9.4.8

Enable Control output 1:   

EnbL

This is a sub-function in the Control output 1 function

oP1

 which allows output 1 to be enabled or disabled

without changing any of the 

on

 or 

off

 times and also

determines whether output 1 turns 

on

 and 

off 

once or

twice in each twenty four hour period.

Select 

oP1

  in the configuration menu and press 

(

which will result in the 

EnbL

 prompt being displayed.

Pressing 

(

  again will enter the sub-function from

which   one   of   the   three   options   may   be   selected
using the 

*

 or 

&

 button:

Display

Control output 1

oFF

Control output 1 disabled

on : 1

Turns 

on

 & 

off

  once per 24 hours

on : 2

Turns 

on

 & 

off

  twice per 24 hours

When the required option is displayed operating 

)

will enter the selection and return to the 

EnbL

 prompt

from which another sub-function may be selected if
control output 1 has not been disabled.

9.4.9

On

 and 

off 

 times: 

oP 1 : on 1

;   

oP 1 : off 1

oP 1 : on 2

;   

oP 1 : off 2

The control output will have one or two  

on

  and  

off

times depending upon whether control output 1 has
been configured to turn  

on

  and  

off

  once or twice in

each 24 hour period. - see 9.4.8.

All of the times are adjusted in the same way.   To
adjust any of them select 

oP1

 from the configuration

menu   and   press 

(

  which   will   result   in   the  

EnbL

prompt being displayed.   The 

*

  or 

&

  button will

scroll through the sub-functions.  Only 

oP 1

 

:

 

on 1

 and

oP1

 

:

 

oFF1

 will be present if control output 1 has been

configured to switch  

on

  and  

off

  once in a 24 hour

period in the 

EnbL

 sub-function.

Select the required sub-function

oP1

 

:

 

on1

Time oP1 turns 

on

 first time

oP1

 

:

 

oFF1

Time oP1 turns 

off

 first time

oP1

 

:

 

on2

Time oP1 turns 

on

 second time

oP1

 

:

 

oFF2

Time oP1 turns 

off

 second time

When selected, pressing 

(

  will show the existing

time with the hours flashing.     Using the 

*

  or 

&

button adjust the hours and then press 

(

 to transfer

control to the minutes display, pressing 

(

 again will

transfer control to the seconds display.     When the
time has been set as required press 

)

 to return to

the sub-menu from which another 

on

 / 

off

 time may

be selected for adjustment.     When all the  

on

  /  

off

times have been entered, return to the configuration
menu by pressing the 

)

 button twice.

9.4.10 Control output 2 (Optional):  oP2

Control output 2 is an optional factory fitted output
which can be configured to turn  

on

  (output closed)

and 

off

 (output open) twice in each twenty-four hour

period.  The control output status is shown by the 2
control output display annunciator.

Function 

oP2

  contains   a   sub-menu   with   five   sub-

functions:

EnbL

Number of times output 2
turns 

on 

&

 off 

in 24 hours.

oP 2

 

:

 

on 1

First time when oP 2 turns 

on

 (closes)

oP 2

 

:

 

oFF 1

First time when oP 2 turns 

off

 (opens)

oP 2

 

:

 

on 2

 

Second time when oP 2 turns 

on

 (closes)

oP 2

 

:

 

oFF 2

 

Second time when oP 2 turns 

off

 (opens)

To check or change the function of Control output 2
select 

oP2

 from the configuration menu and press 

(

which will reveal the first sub-funtion 

EnbL.

9.4.11 Enable control output 2:   

EnbL

This is a sub-function in the Control output 2 function

oP2

 which allows output 2 to be enabled or disabled

without changing any of the 

on

 or 

off

 times and also

determines whether output 2 turns 

on

 and 

off

 once or

twice in each twenty four hour period.Select 

oP2

  in

the   configuration   menu   and   press 

(

  which   will

result in the 

EnbL

 prompt being displayed.   Pressing

(

 again will enter the sub-function from which one

of the three options may be selected using the 

*

 or

&

 button:

Display

Control output 2

oFF

Control output 2 disabled

on : 1

Turns 

on

 & 

off

 once per 24 hours

on : 2

Turns 

on

 & 

off

 twice per 24 hours

When the required option is displayed operating 

)

will enter the selection and return to the 

EnbL

 prompt

from which another sub-function may be selected if
control output 2 has not been disabled.

9.4.12

On

 and 

off 

 times:

oP2 : on 1

;   

oP2 : off 1

oP2 : on 2

;   

oP2 : off 2

The control output will have one or two  

on

  and  

off

times depending upon whether control output 2 has
been configured to turn  

on

  and  

off

  once or twice in

each 24 hour period. - see 9.4.11.

