background image

5

2.

Apparatus in safe area must not be
supplied from nor contain under normal
conditions a source of potential with
respect to earth in excess of 250V rms or
250V dc.

3.

Both M20 entries must be fitted with an Ex
e or Ex n certified cable gland or blanking
plug.

4.

The 4/20mA loop must be able to tolerate

the additional 1.1V required to operate the
indicator.

CAUTION !

The enclosure cover should only be
removed when the measuring loop is not
energised, or when there is no risk of a
flammable atmosphere being present and
dust or water can not enter the
enclosure.  Before replacing the
enclosure cover ensure that the sealing
gasket is undamaged and that it is free
from dirt and foreign bodies.

In practice it is only necessary to ensure that in
normal operation the maximum current flowing in
the 4/20mA loop is less than 40mA.   Fig 2 shows
a temperature measuring loop in which the
maximum current in normal operation is defined by
the maximum output from the Type n transmitter.

The sum of the maximum voltage drops of all the
components in the loop must be less than the
minimum power supply voltage.  Considering the
example shown in Fig 2.

Minimum operating voltage of 2-wire Tx

10.0

Maximum voltage drop caused by controller

5.0

Maximum voltage drop caused by BA304NC

1.1

Maximum voltage drop caused by cables

0.4

                                                                           _____

16.5V

Therefore at 20mA the power supply in this
example must have an output greater than 16.5V

4.2  Remote indication

A BA304NC indicator may be driven from a
4/20mA safe area signal to provide a remote
indication within a Zone 2 hazardous area.   Fig 3
shows a typical application in which the output
from a gas analyser drives a BA304NC.  Again it is
necessary to ensure that the loop complies with
the three design requirements listed in section 4.1.

Fig 3  Remote indication

5. INSTALLATION

5.1 Location

The BA304NC indicator can be supplied in either a
glass reinforced polyester (GRP), or an epoxy
painted aluminium enclosure.    Both provide IP66
protection and have a polycarbonate window and
stainless steel fittings.  The GRP enclosure is
suitable for most industrial installations including
off-shore and waste water treatment applications.
For installations where solvents may be present,
the aluminium enclosure provides maximum
protection, but it is not recommended for offshore
applications.

Both enclosures are surface mounting, but may be
pipe or panel mounted using the accessory kits
described in section 8 of this manual.

To simplify installation, the enclosure can be
installed and the field wiring terminated prior to the
indicator assembly being fitted.  The enclosure
contains diodes to maintain continuity of the
4/20mA loop when the indicator assembly is not
present.    Terminals 2 and 4 are internally joined
and may be used for linking the return 4/20mA wire
- see Fig 2.   Similarly, terminals 5 and 6 are
internally joined and may be used for linking the
cable screens.   Terminal 7 is internally connected
to an insulated radio frequency screen in the GRP
enclosure, and to the case in the aluminium
enclosure .

Summary of Contents for BA304NC

Page 1: ...Issue 5 11th November 2009 BA304NC Type nL Loop powered 3 digit field mounting indicator issue 5...

Page 2: ...al point 6 4 Reverse action 6 5 Calibration example 6 6 Over and under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine mainte...

Page 3: ...ly constant is multiplied by a switch mode power supply and used to power the analogue to digital converter and liquid crystal display The voltage developed across R1 which is proportional to the 4 20...

Page 4: ...erminals 1 and 3 may be safely connected in series with any 4 20mA loop providing that in normal operation the input current to the indicator does not exceed 40mA 3 4 Certification Label Information T...

Page 5: ...5V 4 2 Remote indication A BA304NC indicator may be driven from a 4 20mA safe area signal to provide a remote indication within a Zone 2 hazardous area Fig 3 shows a typical application in which the o...

Page 6: ...cable entries and install Ex e or Ex n certified glands conduit fittings or blanking plugs e Connect the field wiring to the terminals as shown in Fig 5 f Replace the indicator assembly and evenly ti...

Page 7: ...e between Elevation 0 and 1000 Suppression 0 and 1000 Zero link Position Display with 4mA input adjustable between 0 to 500 0 and 500 500 to 1000 500 to 1000 6 2 Span adjustment Span is defined as the...

Page 8: ...ed in front of the least significant digit therefore the decimal point link should be placed in the 00 0 position Step 5 With 4 000mA input adjust the zero potentiometer until the indicator displays 2...

Page 9: ...Fault finding after commissioning CAUTION ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance should only be performed when there is no risk of a flammable atmosphere being present and d...

Page 10: ...all ATEX certified indicator assemblies carry the legend ATEX If after replacement of the indicator assembly the instrument still does not function it is likely that the fault is within the protectio...

Page 11: ...ntiometer should not be used to set the display to zero with a 4mA input Zero suppression or elevation may not be used i e 4mA must correspond to zero flow For reference the following table shows the...

Page 12: ...s less than 30V dc in normal operation the backlight safety components will ensure that the maximum input current and power are within the safety limits Fig 8 Separately powered backlight Reducing the...

Reviews: