background image

9

6.2.4  Reset the instrument to node factory
          defaults           ‘rESEt’

The BA444NDF-P may be reset to the factory
defaults that are shown below:

Security Code

0000 (disabled)

Device address

126

For each of the eight inputs:

Decimal point

XXX.XX

Bar Type

Left

Bar lower limit

0.0

Bar Upper limit

100.0

Gain

1.0

Offset

0.0

 To reset the BA444NDF-P select ‘rESEt’ in the
configuration menu by operating the 

 or 

button.   To enter the function press 

P

 which will

reveal ‘0000’ with the left hand digit flashing.  To
prevent accidental use of this function, ‘5urE’ must
be entered to confirm that the instrument is to be
reset.

Using the 

 or 

 button set the flashing digit to ‘5’

and press the 

P

 button to move control to the next

digit which should be set to ‘u’.  When the four
letters of ‘5urE’ have been entered operating the 

E

button will reset the BA444NDF-P to the factory
defaults.   Any existing configuration and
addresses will be lost when the instrument is reset.

FIG 4 Node configuration menu

6.3  Listener configuration menu

When used as a fieldbus listener the BA444NDF-P
is not visible to the fieldbus host and can only be
configured using the front panel push buttons
shown in Fig 3.

The listener configuration menu is separated into
three sections, ‘SCAn’, ‘LISt’ and ‘Edit’, plus three
housekeeping functions ‘CodE’, ‘tYPE’ and ‘rESEt’
as shown in Fig 6.

‘SCAn’ is the simplest method of configuration if
the addresses of the data sources to be displayed
by the BA444NDF-P listener are not known.

In the ‘SCAn’ function pressing the 

P

 button

causes the BA444NDF-P listener to search the
fieldbus segment to which it is connected for all
data sources.    The hexadecimal device
addresses for each data source are displayed as
shown in Fig 5.

The 

 and 

 push buttons scroll the display

through all the data sources on the segment
showing the source and destination address for
each one.   To aid identification, operating the 

P

button will preview the value of the data at the
selected addresses with a zero index i.e. the first
five bytes in the data string.   If the format of the
data is not DS-33 ( float) ‘no dAt’ will be
displayed.  The selected source and destination
addresses may be allocated to one of the eight
BA444NDF-P listener inputs in-1, to in-8.
Operating the 

P

 button will reveal the current

listener input which may be changed using the 

or 

 push button, when set as required, operating

the 

E

 push button will enter the allocation.  If the

process variable to be displayed is located further
along the data stream i.e. has an index greater
than 5, the required index must be entered via the
index ‘ind’ function in the edit sub-menu.

A worked configuration example illustrating this
procedure is contained in the Quick Set-up section
of the 

BEKA PROFIBUS PA Display – Fieldbus

Interface Guide

.

Fig 5  Device Addresses

If the source and destination addresses and index
of the process variable to be displayed by the
BA444NDF-P listener are known, they may be
directly entered via the edit sub-menu.  This sub-
menu also provides full control of both the numeric
and bargraph display parameters.

Summary of Contents for BA444NDF-P

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA444NDF P...

Page 2: ...anehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 44 0...

Page 3: ...Issue 3 4th march 2014 BA444NDF P PROFIBUS PA Type n Field mounting 8 variable Fieldbus Indicator Issue 3...

Page 4: ...6 4 2 List configured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source address 6 4 6 Enter destination address 6 4 7 Enter Index 6 4 8 Decimal poi...

Page 5: ...of this manual describes ATEX design and installation requirements for BA444NDF P applications in flammable gas atmospheres System design and installation requirements for ATEX dust and for IECEx gas...

Page 6: ...ustrial gases 3 3 Fieldbus connection The BA444NDF P Indicator is powered and communicates via the fieldbus which is connected to terminals 1 and 2 These terminals are non polarised comply with the Fi...

Page 7: ...may be connected to any Type nL certified associated apparatus irrespective of its Io providing Uo of the Type nL certified associated apparatus is equal to or less than 36V which is the Ui of the BA4...

Page 8: ...erminal should be connected to the potential equalising network as recommenced in EN 60079 14 The BA444NDF P enclosure is supplied with a bonding plate to ensure electrical continuity between the thre...

Page 9: ...7 Fig 3 Dimensions and terminal connections...

Page 10: ...rating the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button...

Page 11: ...BA444NDF P listener are not known In the SCAn function pressing the P button causes the BA444NDF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecima...

Page 12: ...10...

Page 13: ...meters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected inpu...

Page 14: ...source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a...

Page 15: ...red position omit it or activate all the decimal points which automatically provides maximum resolution in the display mode irrespective of the numeric value When positioned as required operating the...

Page 16: ...code has been selected press E to enter the selection and return to the CodE prompt in the configuration menu The revised access code will be activated when the transmitter is returned to the display...

Page 17: ...2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on FNICO systems but should only be performed on non FNICO systems when there is no ri...

Page 18: ...new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA444NDF P can be supplied with a blank or custom...

Page 19: ...yer on BA444NDF P 175 C up to 5mm thick Dust layer on BA444NDF over 5mm thick Refer to EN 61241 14 At an ambient temperature between 20 and 60 C A1 2 Certification Label Information The certification...

Page 20: ...st for a short time Be used with gases in groups Group A propane Group B ethylene Group C hydrogen Having a temperature classification of T1 450 C T2 300 C T3 200 C T4 135 C At an ambient temperature...

Page 21: ...on BA444NDF P 175 C up to 5mm thick Dust layer on BA444NDF P Refer to over 5mm thick IEC 61241 14 At an ambient temperature between 20 and 60 C The IECEx certificate may be downloaded from www beka co...

Reviews: