Technical data
EPI3174-0002
ERI3174-0002
Communication
IO-Link
Data transfer rate
230.4 kBaud (COM 3)
IO-Link connection
1 x M12 connector, a-coded
Specification version
IO-Link V1.1, Class B
Requirements for IO-Link
master
V1.1
Number of inputs
4
4 x M12 socket, screwable
Connection technology
two-wire, four-wire
Signal type
Configurable:
0 V…+10 V
-10 V…+10 V
0 mA…20 mA
4 mA…20 mA
Internal resistance
> 200 kΩ (typ. 85 Ω + diode voltage)
Common-mode voltage
U
CM
max. 35 V
Resolution
16 bit (including sign)
Input filter
Configurable
Input filter limit frequency 5 kHz
Conversion time
~ 100 µs
Measuring error
< ±0.3 % (relative to full scale value)
Number of outputs
0
Current consumption of
the module circuitry
typically 100 mA from L
+
Supply of the module
electronics
L
+
Sensor supply
2L
+
, DC, freely selectable up to 30 V
Process image
Inputs: 4 x 16 bit, status: 4 x 16 bit
Electrical isolation
L
+
/2L
+
: yes
Housing
Industrial housing (polyamide PA6)
Die-cast zinc housing
Weight
typ. 165 g
typ. 250 g
Permissible ambient
temperature during
operation
-25°C ... +60°C
Permissible ambient
temperature during
storage
-40°C ... +85°C
Vibration / shock
resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity / emission conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP65, IP66, IP67 (conforms to EN 60529)
See also chapter
General operating conditions [
Installation position
variable
Approvals
CE, UL