Commissioning/configuration of IO-Link master/device
EPI3xxx, ERI3xxx
73
Version: 1.2
5.3.6
EPI31xx, ERI31xx - Setting of the IO-Link device parameters
5.3.6.1
Selection of the analog signal type, index 0x3800:0n
In delivery state, all channels of the EPI31x4, ERI31x4 are set for analog voltage measurement (-10 V …
+10 V).
Setting the correct signal type before connecting the sensors
Set the correct signal type before connecting the sensors!
This setting can be set individually for each channel in parameter 0x3800:0n (see the figure below). Changes
become effective immediately after writing the parameter.
Fig. 79: Selection of the analog signal type