Step 13 Reset the grand total to zero

To  reset  the  grand  total  to  zero  select
'CLr.Gtot'  from  the  configuration  menu
and  press

 

P

  which  will  cause  the

instrument  to  display  'Clr.no'.      Toggle
this to 'CLr.YES' using the 

 or 

 push

button and press 

P

 which will result in a

'0000'  prompt.    Using  the

,   and

 

buttons and the

 

P

 button to move control

to the next digit, confirm the request by
entering the password 'SurE'. Note: S is
entered as 5.    Pressing

 

E

 will then reset

the grand total counter to zero and return
the instrument to the 'CLr.Gtot' prompt in
the configuration menu.  

Step 14 Enter security code

The example requires that access to the
Rate  Totaliser  configuration  menu  is
protected by the security code 1209.  To
enter  this  code  select  ‘CodE’  from  the
configuration  menu  and  press  

P  

which

will reveal the existing security code with
one flashing digit.  Using the 

 and 

push buttons and the P button to transfer
control  between  digits  set  the  code  to
1209 and then press E to enter the code
and  return  to  ‘CodE’  prompt  in  the
configuration menu.

Step 15 Return to the Rate Totaliser operating 

mode.

Configuration is now complete, return to
the  Rate  Totaliser  operating  mode  by
pressing the 

E

 button.   

8.2  Using the internal reference

This example explains how to calibrate a BA354NE
Rate  Totaliser  using  the  instruments  internal
reference which means that it does not have to be
disconnected from the measuring loop and no test
equipment is required.

As  in  the  previous  example  the  BA354NE  Rate
Totaliser is connected to a flowmeter having a linear
output  of  20mA  at  a  flow  of  1100  litres  /  minute.
The BA354NE is required to display flow in litres per
minute  with  maximum  resolution  and  total  flow  in
cubic metres with a resolution of 0.1 cubic metres.
Total is to be shown on the upper large display and
rate on the lower smaller display.  Totalisation is to
occur  for  flow  rates  between  1  and  100%  of
maximum flow.  A security code of 1209 is required.
In the operating mode the BA354NE is required to
display  the  input current as a percentage  of span
when the  

P

 push-button is operated and operating

the 

 and  

 buttons

 

simultaneously to reset the

total display to zero.

All the configuration steps are identical to those in
the previous example except for steps 1 and 8.

Step 1

Leave the BA354NE in measurement 
loop.

It  is  not  necessary  to  remove  the
BA354NE  Rate  Totaliser  from  the
measurement loop to reconfigure it using
the  instruments  internal  references.
Throughout  the  procedure  the  loop
current must be between 4 and 20mA.

Step 8

Calibrate the rate display

Select  calibration  of  the  rate  display
using the internal reference ‘5Et’ from the
configuration  menu  and  press  

P

.  

 The

BA354NE will display ‘Zero’, pressing  

P

again  will  reveal  the  calibrated  rate
display  at  4mA  input  with  one  digit
flashing.  The 

 and 

 push buttons will

adjust the flashing digit and the  

P

 push

button  will  transfer  control  to  the  next
digit.    Enter 0000.0  and then press 

E

 to

return to the 'ZEro' prompt.  

Press the 

 button to access the ‘SPAn’

prompt and press P which will reveal the
calibrated rate display at 20mA with one
digit flashing. The 

 and 

 push buttons

will  adjust  the  flashing  digit  and  the  

P

push  button  will  transfer  control  to  the
next digit.    Enter 1100.0  and then press

E

 to return to the 'SPAn' prompt.  Finally,

press  

E

  again  to  enter  the  new  rate

calibration  and return to the ‘5et’ prompt
in the configuration menu.

Step 9

Return to the Rate Totaliser operating 
mode.

Configuration is now complete, return to
the  Rate  Totaliser  operating  mode  by
pressing the 

E

 button.

26

Summary of Contents for BA354NE

Page 1: ...Issue 3 3rd July 2014 BA354NE Type nA 4 20mA loop powered field mounting Rate Totaliser Issue 3...

Page 2: ...to a new indicator 7 2 Lineariser calibration using internal reference 7 2 1 Example Adding break points to a new indicator 7 3 Lineariser error message 7 4 Under and over range 7 5 Lineariser default...

Page 3: ...strument The voltage developed across R1 which is proportional to the 4 20mA input current provides the input signal for the analogue to digital converter Each time a 4 20mA current is applied to the...

Page 4: ...n clear the grand total and Gt CLrd will be displayed to confirm the operation The instrument will then automatically return to the operating mode Selectable function in the configuration menu See sec...

Page 5: ...TEX installations in explosive gas atmospheres conforming with EN60079 14 Electrical Installations in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice...

Page 6: ...uit that defines the voltage developed between the input terminals 1 and 3 therefore the ATEX certificate does not specify a maximum safety input voltage Ui 3 4 Reset terminals The input safety parame...

