GT-650/GT-900 User's Manual
64
Figure 48: AUTO-TEST display after pressing the START key (example, TC# 145 was
selected as an attribute to the appliance code)
1 ...... “
” menu key, to move the cursor down in order to check the set of
tests to be done.
2 ...... “
” menu key, to move the cursor up in order to check the set of
tests to be done.
3 ...... Protection class of selected AUTO-TEST. The PC is fixed for all factory-
programmed AUTO-TESTS.
4 ...... Name of the AUTO-TEST (it can be freely edited in MENU / AUTO-TEST /
EDIT/VIEW menu, 11 characters max.).
5 ...... TC# (Test code) / AUTO-TEST code (fixed for factory-programmed AUTO-
TESTS).
6 ...... Tests, test parameters and limit values. Here are some explanations of
possible test parameters below:
R
PE 0.2
C .... Measurement current 0.2 A (0.2) / 5 A (5.0)
R
PE 0.2
C .... Test lead compensated (C) / not compensated (blank)
R
INS LO
........ Measurement voltage 250 V (LO) / 500 V (HI)
I
PE
A
........ Phase connected to the right ( ) / left ( ) terminal of mains
socket
I
PE
A
........ Actual value (A) / max. value (M) displayed
Actual value can be changed to max. value by pressing the
“MAX” menu key during the measurement or after
finishing it. Actual value will be displayed after finishing
the measurement in any case.
I
T
A
......... Phase connected to the right ( ) / left ( ) terminal of mains
socket
I
T
A
......... Actual value (A) / max. value (M) displayed
Actual value can be changed to max. value by pressing the
“MAX” menu key during the measurement or after
finishing it. Actual value will be displayed after finishing
the measurement in any case.
LO
A ... Measurement range 0 … 20 mA (LO) / 0 … 60 A (HI)
LO
A ... Actual value (A) / max. value (M) displayed
Actual value can be changed to max. value by pressing the
“MAX” menu key during the measurement or after finishing it.
Actual value will be displayed after finishing the measurement
in any case.
R
INS
I .......... Measurement will be done on input (I) / output side (O)
of tested PRCD.