All of the times are adjusted in the same way.   To
adjust any of them select 

oP2

 from the configuration

menu   and   press 

(

  which   will   result   in   the   EnbL

prompt being displayed.   The 

*

  or 

&

  button will

scroll through the sub-functions.  Only 

oP2 : on1

 and

oP2

 

:

 

oFF1

 will be present if control output 2 has been

configured to switch  

on

  and  

off  

once in a 24 hour

period in the 

EnbL

 sub-function.

Summary of Contents for BA377E

Page 1: ...Issue 6 4th May 2021 BA377E Single input Intrinsically safe Timer or Clock Issue 6...

Page 2: ...n configured as a Timer 6 4 Timer structure 6 5 Configuration as a Timer 6 5 1 Accessing configuration functions 6 5 2 Summary of Timer configuration functions 6 5 3 Instrument function FunCtion 6 5 4...

Page 3: ...hronising time 5YnC t 9 4 7 Control output 1 Optional oP1 9 4 8 Enable Control output 1 EnbL 9 4 9 On and off times oP 1 on 1 oP 1 off 1 oP 1 on 2 oP 1 off 2 9 4 10 Control output 2 Optional oP2 9 4 1...

Page 4: ...arate appendixes to this manual The intrinsic safety of the instrument is unaffected by whether it is configured as a Timer or as a Clock 2 1 ATEX gas certification Notified Body Intertek Testing and...

Page 5: ...negative side is internally connected to the negative side of the power supply and the reset terminal RS2 See Fig 9 Some types of sensor that may be connected to the BA377E input such as a switch cont...

Page 6: ...ed to the BA377E energised input The sensor and wiring should be able to withstand a 500V rms insulation test to earth and the sensor should be located in the same hazardous area as the BA377E The max...

Page 7: ...tance and inductance between each set of control output terminals is Ci 24nF Li 8 H To determine the maximum permissible cable capacitance Ci should be subtracted from the maximum permitted external c...

Page 8: ...s Alternatively the sensor may be located in the safe area Fig 2 shows how an additional Zener barrier is used to transfer signals to the Timer in the hazardous area When more than one Zener barrier i...

Page 9: ...activated reed relays comply with these requirements The BA377E contains a configurable debounce circuit to prevent false triggering of the instrument Three levels of debounce protection are available...

Page 10: ...dous area which may be combined with the supply barrier so that only one package is required A diode return barrier is not suitable for this application Fig 1 illustrates how a BA377E may be reset fro...

Page 11: ...f the BA377E having the correct function may be used Fig 5 BA377E used with galvanic isolators Fig 5 illustrates the basic circuit that is used for all BA377E installations protected by galvanic isola...

Page 12: ...nput signal must fall below the lower threshold and rise above the upper threshold Sensor Switching thresholds Lower Upper Low voltage range 1 0V 3 0V High voltage range 3 0V 10 0V Proximity detector...

Page 13: ...parameters equal to or less than Uo 28V dc Io 200mA dc Po 0 84W The BA377E Timer may therefore be directly connected to and controlled by most certified intrinsically safe high level outputs The maxi...

Page 14: ...meters complying with the requirements for simple apparatus This allows the control output terminals A1 A2 and A3 A4 to be connected to almost any certified intrinsically safe circuit protected by a g...

Page 15: ...ogether with the recommended panel cut out dimensions To achieve an IP66 seal between the instrument enclosure and the instrument panel the smaller tolerance aperture must be used Although the front o...

Page 16: ...ng clamps 4 4 Scale card The BA377E s units of measurement are shown on a printed scale card in a window at the right hand side of the display The scale card is mounted on a flexible strip that is ins...

Page 17: ...rough which a scale card showing the units of measurement such as hours can be seen New instruments are fitted with a scale card showing the units of measurement specified when the instrument was orde...

Page 18: ...mer cycle can be accomplished via the front panel push buttons or by a remote contact A grand total time is maintained which can be viewed by operating the front panel push buttons It may be reset to...

Page 19: ...iguration function See 6 5 20 To reset the grand total to zero from the display mode press the buttons for ten seconds until CLr no is displayed using the or button change the display to CLr YE5 and p...

Page 20: ...lete The lines between the circles represent the event required to move the Timer between states e g to initiate timing the Timer is moved from the Reset state to the Running state by a start event Th...

Page 21: ...failure Local total reset t rE5Et on Local grand total reset Gt rE5Et oFF External reset E r5et 5td Enable control output 1 EnbL oFF Enable control output 2 EnbL oFF Optional output 6 5 1 Accessing co...

Page 22: ...ion functions When read in conjunction with Fig 14 it provides a quick aid for configuring the Timer If more detail is required each section of this summary contains a reference to a full description...

