28
6.22 External reset:
E clr
The BA384NG total displays can be remotely reset
to zero when terminals RS1 and RS2 are connected
together for more than one second. See sections
3.7 and 4.3 This function defines which totals are
reset.
To check or change which totals are reset, select
E clr
from the configuration menu and press
(
which will reveal the existing setting. Using the
&
or
*
button select the required option:
clr anb
to reset total A and total b
clr a
to reset total A
clr b
to reset total b
When the required optioned is displayed press
)
to
save the selection and return to the
E
.
clr
prompt in
the configuration menu.
6.23 Grand total reset from configuration
menu:
CLr Gtot
The grand total is a separate sixteen digit counter
which is incremented in parallel with the composite
total input A+b or input A-b, but is not zeroed when
the two individual totals input A and input b are reset
to zero. The grand total may be viewed with the
instrument in the totalising mode as two eight digit
sections as described in section 2.2 of this manual.
The grand total can be reset to zero from within the
configuration menu using this
CLr Gtot
function, or
from the totalising mode if sub-function
Clr gtot
is
activated in the
loc clr
function – see 6.21.
To zero the grand total from within the configuration
menu select
CL . Gtot
and press
(
which will cause
the instrument to display
Clr . No
with
no
flashing.
Press the
&
or
*
push button until
Clr
.
YE5
is
displayed and then press
(
which will result in a
0000
prompt being displayed with the first digit
flashing. This is a request for the instruction to be
confirmed by entering
5urE
using the
&
or
*
button to adjust the flashing digit and the
(
button
to move control to the next digit. When entered
pressing
)
will reset the grand total to zero and
return the Rate Totaliser to the configuration menu.
Note:
Once reset, the grand total can not be
recovered.
6.24 Security code:
CodE
Access to the instrument configuration menu may be
protected by a four digit alphanumeric security code
which must be entered to gain access. Unless
otherwise requested, new instruments are
configured with the default security code
0000
which
allows unrestricted access to all configuration
functions.
To enter a new security code select
CodE
from the
configuration menu and press
(
which will cause
the Rate Totaliser to display
0000
with one digit
flashing. The flashing digit may be adjusted using
the
&
or
*
push button, when set as required
operating the
(
button will transfer control to the
next digit. When all the digits have been adjusted
press
)
to save the new code and return to the
CodE
prompt in the configuration menu. The revised
security code will be activated when the Rate
Totaliser is returned to the totalising mode.
Please contact BEKA associates sales department if
the security code is lost.
6.25 Reset to factory defaults:
r5et def
This function resets the BA384NG Rate Totaliser
including the two linearisers, to the factory default
configurations which are shown in section 6.0
To reset the Rate Totaliser to the factory default
configurations select
r5Et def
from the configuration
menu and press
(
which will result in a
0000
display with the first digit flashing. This is a request
to confirm the reset to factory default instruction by
entering
5urE
. Using the
&
or
*
button set the
flashing digit to
5
and press
(
to transfer control to
the second digit which should be set to
u
. When
5urE
has been entered, pressing the
)
button will
reset the BA384NG to the factory defaults and return
the instrument to the totalising mode.