Mounting
Snap-on mounting using a standard DIN rail EN 50022.
The unit is designed to allow side-by-side mounting, with an ambient temperature of < 60°C.
manual
Multifunctions timer SOZMR
microcontrollerswitched
serie 17,5 mm
article
– nr. SOZMR1 – 022203-505005
SOZMR2
– 777555
Technical data
Supply voltage A1 / A2:
230V AC
+/- 15%
A3 / A2:
24V AC/DC
+/- 15%
Frequency range:
0 / 50 ... 60Hz
Power consumption:
approx. 1.0 W ; approx. 6 VA with 230V AC
Operating mode:
continuous
Supply voltage influence:
< 0.01% over voltage range
Temperature influence:
< 0.01%/°C
Recovery time:
> 100ms
Repetitive accuracy:
0.2%
Timing range :
0,05s - 10min. (8 time ranges)
Operation indicators
Supply voltage:
LED, green
Relay in working position:
LED, yellow
Contact
Number of changeovers:
1 or 2
Contact material:
AgNi 0,15
Maximum switching voltage:
400V
Maximum switching current:
8A
Maximum switching power :
2000VA
contact live :
30 x 10
6
(mechanical)
Drop-off time of switching element:
approx. 20ms
General data
Ambient temperature:
- 25 ... + 60°C
Mounting position:
any
LVD 2006/95/EG :
61812-1
EMC Dir. 2004/108/EG :
61812-1
overvoltage category :
3 (300V)
contamination degree :
2 (250V)
Isolation : 15/16/18 -> A1/A2/A3/B1/B2
basic isolation (250V)
25/26/28 -> A1/A2/A3/B1/B2
basic isolation (250V)
15/16/18 -> 25/26/28
double isolation (250V)
Connection terminals:
Crosshead screws; M3.5 self-opening
Connection cross section:
2 x 2.5mm²
Mounting:
Symmetrical rail DIN EN 50022
Dimensions l x w x h:
90mm x 17.5mm x 69.5mm
Weight:
SOZMR1 - 96g
SOZMR2 - 104g
A2
B2
K1
15
18
A1
B1
K1
A
1
A
2
A
3
B
1
B
2
1
5
1
6 1
8
1
5
1
6 1
8
2
5
2
6 2
8
6
5
4
3
2
Time
Function
3
3
3
3
3
3
2
2
2
2
2
2
Ansprechverzögert ; On delay ; Retard á la mise sous tension
Abfallverzögert ; Off delay ; Retard au déclenchement
*
6
5
6
5
4
4
0,05 - 1s
0,15 - 3s
0,5 - 10s
1,5 - 30s
3,0 - 60s.
5,0 - 100s.
15 - 300s.
0,5 - 10min
3
2
1
3
2
1
* these function require B1and B2
X
X
X
X
B 2
1 5
A 2
1 6
1 8
B 1
A 3
A 1
X
2 8
2 5
2 6
B 2
1 5
A 2
1 6
1 8
B 1
A 3
A 1
SOZMR1 SOZMR2