background image

4

3.2  Zones, Gas Groups and T rating

The BA304NC has been certified as Group II,
Category 3G apparatus as defined in the ATEC
Directive and as Ex nL IIC T5 Tamb -40 to 60

o

C.

‘L’ indicates that the BA304NC uses an energy-
limiting technique to achieve compliance as
defined in EN 60079-15.  This technique is based
on the philosophy of 

intrinsic safety

 which limits the

current and voltage applied to components which
may generate a spark in normal operation.  e.g.
switches and potentiometers

These approvals confirm that the BA304NC is safe
in normal operation and may be:

Installed in a Zone 2 hazardous area

At ambient temperatures between
-40 to 60

o

C.

Used in gase groups:

Group A

propane

Group B

ethylene

Group C

hydrogen

Having a temperature classification of:

T1

450ºC

T2

300ºC

T3

200ºC

T4

135ºC

T5

100ºC

Although certified safe in normal operation at
ambient temperatures between –40 and  +60ºC,
the  guaranteed operating temperature range of
the BA304NC is –20 to +60ºC.

This allows the BA304NC indicator to be installed
in a Zone 2 low risk hazardous area and to be
used with most common industrial gases.

3.3  Input parameters

Input terminals 1 and 3 may be safely connected in
series with any 4/20mA loop providing that in
normal operation the input current to the indicator
does not exceed 40mA.

3.4  Certification Label Information

The certification information label is fitted on the
top outer surface of the enclosure.  It shows the
ATEX certification information plus BEKA
associates name and location.

The instrument serial number and date of
manufacture are shown on a separate label within
the instrument enclosure.

4.   SYSTEM DESIGN FOR ZONE 2

4.1 Transmitter loops

A BA304NC indicator may be connected in series
with almost any 4/20mA current loop and
calibrated to display the measured variable or
control signal in engineering units.

Fig 2 illustrates a typical application in which a
BA304NC indicator is connected in series with a 2-
wire transmitter and controller.

Fig 2  BA304NC in a transmitter loop

There are four basic design requirements:

1. 

In normal operation the voltage, current
and power applied to the terminals 1 and 3
of the BA304NC must not exceed:

Ui

=

4V

Ii

=

40mA dc

Pi

=

0.2W

Providing the maximum input current in
normal operation is less than 40mA, the
maximum voltage between the indicator
terminals and the maximum input power to
the indicator will be automatically limited to
less than the above figures by the internal
safety components.

Summary of Contents for BA304NC

Page 1: ...Issue 5 11th November 2009 BA304NC Type nL Loop powered 3 digit field mounting indicator issue 5...

Page 2: ...al point 6 4 Reverse action 6 5 Calibration example 6 6 Over and under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine mainte...

Page 3: ...ly constant is multiplied by a switch mode power supply and used to power the analogue to digital converter and liquid crystal display The voltage developed across R1 which is proportional to the 4 20...

Page 4: ...erminals 1 and 3 may be safely connected in series with any 4 20mA loop providing that in normal operation the input current to the indicator does not exceed 40mA 3 4 Certification Label Information T...

Page 5: ...5V 4 2 Remote indication A BA304NC indicator may be driven from a 4 20mA safe area signal to provide a remote indication within a Zone 2 hazardous area Fig 3 shows a typical application in which the o...

Page 6: ...cable entries and install Ex e or Ex n certified glands conduit fittings or blanking plugs e Connect the field wiring to the terminals as shown in Fig 5 f Replace the indicator assembly and evenly ti...

Page 7: ...e between Elevation 0 and 1000 Suppression 0 and 1000 Zero link Position Display with 4mA input adjustable between 0 to 500 0 and 500 500 to 1000 500 to 1000 6 2 Span adjustment Span is defined as the...

Page 8: ...ed in front of the least significant digit therefore the decimal point link should be placed in the 00 0 position Step 5 With 4 000mA input adjust the zero potentiometer until the indicator displays 2...

Page 9: ...Fault finding after commissioning CAUTION ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance should only be performed when there is no risk of a flammable atmosphere being present and d...

Page 10: ...all ATEX certified indicator assemblies carry the legend ATEX If after replacement of the indicator assembly the instrument still does not function it is likely that the fault is within the protectio...

Page 11: ...ntiometer should not be used to set the display to zero with a 4mA input Zero suppression or elevation may not be used i e 4mA must correspond to zero flow For reference the following table shows the...

Page 12: ...s less than 30V dc in normal operation the backlight safety components will ensure that the maximum input current and power are within the safety limits Fig 8 Separately powered backlight Reducing the...

Reviews: