Commissioning and configuration
EP9300-0022
26
Version: 2.3
5
Commissioning and configuration
5.1
IP address
The EP9300-0022 has no predefined IP address. The IP address can be assigned by one of the following
network devices:
• Profinet controller (normal case)
• DHCP server
On rotary switch S1, set the network device that should assign the IP address:
Fig. 13: Rotary switch S1
S1
Source of the IP address
1
DHCP server
3
Profinet controller
5.2
Profinet name
The Profinet name of the EP9300-0022 is "EP9300-xxx". "xxx" is a decimal number between 1 and 255,
which you can set via the rotary switches S2 and S3. The rotary switches are hexadecimally coded:
• S2 sets the higher-value nibble.
• S3 sets the lower-value nibble.
Fig. 14: Rotary switches S2 and S3
S2
S3
Profinet name
0
1
EP9300-001
0
2
EP9300-002
0
3
EP9300-003
…
…
…
1
0
EP9300-016
…
…
…
F
F
EP9300-255
Summary of Contents for EP9300-0022