Page 23: ...12 00 Hours minutes 30 00 Minutes seconds 30 Seconds Excludes delay of optional control outputs which is always shown in seconds and the grand total which is always shown in hours Only available if 5e...

Page 24: ...l total reset r5Et EnbL When on is selected Timer is reset to zero or 5et t if timing down when the and buttons are operated simultaneously for more than 3 seconds in the display mode See section 6 5...

Page 25: ...n menu If CloC is displayed press the or button to change the setting to ELAP5E followed by the button which will result in a 0000 prompt being displayed with the first digit flashing This is a reques...

Page 26: ...1600 s 40 s Heavy 3200 s 350 s Light 400 s 5 s 6 5 7 Lower display di5P 2 The configuration of the lower display which has six 12mm high digits depend upon whether the repeat timer function CYCLE5 whi...

Page 27: ...on menu Options available are Voltage inputs or control from front panel Display Start Stop ControL 1 Input high Input low ControL 2 Input low Input high LoCAL button button Contact and open collector...

Page 28: ...28...

Page 29: ...29...

Page 30: ...o the next digit When set as required enter the selection and return to the cycl cnt prompt in the sub menu by operating the button 6 5 14 Restart delay r5t dela This sub function defines the time del...

Page 31: ...diately Continue When power is restored the Timer will continue from where it stopped without any manual intervention To check or change the function select P fail from the configuration menu and pres...

Page 32: ...examples in section 7 2 and 7 3 of this manual illustrate the use of the control outputs Further examples can be found in Application Guide AG374 which is available on the BEKA website 6 5 22 Control...

Page 33: ...select op1 dELA from the control output 1 sub menu and press which will reveal the existing delay time with one digit flashing The flashing digit can be adjusted using the or button and the button to...

Page 34: ...u When 5urE has been entered pressing the button will reset all the configuration functions and return the instrument to the display mode Note r5Et dEF does not reset the grand total to zero 7 TIMER A...

Page 35: ...ich it stopped when the start button is operated Fig 16 Control of valve in a hazardous area The required instrument configuration for this example are shown below Function Display Setting Access code...

Page 36: ...t BEKA if code is lost 8 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installed in a hazardous area...

Page 37: ...regularly checked Inspection frequency should be chosen to suit the environmental conditions 8 5 Guarantee Instruments which fail within the guarantee period should be returned to BEKA associates or o...

Page 38: ...wing initialisation the instrument will display a flashing display which is a request for the local time to be entered The clock will not start to function until a display time has been entered or the...

Page 39: ...out this manual push buttons are shown as and and legends displayed by the Clock are shown in a seven segment font as they appear on the instrument e g di5PLAY and CodE Access to the configuration men...

Page 40: ...40...

Page 41: ...rol output 1 Optional Control output 1 can turn on output closed and off output open twice in each twenty four hour period This function contains five sub function EnbL Enables output 1 and defines if...

Page 42: ...time is entered the Clock will display a flashing 00 00 00 or 00 00 for 24 hour formats or A12 00 00 or A12 00 for 12 hour formats To adjust the clock set time select 5Et from the configuration menu a...

Page 43: ...tered return to the configuration menu by pressing the button twice 9 4 10 Control output 2 Optional oP2 Control output 2 is an optional factory fitted output which can be configured to turn on output...

Page 44: ...m the display mode may be protected by a four digit alphanumeric security code which must be entered to gain access Default security code 0000 allows unrestricted access With ACCd displayed press to e...

Page 45: ...will then change the instrument to a Clock and return the display to FunCtion in the configuration menu Step 3 Select display format Using the or button select di5PLAY in the configuration menu and pr...

Page 46: ...cess to the configuration menu Using the and buttons select CodE from the configuration menu and press which will reveal 0000 with the first digit flashing This example requires the security code to b...

Page 47: ...nly certified test equipment should be used unless a gas clearance certificate is available If a BA377E fails after it has been functioning correctly as a Clock the following table may help to identif...

Page 48: ...8 11 6 Customer comments BEKA is always pleased to receive comments from customers about our products and services All communications are acknowledged and whenever possible suggestions are implemented...

Page 49: ...icate may be downloaded from www beka co uk www iecex com or requested from the BEKA sales office A1 2 Installation The IECEx intrinsic safety parameters are identical to the ATEX safety parameters de...

Page 50: ...e systems shown in sections 2 and 3 of this manual may therefore also be used for US and Canadian installations subject to compliance with the local codes of practice ETL and cETL intrinsic safety cod...

Page 51: ...51...

Page 52: ...52...

Page 53: ...53...

Page 54: ...54...

Page 55: ...55...

Page 56: ...56...

Page 57: ...57...

Page 58: ...58...

Page 59: ...59...

Page 60: ...60...

Page 61: ...61...

Page 62: ...62...

Reviews: