6.15  Total scale factor:  ‘5CALE-t’

Together with the timebase 't-bA5E', this is a dividing
factor  that  defines  the  arithmetic  relationship
between the rate and total displays.  When the flow
rate and the total flow are required in the same units
5CALE-t = 1.0  

The  total  scale  factor  may  be  set  to  any  value
between 0.0001 and 99999 allowing the total flow
and  rate  of  flow  to  be  displayed  in  different
engineering units. 

5CALE-t  =     Units of rate display

                   Units of total display

When  calculating  5CALE-t  the  required  units  of
measurement for the total display must be converted
to those used for the rate display as shown in the
following example:

The  BA354NE  rate  display  represents  litres  per
second but the total flow display is required in UK
gallons.   There are 4.5461 litres in a UK gallon.

5CALE-t   =    Units of rate display
                        Units of total display

       =            1 litre 

                              1 gallon

=           1 litre          

  

           1 / 4.5461 litres

5CALE-t   =    4.5461
  

                   

Alternatively,  if  the  total  display  is  required  in
thousand of UK gallons

=           1 litre          

  

           1 / 4546.1 litres

5CALE-t   =    4546.1

The total scale factor 5CALE-t is not dependent on
the  rate  display  units  of  time.  i.e.  flow  units  per
second, minute or per hour.  The timebase t-bA5E
accounts for these differences.
To  check  or  change  the  total  scale  factor  select
'5CALE-t' from the configuration menu and press  

P

to  reveal  the  existing  setting,  one  digit  will  be
flashing.    The  value  of  the  flashing  digit  may  be
changed by pressing the 

 or 

 button.  When this

digit is set as required pressing 

P

 will transfer control

to the next digit, which may be adjusted in the same
way.   

To position the decimal point, repeatedly operate the

P

 button until the decimal point starts flashing.  The

decimal point can then be positioned by pressing the

 or 

 button.  

When the required total scale factor has been set,
press  

E   t

o  enter  the  number  and  return  to  the

‘5CALE-t’ prompt in the configuration menu.

6.16  Clip-off:  ‘CLiP-oFF’

To prevent totalisation of very low flow rates, which
over  long  periods  may  result  in  significant
totalisation errors, the BA354NE rate display can be
conditioned  to  stop totalisation  when the  flow  rate
falls below a specified clip-off threshold.    Clip-off is
an  absolute  value,  for  bi-direction  flow  systems  it
inhibits  totalisation  for flow  rates bclip-off
and –clip-off.  

Clip-off  is  shown  in  the  same  units  as  the
instruments  rate  display.  To  check  or  change  the
clip-off  threshold  select  'CLiP-oFF'  from  the
configuration menu and press 

P

 to reveal the current

level, one digit will  be flashing.   The  value of the
flashing digit may be changed by pressing the 

 or

 button.  When this digit is set as required pressing

P

 will transfer control to the next digit, which may be

adjusted in the same way.    When set as required,
press the

 E

 button to enter the revised threshold and

return to the ‘CliP-oFF’ prompt in the configuration
menu.

For  uni-directional  flow  when  the  flow  rate  falls
below the clip-off threshold, totalisation is inhibited,
the  hold  annunciator  is  activated  but  the  flow
indicator continues to rotate until the input current
falls below 4mA.

For bi-directional flow when the positive or negative
flow rate is less than the absolute clip-off threshold,
totalisation is inhibited and the hold annunciator is
activated.  The flow indicator continues to rotate until
the low rate is less than ±0.05% of flow rate display
span.

6.17 Local reset of total and grand total.
         ‘LoC. R5Et’

This  function  contains  two  sub-functions  ‘t-rE5Et’
and ‘Gt-rE5Et’ which allow the total display and the
grand  total  to  be  independently  reset  using  the
instrument  push  buttons  without  access  to  the
configuration menu from the operating mode. 

When enabled, ‘t-rE5Et’ allows an operator to reset
the BA354NE total display to zero by operating the

 and

 

 push buttons simultaneously for at least

two  seconds.        To  check  the  status  of  ‘t-rE5Et’
select 'LoC.r5Et''  from  the configuration  menu  and
press

 P.

   Using the 

 or 

 button select ‘t-rE5Et’

and press 

P

 which will reveal if the function is turned

'on'  or  'oFF'.     Operating  the  

 or  

 button  will

toggle the display between the two conditions.

18

Summary of Contents for BA354NE

Page 1: ...Issue 3 3rd July 2014 BA354NE Type nA 4 20mA loop powered field mounting Rate Totaliser Issue 3...

Page 2: ...to a new indicator 7 2 Lineariser calibration using internal reference 7 2 1 Example Adding break points to a new indicator 7 3 Lineariser error message 7 4 Under and over range 7 5 Lineariser default...

Page 3: ...strument The voltage developed across R1 which is proportional to the 4 20mA input current provides the input signal for the analogue to digital converter Each time a 4 20mA current is applied to the...

Page 4: ...n clear the grand total and Gt CLrd will be displayed to confirm the operation The instrument will then automatically return to the operating mode Selectable function in the configuration menu See sec...

Page 5: ...TEX installations in explosive gas atmospheres conforming with EN60079 14 Electrical Installations in Hazardous Areas When designing systems for installation outside the UK the local Code of Practice...

Page 6: ...uit that defines the voltage developed between the input terminals 1 and 3 therefore the ATEX certificate does not specify a maximum safety input voltage Ui 3 4 Reset terminals The input safety parame...

Page 7: ...ous area should be individually fused and contain a means of isolation However in practice instrumentation energised by a current limited power supply or instrument that can be switched off is often c...

Page 8: ...0V rms insulation test for one minute The switch button must comply with the electrostatic requirements specified by Clause 7 of EN60079 0 and material composition defined in Clause 8 If the totaliser...

Page 9: ...ded GRP enclosure If this enclosure is not bolted to an earthed post or structure the earth terminal should be connected to the plant potential equalising conductor The enclosure is fitted with a bond...

Page 10: ...rised using the square root extractor or the 16 segment lineariser which are selectable in the instrument s FunC sub menu The rate display may then be calibrated using the CAL or 5Et functions to show...

Page 11: ...e entered using the and push buttons and the P button to move control to the next digit When the correct four digit code has been entered pressing E will cause the first parameter FunC to be displayed...

Page 12: ...on or oFF See section 6 8 dP Decimal points Positions the decimal point in the rAtE and totAL displays See section 6 9 Display Summary of function CAL Calibration of the rate display using an external...

Page 13: ...nd Gt rE5Et t rE5Et enables the total display to be reset to zero when and push buttons are operated simultaneously for more than 2 seconds Gt rE5Et enables the grand total to be reset to zero when E...

Page 14: ...14...

Page 15: ...arity with bi directional flow Use of the lineariser is described in section 7 of this instruction manual 6 5 Display resolution rE5n This function defines the resolution of the least significant disp...

Page 16: ...y and identify the lower display variable but on the larger upper display The position of the decimal point can be positioned in the same way by operating the and push buttons when set as required ent...

Page 17: ...s been activated see section 6 17 To zero the grand total from within the configuration menu select Clr Gtot and press P which will cause the instrument to display Clr no Press the or button until CLr...

Page 18: ...low rates which over long periods may result in significant totalisation errors the BA354NE rate display can be conditioned to stop totalisation when the flow rate falls below a specified clip off thr...

Page 19: ...Rate Totaliser is returned to the display mode Please contact BEKA associates sales department if the security code is lost 6 19 Reset to factory defaults r5Et This function enables the Rate Totaliser...

Page 20: ...ineariser calibration using an external current source This method allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required...

Page 21: ...21...

Page 22: ...llowing break point 7 1 1 Example Adding break points to a new Rate Totaliser When adding break points to a new Rate Totaliser or to a lineariser following resetting to the factory defaults using the...

Page 23: ...e E button The corresponding rate display at each of the break points can now be defined using the diSP sub function Using the and buttons select the diSP sub function and press P which will reveal th...

Page 24: ...ither the root extractor or the lineariser are required The standard linear relationship should therefore be selected With FunC displayed press P which will reveal the existing function Using the or b...

Page 25: ...the totaliser scaling factor In this example the rate display is in litres per minute but the total display is required in cubic metres 5CALE t Units of rate display Units of total display There are 1...

Page 26: ...and total flow in cubic metres with a resolution of 0 1 cubic metres Total is to be shown on the upper large display and rate on the lower smaller display Totalisation is to occur for flow rates betw...

Page 27: ...ed by risk analysis or when there is no risk of a flammable atmosphere being present If an Rate Totaliser fails after it has been functioning correctly follow the procedure shown in section 9 1 If thi...

Page 28: ...of the existing escutcheon Do not remove the original escutcheon The BA354NE Rate Totaliser can also be supplied with a blank or custom laser engraved stainless steel plate secured by two screws to th...

Page 29: ...dc Ii 200mA This allows each alarm output to switch any dc circuit providing that in normal operation the maximum supply voltage is not greater than 30V and the switched current is not greater than 2...

Page 30: ...30...

Page 31: ...ted when the selected display rate or total equals the setpoint See section 10 3 6 Hi Lo Alarm function Defines the alarm function as High or Low See section 10 3 7 no nC Normally open or normally clo...

Page 32: ...y pressing the or button followed by the E button to return to the alarm menu 10 3 8 Alarm output status no nC Configures the solid state alarm output to be open no or to be closed nC in the non alarm...

Page 33: ...rate or total display depending upon which has caused the alarm alternates between the numerical value and the alarm reference ALr1 or ALr2 when the alarm output is activated If both alarm outputs ar...

Page 34: ...5Px1 or 5Px2 prompt from which the other setpoint may be selected or the Rate Totaliser may be returned to the display mode by pressing E again Notes 1 With the Rate Totaliser in the display mode dire...

Page 35: ...Separately powered backlight The separately powered backlight is a current sink which will draw a constant 35mA when the supply voltage is equal to or greater than 11V At lower supply voltages the ba...

Page 36: ...A392D Stainless steel bracket secured by two worm drive hose clips Will clamp to any vertical or horizontal pipe with an outside diameter between 60 and 80mm BA393 Heavy duty stainless steel bracket s...

Page 37: ...2 flammable gas atmosheres may also be used for Zone 22 combustible dust applications The Rate Totaliser should be located where the minimum amount of dust will accumulate on the enclosure and the in...

Page 38: ...ified operating temperature of the BA354NE is 20 to 70 C At temperatures below 20 C the instrument will continue to totalise but the display will not function The specified gas and dust safety paramet...

Reviews: