USER MANUAL FOR BEEM OUTDOORS, LLC. 20KW
SILENT STANDBY GENERATOR SET
22
DO NOT open the generator enclosure top while the generator is running. DO NOT
open the control box cover while the generator is running.
ONLY check on electrical or mechanical functions when the generator IS NOT
running.
V. Operating the Generator
If the generator will not start, press the emergency stop switch. Rotate clockwise to
pop up. After waiting for 30 seconds, try to starting again. If the generator cannot be
started, check the generator carefully for loose wires, battery voltage, gas flow to the
lines and generator, etc…
If after restarting the generator, the fault indicator light is red, the generator will shut
down. If this happens, check the reason for the fault occurring. After correcting the fault,
the generator is able to be re-started. If the fault indicator light remains off, then the
generator is operating normally.
Confirm after starting that the normal electrical output range is not exceeded as this
will damage the generator.
After generator has been run for the first time for more than few minutes, shut the
generator engine down and check the following items to make sure that all is in good
working condition.
1. Radiator (coolant level)
To avoid injury:
DO NOT remove the radiator cap until the engine has cooled down. Loosen and
unscrew the radiator cap slowly to avoid any unexpected overflows of hot coolant as
severe burns can occur if excessively hot engine coolant touches your skin.
If while running the engine temperature is high, you may notice an overflow of the
engine coolant from the radiator to the surface below. If this happens, check the
following:
Check for any engine coolant leaks.
Check for any air intake blockage limiting air flow to the generator.
Check for excess dirt or debris blocking any part of the radiator.
Check for kinks or damage to the engine coolant lines going to and from the radiator.
2. Fault light indicator
If illuminated red, this is a warning that the engine or generator is not operating
correctly or has stopped. If this light is red, shut down the generator and check for
problems that may have occurred.