When  set  as  required  pressing  the

  E

 button  will

enter the selection and return the display to the    ‘t-
rE5Et’  sub-function.    The  remote  reset  facility
described  in  section  4.2  of  this  manual  is  not
affected by the status of this local reset function.

When  enabled,  ‘Gt-rE5Et’  allows  an  operator  to
reset the BA354NE grand total to zero by operating
the 

E

 and

 

 push buttons simultaneously for at least

ten seconds.  To check the status of ‘t-rE5Et’ select
'LoC.r5Et'' from the configuration menu and press

 P.

Using  the  

  or  

  button  select  ‘Gt-rE5Et’ and

press 

P

 which will reveal if the function is turned 'on'

or 'oFF'.   Operating the 

 or 

 button will toggle

the display between the two conditions.  When set
as  required  pressing  the

  E

  button  will  enter  the

selection  and  return  the  display  to  the   ‘Gt-rE5Et’
sub-function.

6.18  Security code:  ‘CodE’

Access to the instrument configuration menu may be
protected by a four digit security code which must be
entered  to  gain  access.      New  instruments  are
configured with the default security code 0000 which
allows  unrestricted  access  to  all  configuration
functions. 

To enter a new security code select 'CodE' from the
configuration menu and press

 

P

 which will cause the

Rate Totaliser to display the existing security code
with  one  digit  flashing.   The  flashing  digit  can  be
adjusted using the 

 and

 

 push buttons, when set

as  required  operating  the  

P

  button  will  transfer

control to the next digit.   When all the digits have
been adjusted press

 

E

 to return to the ‘CodE’ prompt

in the configuration menu. The revised security code
will be activated when the Rate Totaliser is returned
to  the  display  mode.    Please  contact  BEKA
associates sales department if the security code is
lost.

6.19  Reset to factory defaults:  ‘r5Et’

This  function  enables  the  Rate  Totaliser  and  the
lineariser to be quickly returned to the factory default
configurations shown in sections 6.2 and 7.5

To reset the Rate Totaliser or lineariser select ‘r5Et’
from the configuration menu and press 

P

, the  Rate

Totaliser will display one of the reset options ‘ConF’
or ‘LtAb’.

‘ConF’

Resets the Rate Totaliser to defaults

‘LtAb’

Resets the lineariser to defaults

Using the 

 or 

 push-button select the required

sub-function  and  press  

P.

   To  prevent  accidental

resetting the request must be confirmed by entering
‘5urE’.   Using the 

 button set the first flashing digit

to ‘5’ and press  

P

 to transfer control to the second

digit which should be set to ‘u’.     When ‘5urE’ has
been  entered  pressing  the  

E

 button  will  reset  the

selected configuration menus and return the display
to the ‘r5Et’ function in the configuration menu. 

6.20  Over-range

Numerical over-range of the rate or total displays is
indicated by all the digits displaying ‘9’ and all the
decimal points flashing. 

When the total display exceeds 99999999 or            -
9999999 it will not automatically roll-over to zero and
continue counting, but the grand total will continue to
count.      If  it  is  likely  that  the  total  will  exceeds
99999999 or -9999999 the grand total, which has a
capacity of 10

16

 and –10

15

 counts, should be reset to

zero at the start of the operation.

If the total display exceeds 99999999 or -9999999
when  the  BA354NE  has  been  configured  for
bi-directional  flow,  the  total  display  will  be  locked
and will not record flow in the opposite direction to
the over-range, although the grand total will continue
to function.

19

Summary of Contents for BA354NE

Page 1: ...Issue 3 3rd July 2014 BA354NE Type nA 4 20mA loop powered field mounting Rate Totaliser Issue 3...

Page 2: ...to a new indicator 7 2 Lineariser calibration using internal reference 7 2 1 Example Adding break points to a new indicator 7 3 Lineariser error message 7 4 Under and over range 7 5 Lineariser default...

Page 3: ...strument The voltage developed across R1 which is proportional to the 4 20mA input current provides the input signal for the analogue to digital converter Each time a 4 20mA current is applied to the...

Page 4: ...n clear the grand total and Gt CLrd will be displayed to confirm the operation The instrument will then automatically return to the operating mode Selectable function in the configuration menu See sec...

Page 5: ...TEX installations in explosive gas atmospheres conforming with EN60079 14 Electrical Installations in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice...

Page 6: ...uit that defines the voltage developed between the input terminals 1 and 3 therefore the ATEX certificate does not specify a maximum safety input voltage Ui 3 4 Reset terminals The input safety parame...

Page 7: ...ous area should be individually fused and contain a means of isolation However in practice instrumentation energised by a current limited power supply or instrument that can be switched off is often c...

