6.5  Calibration example

The BA304NC is required to display:
            25.0  with   4.000mA input
          115.0  with 20.000mA input

i.e. A zero of positive 250 (Ignoring decimal point)
      A span of 900  (Ignoring decimal point)
      A decimal point in position 00.0

The following adjustments are required:

Step 1

The BA304NC is required to display a
positive zero therefore the suppression
/ elevation links should be put in the
elevation position.

Step 2

The required zero  is 250, therefore the
zero link should be put in the 0 to 500
position.

Step 3

The required span is 900, therefore the
span links should be placed in the  500
to 1000 position.

Step 4

The decimal point is required in front of
the least significant digit, therefore the
decimal point link should be placed in
the 00.0 position.

Step 5

With 4.000mA input adjust the zero
potentiometer until the indicator
displays 25.0

Step 6

With 20.000mA input adjust the span
potentiometer until the indicator
displays 115.0

Step 7

Repeat steps 5 and 6 until both
calibration points are correct.  The span
and zero controls are almost
independent so it should only be
necessary to repeat each adjustment
twice.

6.6  Over and under-range

If the indicator display range is exceeded, the three
least significant digits will be blanked.  Under-
range is indicated by -1 and over-range by 1.    If
the display range is not exceeded, the BA304NC
will produce accurate readings outside the 4/20mA
current range.  Although not guaranteed, most
BA304NC indicators will operate between 3 and
25mA.

Summary of Contents for BA304NC

Page 1: ...Issue 5 11th November 2009 BA304NC Type nL Loop powered 3 digit field mounting indicator issue 5...

Page 2: ...al point 6 4 Reverse action 6 5 Calibration example 6 6 Over and under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine mainte...

Page 3: ...ly constant is multiplied by a switch mode power supply and used to power the analogue to digital converter and liquid crystal display The voltage developed across R1 which is proportional to the 4 20...

Page 4: ...erminals 1 and 3 may be safely connected in series with any 4 20mA loop providing that in normal operation the input current to the indicator does not exceed 40mA 3 4 Certification Label Information T...

Page 5: ...5V 4 2 Remote indication A BA304NC indicator may be driven from a 4 20mA safe area signal to provide a remote indication within a Zone 2 hazardous area Fig 3 shows a typical application in which the o...

Page 6: ...cable entries and install Ex e or Ex n certified glands conduit fittings or blanking plugs e Connect the field wiring to the terminals as shown in Fig 5 f Replace the indicator assembly and evenly ti...

Page 7: ...e between Elevation 0 and 1000 Suppression 0 and 1000 Zero link Position Display with 4mA input adjustable between 0 to 500 0 and 500 500 to 1000 500 to 1000 6 2 Span adjustment Span is defined as the...

Page 8: ...ed in front of the least significant digit therefore the decimal point link should be placed in the 00 0 position Step 5 With 4 000mA input adjust the zero potentiometer until the indicator displays 2...

Page 9: ...Fault finding after commissioning CAUTION ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance should only be performed when there is no risk of a flammable atmosphere being present and d...

Page 10: ...all ATEX certified indicator assemblies carry the legend ATEX If after replacement of the indicator assembly the instrument still does not function it is likely that the fault is within the protectio...

Page 11: ...ntiometer should not be used to set the display to zero with a 4mA input Zero suppression or elevation may not be used i e 4mA must correspond to zero flow For reference the following table shows the...

Page 12: ...s less than 30V dc in normal operation the backlight safety components will ensure that the maximum input current and power are within the safety limits Fig 8 Separately powered backlight Reducing the...

Reviews: