50
Appendix 2 ETL & cETL certification for
installations in USA and Canada
A2.0 cETL Mark
For installations in the USA and Canada, the
BA377E Timer or Clock has ETL and cETL intrinsic
safety and nonincendive approval, Control Number
4008610. Copies of the Authorisation to Mark are
available from the BEKA associates sales office and
www.beka.co.uk
A2.1 Intrinsic safety approval
The US and Canadian standards used for
assessment and certification of the BA377E are
listed on the cETL Authorisation to Mark.
Installations must comply with BEKA associates
Control Drawing CI330-52, which is attached to this
appendix.
The ETL safety parameters are the same as the
ATEX and IECEx parameters, the systems shown in
sections 2 and 3 of this manual may therefore also
be used for US and Canadian installations subject to
compliance with the local codes of practice.
ETL and cETL intrinsic safety codes
CL I Div 1 Groups A, B, C, D T5 (US IS gas, Div cert)
CL II Div 1 Groups E, F, G. CL III (US IS dust, Div cert)
CL I Zone 0 AEx ia IIC T5 Ga (US IS gas, Zone cert)
Ex ia IIC T5 Ga (Canadian IS gas, Zone cert)
-40ºC ≤ Ta ≤ +70ºC
.
A2.2 Nonincendive approval
The BA377E Timer or Clock also has ETL
nonincendive approval allowing installation in
Division 2 hazardous (classified) locations without
the need for Zener barriers or galvanic isolators.
Installations must comply with BEKA associates
Control Drawing CI330-53, which is attached to this
appendix, and with the local codes of practice.
ETL and cETL nonincendive codes US & Canada
CL I Div 2 Groups A, B, C, D T5
CL II Div 2 Groups F, G CL III Div 2
-40ºC ≤ Ta ≤ +70ºC
Summary of Contents for BA377E
Page 1: ...Issue 6 4th May 2021 BA377E Single input Intrinsically safe Timer or Clock Issue 6...
Page 28: ...28...
Page 29: ...29...
Page 40: ...40...
Page 51: ...51...
Page 52: ...52...
Page 53: ...53...
Page 54: ...54...
Page 55: ...55...
Page 56: ...56...
Page 57: ...57...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60...
Page 61: ...61...
Page 62: ...62...