6.3.1  Access

Access to the listener configuration menu is
obtained by operating the 

P

 and 

E

 buttons

simultaneously.  If the BA444NDF-P listener
configuration menu is not protected by an access
code the first parameter 'SCAn’ will be displayed.
If the BA444NDF-P is protected by an access
code, ‘CodE’ will be displayed first.  Pressing 

P

 will

allow the four digit security code to be entered digit
by digit using the 

 or 

 button to adjust the

flashing digit and 

P

 to move control to the next

digit.  When the correct code has been entered,
pressing 

E

 will cause the first parameter ‘SCAn’ to

be displayed.    If an incorrect code is entered, or
no button is pressed for ten seconds, the indicator
will automatically return to the display mode.

Section 6.3.2 contains a summary of each
configuration function including a cross reference
to a more detailed description.

6.3.2 Summary of listener configuration
functions

   

Instrument          Summary

   

display               of function

‘SCAn’

Scan fieldbus segment 

Identifies

 

all data sources on the

fieldbus segment to which the listener is
connected and enables selected data to
be allocated to one of the eight listener
inputs in-1 to in-8.
See section 6.4.1

‘LiSt’

List configured input parameters

For each of the eight BA444NDF-P
listener inputs, in-1 to in-8 shows if the
input is enabled, Source Address,
Destination Address and the Index
which have been allocated.
Parameters can not be changed from
within this function.
See section 6.4.2

‘Edit’

Enter addresses and display
parameters

Sub-menu which allows known fieldbus
device addresses to be entered and all
display parameters adjusted for each of
the eight fieldbus listener inputs.
See section 6.4.3

 

‘Enb’

Enable selected input

Enables each of the eight
listener inputs in-1 to in-8 to
be enabled or disabled
without affecting any
parameters.
See section 6.4.4

‘SrC’

Enter Source Address

Allows hexadecimal fieldbus
device source address for
each of the eight listener
inputs in-1 to in-8 to be
entered.
See section 6.4.5

‘dSt’

Enter Destination Address

Allows hexadecimal fieldbus
device destination address
for each listener input in-1 to
in-8 to be entered.
See section 6.4.6

‘ind’

Enter Index

Allows hexadecimal index
for  specified fieldbus source
address to be entered for
each listener input  in-1 to
in-8.
See section 6.4.7

‘dP’

Decimal point position

Defines position of displayed
decimal point for each
listener input in-1 to in-8.
See section 6.4.8

‘bAr’

Configuration of bargraph

Defines the bargraphs
justification and the digital
display at which the
bargraph is zero and full
scale for each listener input
in-1 to in-8.
See section 6.4.9

‘SCALE’ Scale numeric display

Applies zero offset and
scale factor to the numeric
display for each listener
input in-1 to in-8.
See section 6.4.10

‘CodE’

Access code for listener
configuration menu

Enters a four digit security access
code for configuration menu.  Default
code 0000 disables this function.
See section 6.4.11

tYPE’

Change from listener to node

Enables the instrument to be
conditioned as a fieldbus listener or a
fieldbus node.
See section 6.4.12

‘rESEt’

Reset to listener factory defaults

Returns the BA444NDF-P listener to
factory defaults.
See section 6.4.13

Summary of Contents for BA444NDF-P

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA444NDF P...

Page 2: ...anehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 44 0...

Page 3: ...Issue 3 4th march 2014 BA444NDF P PROFIBUS PA Type n Field mounting 8 variable Fieldbus Indicator Issue 3...

Page 4: ...6 4 2 List configured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source address 6 4 6 Enter destination address 6 4 7 Enter Index 6 4 8 Decimal poi...

Page 5: ...of this manual describes ATEX design and installation requirements for BA444NDF P applications in flammable gas atmospheres System design and installation requirements for ATEX dust and for IECEx gas...

Page 6: ...ustrial gases 3 3 Fieldbus connection The BA444NDF P Indicator is powered and communicates via the fieldbus which is connected to terminals 1 and 2 These terminals are non polarised comply with the Fi...

Page 7: ...may be connected to any Type nL certified associated apparatus irrespective of its Io providing Uo of the Type nL certified associated apparatus is equal to or less than 36V which is the Ui of the BA4...

Page 8: ...erminal should be connected to the potential equalising network as recommenced in EN 60079 14 The BA444NDF P enclosure is supplied with a bonding plate to ensure electrical continuity between the thre...

Page 9: ...7 Fig 3 Dimensions and terminal connections...

Page 10: ...rating the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button...

Page 11: ...BA444NDF P listener are not known In the SCAn function pressing the P button causes the BA444NDF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecima...

Page 12: ...10...

Page 13: ...meters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected inpu...

Page 14: ...source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a...

Page 15: ...red position omit it or activate all the decimal points which automatically provides maximum resolution in the display mode irrespective of the numeric value When positioned as required operating the...

Page 16: ...code has been selected press E to enter the selection and return to the CodE prompt in the configuration menu The revised access code will be activated when the transmitter is returned to the display...

Page 17: ...2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on FNICO systems but should only be performed on non FNICO systems when there is no ri...

Page 18: ...new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA444NDF P can be supplied with a blank or custom...

Page 19: ...yer on BA444NDF P 175 C up to 5mm thick Dust layer on BA444NDF over 5mm thick Refer to EN 61241 14 At an ambient temperature between 20 and 60 C A1 2 Certification Label Information The certification...

Page 20: ...st for a short time Be used with gases in groups Group A propane Group B ethylene Group C hydrogen Having a temperature classification of T1 450 C T2 300 C T3 200 C T4 135 C At an ambient temperature...

Page 21: ...on BA444NDF P 175 C up to 5mm thick Dust layer on BA444NDF P Refer to over 5mm thick IEC 61241 14 At an ambient temperature between 20 and 60 C The IECEx certificate may be downloaded from www beka co...

Reviews: