background image

APPENDIX 1

A1.0  ATEX dust certification

In  addition  to  ATEX  certification  permitting
installation  in  Zone  2  gas  atmospheres  which  is
described  in  the  main  section  of  this  instruction
manual,  the  BA354NE  also  has  ATEX  Ex  tc
certification,  allowing  installion  in  Zone  22
combustible dust atmospheres.    

A1.1

Zones and Maximum Surface
Temperature

The  Rate Totaliser has been  certified  as Group  II
Category 3D Ex tc  IIIC T80ºC Dc IP66 apparatus
with a Ta of  –40ºC to +70C.  This is dust ignition
protection by enclosure complying with EN60079-31.

When  installed  as  specified  in  this  instruction
manual  and  complying  with  the  requirements  of
EN60079-14 the Rate Totaliser may be installed in:

Zone 22

explosive atmosphere in the form of a
cloud of combustible dust in air is not
likely to occur in normal operation, but
if it does occur, will only persist for a
short period.

Be used with dust in subdivisions:

IIIA

combustible flyings

IIIB

non-conductive dust

IIIC

conductive dust

Be used with dusts having a Minimum Ignition 
Temperature of:

Dust cloud

120°C

Dust layer on Rate Totaliser 

155

°

C  

up to 5mm thick. 

*

Dust layer on Rate Totaliser 

Refer to

over 5mm thick. 

*

EN60079-14

At an ambient temperature between -40 and +70°C

Note:

  The  specified  operating  temperature  of  the

BA354NE is –20 to +70ºC.  At temperatures below
–20ºC the instrument will continue to totalise but the
display will not function.

*

  Unlikely occurance in Zone 22

A1.2  Installation 

All   the   circuits   shown   in   the   main   section   of   this
manual  for  Rate  Totaliser  installations  in  Zone  2
flammable  gas atmosheres, may  also be used  for
Zone 22 combustible dust applications.    The Rate
Totaliser  should  be  located  where  the  minimum
amount of dust will accumulate on the enclosure and
the  installation  should  be  as  specified  in  this
instruction  manuals  and  comply  with  the
requirements of EN 60079-14 

Electrical installations

design, selection and erection

 

EN  60079-14,  requires  that  each  of  the  wires
entering the hazardous area should be individually
fused and contain a means of isolation.  However, in
practice  instrumentation  energised  by  a  current
limited power supply that can be switched off is often
considered adequate.

A1.3  Maintenance

Ex tc protection does not permit live maintenance,
but  when  fitted  with  an  optional  intrinsically  safe
external keypad  the  BA354NE Rate Totaliser  may
be calibrated in Zone 22 providing the terminal cover
is not removed

.

  

ENSURE PLANT SAFETY BEFORE

STARTING MAINTENANCE

The Rate Totaliser terminal and control covers
should only be removed and live maintenance
performed  when  there  is  little  risk  of  a
combustible  dust  being  present.    During
maintenance ensure that dust or water do not
enter  the  enclosure.      Before  replacing  the
control  and  terminal  covers  ensure  that  the
sealing gaskets are undamaged and free from
dirt and foreign bodies.

Routine  inspection  of

  t

he  Rate  Totaliser’s

mechanical  condition  and  removal  of  accumulated
dust  from  the  outside  of  the  enclosure  should  be
regularly  performed  and  comply  with  the
recommendations  contained  in  EN60079-17
‘Electrical  Installations  Inspections  and
Maintenance’.  The  interval  between  inspections
depends upon environmental conditions.   Removal
of flammable dust should be performed with care to
avoid creating a dust cloud.

37

Summary of Contents for BA354NE

Page 1: ...Issue 3 3rd July 2014 BA354NE Type nA 4 20mA loop powered field mounting Rate Totaliser Issue 3...

Page 2: ...to a new indicator 7 2 Lineariser calibration using internal reference 7 2 1 Example Adding break points to a new indicator 7 3 Lineariser error message 7 4 Under and over range 7 5 Lineariser default...

Page 3: ...strument The voltage developed across R1 which is proportional to the 4 20mA input current provides the input signal for the analogue to digital converter Each time a 4 20mA current is applied to the...

Page 4: ...n clear the grand total and Gt CLrd will be displayed to confirm the operation The instrument will then automatically return to the operating mode Selectable function in the configuration menu See sec...

Page 5: ...TEX installations in explosive gas atmospheres conforming with EN60079 14 Electrical Installations in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice...

Page 6: ...uit that defines the voltage developed between the input terminals 1 and 3 therefore the ATEX certificate does not specify a maximum safety input voltage Ui 3 4 Reset terminals The input safety parame...

Page 7: ...ous area should be individually fused and contain a means of isolation However in practice instrumentation energised by a current limited power supply or instrument that can be switched off is often c...

Page 8: ...0V rms insulation test for one minute The switch button must comply with the electrostatic requirements specified by Clause 7 of EN60079 0 and material composition defined in Clause 8 If the totaliser...

Page 9: ...ded GRP enclosure If this enclosure is not bolted to an earthed post or structure the earth terminal should be connected to the plant potential equalising conductor The enclosure is fitted with a bond...

Page 10: ...rised using the square root extractor or the 16 segment lineariser which are selectable in the instrument s FunC sub menu The rate display may then be calibrated using the CAL or 5Et functions to show...

Page 11: ...e entered using the and push buttons and the P button to move control to the next digit When the correct four digit code has been entered pressing E will cause the first parameter FunC to be displayed...

Page 12: ...on or oFF See section 6 8 dP Decimal points Positions the decimal point in the rAtE and totAL displays See section 6 9 Display Summary of function CAL Calibration of the rate display using an external...

Page 13: ...nd Gt rE5Et t rE5Et enables the total display to be reset to zero when and push buttons are operated simultaneously for more than 2 seconds Gt rE5Et enables the grand total to be reset to zero when E...

Page 14: ...14...

Page 15: ...arity with bi directional flow Use of the lineariser is described in section 7 of this instruction manual 6 5 Display resolution rE5n This function defines the resolution of the least significant disp...

Page 16: ...y and identify the lower display variable but on the larger upper display The position of the decimal point can be positioned in the same way by operating the and push buttons when set as required ent...

Page 17: ...s been activated see section 6 17 To zero the grand total from within the configuration menu select Clr Gtot and press P which will cause the instrument to display Clr no Press the or button until CLr...

Page 18: ...low rates which over long periods may result in significant totalisation errors the BA354NE rate display can be conditioned to stop totalisation when the flow rate falls below a specified clip off thr...

Page 19: ...Rate Totaliser is returned to the display mode Please contact BEKA associates sales department if the security code is lost 6 19 Reset to factory defaults r5Et This function enables the Rate Totaliser...

Page 20: ...ineariser calibration using an external current source This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required...

Page 21: ...21...

Page 22: ...llowing break point 7 1 1 Example Adding break points to a new Rate Totaliser When adding break points to a new Rate Totaliser or to a lineariser following resetting to the factory defaults using the...

Page 23: ...e E button The corresponding rate display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal th...

Page 24: ...ither the root extractor or the lineariser are required The standard linear relationship should therefore be selected With FunC displayed press P which will reveal the existing function Using the or b...

Page 25: ...the totaliser scaling factor In this example the rate display is in litres per minute but the total display is required in cubic metres 5CALE t Units of rate display Units of total display There are 1...

Page 26: ...and total flow in cubic metres with a resolution of 0 1 cubic metres Total is to be shown on the upper large display and rate on the lower smaller display Totalisation is to occur for flow rates betw...

Page 27: ...ed by risk analysis or when there is no risk of a flammable atmosphere being present If an Rate Totaliser fails after it has been functioning correctly follow the procedure shown in section 9 1 If thi...

Page 28: ...of the existing escutcheon Do not remove the original escutcheon The BA354NE Rate Totaliser can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to th...

Page 29: ...dc Ii 200mA This allows each alarm output to switch any dc circuit providing that in normal operation the maximum supply voltage is not greater than 30V and the switched current is not greater than 2...

Page 30: ...30...

Page 31: ...ted when the selected display rate or total equals the setpoint See section 10 3 6 Hi Lo Alarm function Defines the alarm function as High or Low See section 10 3 7 no nC Normally open or normally clo...

Page 32: ...y pressing the or button followed by the E button to return to the alarm menu 10 3 8 Alarm output status no nC Configures the solid state alarm output to be open no or to be closed nC in the non alarm...

Page 33: ...rate or total display depending upon which has caused the alarm alternates between the numerical value and the alarm reference ALr1 or ALr2 when the alarm output is activated If both alarm outputs ar...

Page 34: ...5Px1 or 5Px2 prompt from which the other setpoint may be selected or the Rate Totaliser may be returned to the display mode by pressing E again Notes 1 With the Rate Totaliser in the display mode dire...

Page 35: ...Separately powered backlight The separately powered backlight is a current sink which will draw a constant 35mA when the supply voltage is equal to or greater than 11V At lower supply voltages the ba...

Page 36: ...A392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel bracket s...

Page 37: ...2 flammable gas atmosheres may also be used for Zone 22 combustible dust applications The Rate Totaliser should be located where the minimum amount of dust will accumulate on the enclosure and the in...

Page 38: ...ified operating temperature of the BA354NE is 20 to 70 C At temperatures below 20 C the instrument will continue to totalise but the display will not function The specified gas and dust safety paramet...

Reviews: