be reversed by selecting the
n
states such as
n re5et
.
If the status output is required to be
on
in only one
Timer state, this can be achieved with the following
configuration.
5tat on
state required e.g.
run
5tat off
n state required e.g.
n run
In this example when the Timer enters the
run
state
the status output turns
on
. When the Timer moves
from the
run
to any other state, the status output
turns
off
.
5.5.24 Status output enable:
EnbL
This function allows the status output to be enabled
or disabled without altering any other status output
parameters. To check or change the function select
EnbL
from the status output sub-menu and press
(
to reveal if the status output is
on
or
oFF
. The
setting can be changed by pressing the
&
or
*
button followed by the
)
button to return to the
status output sub-menu.
5.5.25 Status output
on
:
5tat on
The status output may be configured to turn
on
when the Timer enters any one of the five Timer
states. Alternatively, the status output phase may be
reversed by selecting an
n
state. This will cause the
status output to turn
on
when the Timer enters any
other than the specified Timer state. Timer states
are shown in Fig 9.
To define when the status output turns
on
select
5tat on
from the sub-menu and press
(
to show
the existing setting. Pressing the
&
or
*
button
will scroll through the options:
Display
Status output turns
on
when Timer enters selected state
re5et
Reset state
run
Running state
pau5ed
Paused state
delay
Restart delay state
done
Complete state
Status output turns
on
when Timer enters any other than
the selected state
n re5et
Reset state
n run
Running state
n pau5ed
Paused state
n delay
Restart delay state
n done
Complete
state
When the required setting has been selected press
)
to enter the selection and return to the status
output sub-menu.