Page 8: ...0V rms insulation test for one minute The switch button must comply with the electrostatic requirements specified by Clause 7 of EN60079 0 and material composition defined in Clause 8 If the totaliser...

Page 9: ...ded GRP enclosure If this enclosure is not bolted to an earthed post or structure the earth terminal should be connected to the plant potential equalising conductor The enclosure is fitted with a bond...

Page 10: ...rised using the square root extractor or the 16 segment lineariser which are selectable in the instrument s FunC sub menu The rate display may then be calibrated using the CAL or 5Et functions to show...

Page 11: ...e entered using the and push buttons and the P button to move control to the next digit When the correct four digit code has been entered pressing E will cause the first parameter FunC to be displayed...

Page 12: ...on or oFF See section 6 8 dP Decimal points Positions the decimal point in the rAtE and totAL displays See section 6 9 Display Summary of function CAL Calibration of the rate display using an external...

Page 13: ...nd Gt rE5Et t rE5Et enables the total display to be reset to zero when and push buttons are operated simultaneously for more than 2 seconds Gt rE5Et enables the grand total to be reset to zero when E...

Page 14: ...14...

Page 15: ...arity with bi directional flow Use of the lineariser is described in section 7 of this instruction manual 6 5 Display resolution rE5n This function defines the resolution of the least significant disp...

Page 16: ...y and identify the lower display variable but on the larger upper display The position of the decimal point can be positioned in the same way by operating the and push buttons when set as required ent...

Page 17: ...s been activated see section 6 17 To zero the grand total from within the configuration menu select Clr Gtot and press P which will cause the instrument to display Clr no Press the or button until CLr...

Page 18: ...low rates which over long periods may result in significant totalisation errors the BA354NE rate display can be conditioned to stop totalisation when the flow rate falls below a specified clip off thr...

Page 19: ...Rate Totaliser is returned to the display mode Please contact BEKA associates sales department if the security code is lost 6 19 Reset to factory defaults r5Et This function enables the Rate Totaliser...

Page 20: ...ineariser calibration using an external current source This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required...

Page 21: ...21...

Page 22: ...llowing break point 7 1 1 Example Adding break points to a new Rate Totaliser When adding break points to a new Rate Totaliser or to a lineariser following resetting to the factory defaults using the...

Page 23: ...e E button The corresponding rate display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal th...

Page 24: ...ither the root extractor or the lineariser are required The standard linear relationship should therefore be selected With FunC displayed press P which will reveal the existing function Using the or b...

Page 25: ...the totaliser scaling factor In this example the rate display is in litres per minute but the total display is required in cubic metres 5CALE t Units of rate display Units of total display There are 1...

Page 26: ...and total flow in cubic metres with a resolution of 0 1 cubic metres Total is to be shown on the upper large display and rate on the lower smaller display Totalisation is to occur for flow rates betw...

Page 27: ...ed by risk analysis or when there is no risk of a flammable atmosphere being present If an Rate Totaliser fails after it has been functioning correctly follow the procedure shown in section 9 1 If thi...

Page 28: ...of the existing escutcheon Do not remove the original escutcheon The BA354NE Rate Totaliser can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to th...

Page 29: ...dc Ii 200mA This allows each alarm output to switch any dc circuit providing that in normal operation the maximum supply voltage is not greater than 30V and the switched current is not greater than 2...

Page 30: ...30...

Page 31: ...ted when the selected display rate or total equals the setpoint See section 10 3 6 Hi Lo Alarm function Defines the alarm function as High or Low See section 10 3 7 no nC Normally open or normally clo...

Page 32: ...y pressing the or button followed by the E button to return to the alarm menu 10 3 8 Alarm output status no nC Configures the solid state alarm output to be open no or to be closed nC in the non alarm...

Page 33: ...rate or total display depending upon which has caused the alarm alternates between the numerical value and the alarm reference ALr1 or ALr2 when the alarm output is activated If both alarm outputs ar...

Page 34: ...5Px1 or 5Px2 prompt from which the other setpoint may be selected or the Rate Totaliser may be returned to the display mode by pressing E again Notes 1 With the Rate Totaliser in the display mode dire...

Page 35: ...Separately powered backlight The separately powered backlight is a current sink which will draw a constant 35mA when the supply voltage is equal to or greater than 11V At lower supply voltages the ba...

Page 36: ...A392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel bracket s...

Page 37: ...2 flammable gas atmosheres may also be used for Zone 22 combustible dust applications The Rate Totaliser should be located where the minimum amount of dust will accumulate on the enclosure and the in...

Page 38: ...ified operating temperature of the BA354NE is 20 to 70 C At temperatures below 20 C the instrument will continue to totalise but the display will not function The specified gas and dust safety paramet...

Reviews: