background image

10

7.3  Servicing

CAUTION!

ENSURE PLANT SAFETY BEFORE

STARTING MAINTENANCE

Live maintenance should only be
performed when there is no risk of a
flammable atmosphere being present,
and dust or water can not enter the
enclosure.  Before replacing enclosure
cover ensure that the sealing gasket is
undamaged and free from dirt and
foreign bodies.

To simplify servicing, all ATEX certified BA304NC
indicators use a common indicator assembly which
may be replaced on site.  All ATEX certified
BA304NC indicator assemblies without
accessories are interchangeable.

To replace the indicator assembly remove the
three 'B' screws shown in Fig 4 which will allow the
assembly to be removed.   If the instrument is fitted
with a backlight the fly-lead connecting it to the
terminals must be un-plugged.  The replacement
indicator assembly may then be installed and the
enclosure reassembled.

Please note that an ATEX certified BA304NC
indicator assembly must not be replaced by a non
ATEX certified BA304NC assembly.  The product
code label on all ATEX certified indicator
assemblies carry the legend ‘ATEX’.

If after replacement of the indicator assembly the
instrument still does not function, it is likely that the
fault is within the protection components on the
terminal assembly.   Terminal assemblies may also
be replaced on site providing that an instrument
with a backlight is fitted with a replacement board
including terminals 12 and 13.

We recommend that faulty instruments
and instrument assemblies are returned
to BEKA associates or your local BEKA
agent for repair.

7.4  Routine maintenance

The mechanical condition of the instrument and
the electrical calibration should be regularly
checked.  The interval between inspections
depends upon environmental conditions.   We
recommend that initially instrument calibration
should be checked annually.

7.5  Guarantee

Indicators which fail within the guarantee period
should be returned to BEKA associates or your
local BEKA agent.  It is helpful if a brief description
of the fault symptoms is provided.

7.6  Customer comments

BEKA associates is always pleased to receive
comments from customers about our products and
services.  All communications are acknowledged
and whenever possible, suggestions are
implemented.

Summary of Contents for BA304NC

Page 1: ...Issue 5 11th November 2009 BA304NC Type nL Loop powered 3 digit field mounting indicator issue 5...

Page 2: ...al point 6 4 Reverse action 6 5 Calibration example 6 6 Over and under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine mainte...

Page 3: ...ly constant is multiplied by a switch mode power supply and used to power the analogue to digital converter and liquid crystal display The voltage developed across R1 which is proportional to the 4 20...

Page 4: ...erminals 1 and 3 may be safely connected in series with any 4 20mA loop providing that in normal operation the input current to the indicator does not exceed 40mA 3 4 Certification Label Information T...

Page 5: ...5V 4 2 Remote indication A BA304NC indicator may be driven from a 4 20mA safe area signal to provide a remote indication within a Zone 2 hazardous area Fig 3 shows a typical application in which the o...

Page 6: ...cable entries and install Ex e or Ex n certified glands conduit fittings or blanking plugs e Connect the field wiring to the terminals as shown in Fig 5 f Replace the indicator assembly and evenly ti...

Page 7: ...e between Elevation 0 and 1000 Suppression 0 and 1000 Zero link Position Display with 4mA input adjustable between 0 to 500 0 and 500 500 to 1000 500 to 1000 6 2 Span adjustment Span is defined as the...

Page 8: ...ed in front of the least significant digit therefore the decimal point link should be placed in the 00 0 position Step 5 With 4 000mA input adjust the zero potentiometer until the indicator displays 2...

Page 9: ...Fault finding after commissioning CAUTION ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance should only be performed when there is no risk of a flammable atmosphere being present and d...

Page 10: ...all ATEX certified indicator assemblies carry the legend ATEX If after replacement of the indicator assembly the instrument still does not function it is likely that the fault is within the protectio...

Page 11: ...ntiometer should not be used to set the display to zero with a 4mA input Zero suppression or elevation may not be used i e 4mA must correspond to zero flow For reference the following table shows the...

Page 12: ...s less than 30V dc in normal operation the backlight safety components will ensure that the maximum input current and power are within the safety limits Fig 8 Separately powered backlight Reducing the...

Reviews: