4.  SYSTEM DESIGN FOR HAZARDOUS
     AREAS

4.1  FNICO Systems

The BA444NDF-P may be connected to any ATEX
certified FNICO compliant PROFIBUS PA
segment, providing the segment can supply the
additional 13mA required to power the instrument.

Fig 1 shows a typical fieldbus segment.  To comply
with FNICO requirements, the power supply,
terminators, field devices and the interconnecting
cables must conform to the requirements specified
in EN 60079 part 27:2006.

Fig 1   FNICO PROFIBUS PA system

4.2

  

Non-FNICO Systems

As shown in section 3.3 the BA444NDF-P also has
entity input parameters.   The listener complies
with the requirements for

 ‘Self protected energy-

limited apparatus’

 as defined by Clause 30.1

Paragraph b of EN 60079-15. This means that the
BA444NDF-P contains its own current limiting
components and may be connected to any Type
nL certified associated apparatus irrespective of its
Io providing:

Uo of the Type nL certified associated
apparatus is equal to or less than 36V which is
the Ui of the BA444NDF.  

Note:

 Maximum

operating voltage is 32V.

C cable + sum of Ci of all other instruments
connected to the segment is equal to, or less
than, Co of the Type nL associated apparatus
powering the fieldbus segment to which the
BA444NDF-P is connected.

L cable + 8µH + sum of Li of all other
instruments connected to the segment is equal
to, or less than, Lo of the Type nL associated
apparatus powering the fieldbus segment to
which the BA444NDF-P is connected.

The fieldbus segment can provide an additional
13mA at between 9 and 32V to power the
BA444NDF-P PROFIBUS PA Indicator.

These requirements are not restrictive and allow
the BA444NDF-P 8 variable PROFIBUS PA
indicator to be connected to almost all Type nL
fieldbus segments powered by Type n associated
apparatus or Zone 2 mounted segment isolators.

Summary of Contents for BA444NDF-P

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA444NDF P...

Page 2: ...anehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 44 0...

Page 3: ...Issue 3 4th march 2014 BA444NDF P PROFIBUS PA Type n Field mounting 8 variable Fieldbus Indicator Issue 3...

Page 4: ...6 4 2 List configured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source address 6 4 6 Enter destination address 6 4 7 Enter Index 6 4 8 Decimal poi...

Page 5: ...of this manual describes ATEX design and installation requirements for BA444NDF P applications in flammable gas atmospheres System design and installation requirements for ATEX dust and for IECEx gas...

Page 6: ...ustrial gases 3 3 Fieldbus connection The BA444NDF P Indicator is powered and communicates via the fieldbus which is connected to terminals 1 and 2 These terminals are non polarised comply with the Fi...

Page 7: ...may be connected to any Type nL certified associated apparatus irrespective of its Io providing Uo of the Type nL certified associated apparatus is equal to or less than 36V which is the Ui of the BA4...

Page 8: ...erminal should be connected to the potential equalising network as recommenced in EN 60079 14 The BA444NDF P enclosure is supplied with a bonding plate to ensure electrical continuity between the thre...

Page 9: ...7 Fig 3 Dimensions and terminal connections...

Page 10: ...rating the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button...

Page 11: ...BA444NDF P listener are not known In the SCAn function pressing the P button causes the BA444NDF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecima...

Page 12: ...10...

Page 13: ...meters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected inpu...

Page 14: ...source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a...

Page 15: ...red position omit it or activate all the decimal points which automatically provides maximum resolution in the display mode irrespective of the numeric value When positioned as required operating the...

Page 16: ...code has been selected press E to enter the selection and return to the CodE prompt in the configuration menu The revised access code will be activated when the transmitter is returned to the display...

Page 17: ...2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on FNICO systems but should only be performed on non FNICO systems when there is no ri...

Page 18: ...new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA444NDF P can be supplied with a blank or custom...

Page 19: ...yer on BA444NDF P 175 C up to 5mm thick Dust layer on BA444NDF over 5mm thick Refer to EN 61241 14 At an ambient temperature between 20 and 60 C A1 2 Certification Label Information The certification...

Page 20: ...st for a short time Be used with gases in groups Group A propane Group B ethylene Group C hydrogen Having a temperature classification of T1 450 C T2 300 C T3 200 C T4 135 C At an ambient temperature...

Page 21: ...on BA444NDF P 175 C up to 5mm thick Dust layer on BA444NDF P Refer to over 5mm thick IEC 61241 14 At an ambient temperature between 20 and 60 C The IECEx certificate may be downloaded from www beka co...

Reviews: