12

Step 6

With 20.000mA input current adjust the
span potentiometer until the indicator
displays 140.0

Step 7

Repeat steps 5 and 6 until both
calibration points are correct.

8.3  Display backlight

The BA304NC can be supplied with LED
backlighting to improve display contrast in poorly
illuminated areas.  This backlight is electrically
segregated from the measuring circuit and has
been certified as a separate Ex nL Group II,
Category 3G circuit.

The Type n input safety parameters ae:

Ui

=       30V dc

Ii

=       100mA

Pi

=       1.3W

This allows the backlight to be powered from a
safe area 18 to 30V dc supply as shown in Fig 8.
Providing the supply voltage is less than 30V dc in
normal operation the backlight safety components
will ensure that the maximum input current and
power are within the safety limits.

Fig 8  Separately powered backlight

Reducing the supply voltage below 18V will reduce
the backlight brilliance.

8.4  Pipe mounting kits

Two pipe mounting kits are available for securing
the BA304NC to a horizontal or vertical pipe.

BA392C Stainless steel bracket secured by two

worm drive hose clips.  For 60 to 80mm
outside diameter pipes.

BA393

Heavy duty stainless steel bracket
secured by a single 'V' bolt.  Will clamp
to any pipe with an outside diameter
between 40 and 80mm.

8.5  Panel mounting kit

The BA394 stainless steel panel mounting kit will
secure a BA304NC indicator into a panel aperture,
but it does not seal the joint between the indicator
enclosure and the instrument panel.

Summary of Contents for BA304NC

Page 1: ...Issue 5 11th November 2009 BA304NC Type nL Loop powered 3 digit field mounting indicator issue 5...

Page 2: ...al point 6 4 Reverse action 6 5 Calibration example 6 6 Over and under range 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine mainte...

Page 3: ...ly constant is multiplied by a switch mode power supply and used to power the analogue to digital converter and liquid crystal display The voltage developed across R1 which is proportional to the 4 20...

Page 4: ...erminals 1 and 3 may be safely connected in series with any 4 20mA loop providing that in normal operation the input current to the indicator does not exceed 40mA 3 4 Certification Label Information T...

Page 5: ...5V 4 2 Remote indication A BA304NC indicator may be driven from a 4 20mA safe area signal to provide a remote indication within a Zone 2 hazardous area Fig 3 shows a typical application in which the o...

Page 6: ...cable entries and install Ex e or Ex n certified glands conduit fittings or blanking plugs e Connect the field wiring to the terminals as shown in Fig 5 f Replace the indicator assembly and evenly ti...

Page 7: ...e between Elevation 0 and 1000 Suppression 0 and 1000 Zero link Position Display with 4mA input adjustable between 0 to 500 0 and 500 500 to 1000 500 to 1000 6 2 Span adjustment Span is defined as the...

Page 8: ...ed in front of the least significant digit therefore the decimal point link should be placed in the 00 0 position Step 5 With 4 000mA input adjust the zero potentiometer until the indicator displays 2...

Page 9: ...Fault finding after commissioning CAUTION ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance should only be performed when there is no risk of a flammable atmosphere being present and d...

Page 10: ...all ATEX certified indicator assemblies carry the legend ATEX If after replacement of the indicator assembly the instrument still does not function it is likely that the fault is within the protectio...

Page 11: ...ntiometer should not be used to set the display to zero with a 4mA input Zero suppression or elevation may not be used i e 4mA must correspond to zero flow For reference the following table shows the...

Page 12: ...s less than 30V dc in normal operation the backlight safety components will ensure that the maximum input current and power are within the safety limits Fig 8 Separately powered backlight Reducing the...

Reviews: