When set as required pressing the
E
button will
enter the selection and return the display to the ‘t-
rE5Et’ sub-function. The remote reset facility
described in section 4.2 of this manual is not
affected by the status of this local reset function.
When enabled, ‘Gt-rE5Et’ allows an operator to
reset the BA354NE grand total to zero by operating
the
E
and
▲
push buttons simultaneously for at least
ten seconds. To check the status of ‘t-rE5Et’ select
'LoC.r5Et'' from the configuration menu and press
P.
Using the
▼
or
▲
button select ‘Gt-rE5Et’ and
press
P
which will reveal if the function is turned 'on'
or 'oFF'. Operating the
▼
or
▲
button will toggle
the display between the two conditions. When set
as required pressing the
E
button will enter the
selection and return the display to the ‘Gt-rE5Et’
sub-function.
6.18 Security code: ‘CodE’
Access to the instrument configuration menu may be
protected by a four digit security code which must be
entered to gain access. New instruments are
configured with the default security code 0000 which
allows unrestricted access to all configuration
functions.
To enter a new security code select 'CodE' from the
configuration menu and press
P
which will cause the
Rate Totaliser to display the existing security code
with one digit flashing. The flashing digit can be
adjusted using the
▲
and
▼
push buttons, when set
as required operating the
P
button will transfer
control to the next digit. When all the digits have
been adjusted press
E
to return to the ‘CodE’ prompt
in the configuration menu. The revised security code
will be activated when the Rate Totaliser is returned
to the display mode. Please contact BEKA
associates sales department if the security code is
lost.
6.19 Reset to factory defaults: ‘r5Et’
This function enables the Rate Totaliser and the
lineariser to be quickly returned to the factory default
configurations shown in sections 6.2 and 7.5
To reset the Rate Totaliser or lineariser select ‘r5Et’
from the configuration menu and press
P
, the Rate
Totaliser will display one of the reset options ‘ConF’
or ‘LtAb’.
‘ConF’
Resets the Rate Totaliser to defaults
‘LtAb’
Resets the lineariser to defaults
Using the
▲
or
▼
push-button select the required
sub-function and press
P.
To prevent accidental
resetting the request must be confirmed by entering
‘5urE’. Using the
▲
button set the first flashing digit
to ‘5’ and press
P
to transfer control to the second
digit which should be set to ‘u’. When ‘5urE’ has
been entered pressing the
E
button will reset the
selected configuration menus and return the display
to the ‘r5Et’ function in the configuration menu.
6.20 Over-range
Numerical over-range of the rate or total displays is
indicated by all the digits displaying ‘9’ and all the
decimal points flashing.
When the total display exceeds 99999999 or -
9999999 it will not automatically roll-over to zero and
continue counting, but the grand total will continue to
count. If it is likely that the total will exceeds
99999999 or -9999999 the grand total, which has a
capacity of 10
16
and –10
15
counts, should be reset to
zero at the start of the operation.
If the total display exceeds 99999999 or -9999999
when the BA354NE has been configured for
bi-directional flow, the total display will be locked
and will not record flow in the opposite direction to
the over-range, although the grand total will continue
to function.
19