Page 7: ...ous area should be individually fused and contain a means of isolation However in practice instrumentation energised by a current limited power supply or instrument that can be switched off is often c...

Page 8: ...0V rms insulation test for one minute The switch button must comply with the electrostatic requirements specified by Clause 7 of EN60079 0 and material composition defined in Clause 8 If the totaliser...

Page 9: ...ded GRP enclosure If this enclosure is not bolted to an earthed post or structure the earth terminal should be connected to the plant potential equalising conductor The enclosure is fitted with a bond...

Page 10: ...rised using the square root extractor or the 16 segment lineariser which are selectable in the instrument s FunC sub menu The rate display may then be calibrated using the CAL or 5Et functions to show...

Page 11: ...e entered using the and push buttons and the P button to move control to the next digit When the correct four digit code has been entered pressing E will cause the first parameter FunC to be displayed...

Page 12: ...on or oFF See section 6 8 dP Decimal points Positions the decimal point in the rAtE and totAL displays See section 6 9 Display Summary of function CAL Calibration of the rate display using an external...

Page 13: ...nd Gt rE5Et t rE5Et enables the total display to be reset to zero when and push buttons are operated simultaneously for more than 2 seconds Gt rE5Et enables the grand total to be reset to zero when E...

Page 14: ...14...

Page 15: ...arity with bi directional flow Use of the lineariser is described in section 7 of this instruction manual 6 5 Display resolution rE5n This function defines the resolution of the least significant disp...

Page 16: ...y and identify the lower display variable but on the larger upper display The position of the decimal point can be positioned in the same way by operating the and push buttons when set as required ent...

Page 17: ...s been activated see section 6 17 To zero the grand total from within the configuration menu select Clr Gtot and press P which will cause the instrument to display Clr no Press the or button until CLr...

Page 18: ...low rates which over long periods may result in significant totalisation errors the BA354NE rate display can be conditioned to stop totalisation when the flow rate falls below a specified clip off thr...

Page 19: ...Rate Totaliser is returned to the display mode Please contact BEKA associates sales department if the security code is lost 6 19 Reset to factory defaults r5Et This function enables the Rate Totaliser...

Page 20: ...ineariser calibration using an external current source This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required...

Page 21: ...21...

Page 22: ...llowing break point 7 1 1 Example Adding break points to a new Rate Totaliser When adding break points to a new Rate Totaliser or to a lineariser following resetting to the factory defaults using the...

Page 23: ...e E button The corresponding rate display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal th...

Page 24: ...ither the root extractor or the lineariser are required The standard linear relationship should therefore be selected With FunC displayed press P which will reveal the existing function Using the or b...

Page 25: ...the totaliser scaling factor In this example the rate display is in litres per minute but the total display is required in cubic metres 5CALE t Units of rate display Units of total display There are 1...

Page 26: ...and total flow in cubic metres with a resolution of 0 1 cubic metres Total is to be shown on the upper large display and rate on the lower smaller display Totalisation is to occur for flow rates betw...

Page 27: ...ed by risk analysis or when there is no risk of a flammable atmosphere being present If an Rate Totaliser fails after it has been functioning correctly follow the procedure shown in section 9 1 If thi...

Page 28: ...of the existing escutcheon Do not remove the original escutcheon The BA354NE Rate Totaliser can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to th...

Page 29: ...dc Ii 200mA This allows each alarm output to switch any dc circuit providing that in normal operation the maximum supply voltage is not greater than 30V and the switched current is not greater than 2...

Page 30: ...30...

Page 31: ...ted when the selected display rate or total equals the setpoint See section 10 3 6 Hi Lo Alarm function Defines the alarm function as High or Low See section 10 3 7 no nC Normally open or normally clo...

Page 32: ...y pressing the or button followed by the E button to return to the alarm menu 10 3 8 Alarm output status no nC Configures the solid state alarm output to be open no or to be closed nC in the non alarm...

Page 33: ...rate or total display depending upon which has caused the alarm alternates between the numerical value and the alarm reference ALr1 or ALr2 when the alarm output is activated If both alarm outputs ar...

Page 34: ...5Px1 or 5Px2 prompt from which the other setpoint may be selected or the Rate Totaliser may be returned to the display mode by pressing E again Notes 1 With the Rate Totaliser in the display mode dire...

Page 35: ...Separately powered backlight The separately powered backlight is a current sink which will draw a constant 35mA when the supply voltage is equal to or greater than 11V At lower supply voltages the ba...

Page 36: ...A392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel bracket s...

Page 37: ...2 flammable gas atmosheres may also be used for Zone 22 combustible dust applications The Rate Totaliser should be located where the minimum amount of dust will accumulate on the enclosure and the in...

Page 38: ...ified operating temperature of the BA354NE is 20 to 70 C At temperatures below 20 C the instrument will continue to totalise but the display will not function The specified gas and dust safety paramet...

Reviews: