1.  DESCRIPTION

The BA444NDF-P fieldbus indicator is a Type n,
PROFIBUS PA instrument that may be configured
as a fieldbus node or as a fieldbus listener. It can
display up to eight fieldbus process variables on a
five digit LCD and a 31 segment analogue
bargraph.   The instrument is bus powered so no
additional power supply is required and has
PROFIBUS PA User Organisation approval,
certificate Z01505.

Fieldbus node configuration may be performed by
either a User PRM data download or by a DPV1
configurator, and if required, the instrument
address may be entered via the front panel push
buttons.

When configured as a fieldbus listener, the
BA444NDF-P is not visible to the fieldbus host and
can only be configured using the push buttons on
the front of the instrument.

Housed in a robust IP66 glass reinforced polyester
(GRP) enclosure with a toughened glass window,
the BA444NDF-P is surface mounting, or may be
pipe mounted using one of the accessory kits.

The indicator is ATEX Group II Category 3G
certified for use in Zone 2 explosive gas
atmospheres.   The indicator also has IECEx Type
nL approval for international applications.

For use in combustible dust atmospheres the
BA444NDF-P has ATEX and IECEx Ex tD dust
certification.   See Appendix 1 for details of ATEX
dust certification and Appendix 2 for IECEx
certification.

The instrument’s communication protocol is shown
on a label inside the terminal cover.  The ‘-P’ order
code suffix also indicates the protocol but is not
shown on the instrument certification label.
There is an alternative version of the fieldbus
display, order code BA444NDF-F for use on
FOUNDATION™ fieldbus networks.

1.1

  

Documentation

The main body of this manual describes ATEX
design and installation requirements for
BA444NDF-P applications in flammable gas
atmospheres.   System design and installation
requirements for ATEX dust and for IECEx gas
and dust applications are shown in appendices to
this manual.

For additional node configuration information
please refer to the 

BEKA PROFIBUS PA Display –

Fieldbus Interface Guide

 which is available from

the BEKA sales office, or may be downloaded from
www.beka.co.uk

2.  OPERATION

The BA444NDF-P indicator can display up to eight
pre-configured PROFIBUS PA process variables
designated in-1 to in-8.   The operator can select
which variable is displayed using the 

and 

push buttons which scroll the display through the
eight inputs.   A numeric annunciator on the left
hand side of the display shows which of the eight
inputs is currently being displayed.

2.1  Error messages

‘no ConF’

No inputs have been
configured or are enabled.

‘no dAtA’

No data is being received
with the current configuration.

3.  Type nL CERTIFICATION

3.1 ATEX certificate

The BA444NDF-P has been issued with a Type
Examination Certificate by Notified Body Intertek
Testing and Certification Ltd (ITS) confirming
compliance with the European ATEX Directive
94/9/EC for Group II, Category 3GD equipment.
The instrument bears the Community Mark and,
subject to local codes of practice, may be installed
in any of the European Economic Area (EEA)
member countries.  ATEX certificates are also
acceptable for installations in Switzerland.

This manual describes ATEX installations in
explosive gas atmospheres  which conform with
EN 60079:Part14 Electrical Installation in
Hazardous Areas.  When designing systems for
installation outside the UK, the local Code of
Practice should be consulted.

For use in the presence of combustible dust,
please refer to Appendix 1 that describes ATEX
installations complying with EN 61241-14.

Summary of Contents for BA444NDF-P

Page 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA444NDF P...

Page 2: ...anehill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 44 0...

Page 3: ...Issue 3 4th march 2014 BA444NDF P PROFIBUS PA Type n Field mounting 8 variable Fieldbus Indicator Issue 3...

Page 4: ...6 4 2 List configured input parameters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source address 6 4 6 Enter destination address 6 4 7 Enter Index 6 4 8 Decimal poi...

Page 5: ...of this manual describes ATEX design and installation requirements for BA444NDF P applications in flammable gas atmospheres System design and installation requirements for ATEX dust and for IECEx gas...

Page 6: ...ustrial gases 3 3 Fieldbus connection The BA444NDF P Indicator is powered and communicates via the fieldbus which is connected to terminals 1 and 2 These terminals are non polarised comply with the Fi...

Page 7: ...may be connected to any Type nL certified associated apparatus irrespective of its Io providing Uo of the Type nL certified associated apparatus is equal to or less than 36V which is the Ui of the BA4...

Page 8: ...erminal should be connected to the potential equalising network as recommenced in EN 60079 14 The BA444NDF P enclosure is supplied with a bonding plate to ensure electrical continuity between the thre...

Page 9: ...7 Fig 3 Dimensions and terminal connections...

Page 10: ...rating the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button...

Page 11: ...BA444NDF P listener are not known In the SCAn function pressing the P button causes the BA444NDF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecima...

Page 12: ...10...

Page 13: ...meters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected inpu...

Page 14: ...source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a...

Page 15: ...red position omit it or activate all the decimal points which automatically provides maximum resolution in the display mode irrespective of the numeric value When positioned as required operating the...

Page 16: ...code has been selected press E to enter the selection and return to the CodE prompt in the configuration menu The revised access code will be activated when the transmitter is returned to the display...

Page 17: ...2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on FNICO systems but should only be performed on non FNICO systems when there is no ri...

Page 18: ...new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA444NDF P can be supplied with a blank or custom...

Page 19: ...yer on BA444NDF P 175 C up to 5mm thick Dust layer on BA444NDF over 5mm thick Refer to EN 61241 14 At an ambient temperature between 20 and 60 C A1 2 Certification Label Information The certification...

Page 20: ...st for a short time Be used with gases in groups Group A propane Group B ethylene Group C hydrogen Having a temperature classification of T1 450 C T2 300 C T3 200 C T4 135 C At an ambient temperature...

Page 21: ...on BA444NDF P 175 C up to 5mm thick Dust layer on BA444NDF P Refer to over 5mm thick IEC 61241 14 At an ambient temperature between 20 and 60 C The IECEx certificate may be downloaded from www beka co...

Reviews: